Analysis of Harmonic Improvement in the Computer Laboratory of Samarinda State Polytechnic with the Addition of a Static VAR Compensator

Rizky Aprylianto, Susilo; Geofany, Valdano; Hari, Subagyo; Wahyu, Setiawan

Abstract

Abstract : An electrical system is said to have a high level of reliability if it is capable of supplying electrical energy continuously and in accordance with user needs. The quality of electrical power can be disrupted by the use of non-linear loads, such as computer devices, electronic devices, and energy-saving lamps. Harmonic problems in power quality arise due to the interaction between the sinusoidal waves of the system and the characteristics of non-linear loads, such as those found in the Computer Laboratory of the Samarinda State Polytechnic, which results in high harmonic current values. To determine the actual conditions, electrical parameters were measured. The results of the measurements showed a total current harmonic distortion value of 33.65% in phase R, 15.85% in phase S, and 92.99% in phase T. The individual current harmonic distortion in phase R decreased from 28.39% to 4.53%, to 3.76% in phase S, and to 2.63% in phase T on Thursday at 15:00 WITA. To overcome this, the use of a Static Var Compensator (SVC) is proposed as a solution to reduce the level of harmonics in the electrical system at the Computer Laboratory of the Samarinda State Polytechnic. The simulation was conducted using Matlab R2023a software through the Simulink feature. The results obtained show that the Static Var Compensator can reduce harmonics well, as seen from the harmonic values on Thursday, where before the Static Var Compensator was installed, the harmonics in phase R were 9.81%, phase S were 10.98%, and phase T were 9%.

Full text

International Journal of Current Science Research and Review ISSN: 2581-8341 Volume 08 Issue 11 November 2025 DOI: 10.47191/ijcsrr/V8-i11-38, Impact Factor: 8.048 IJCSRR @ 2025 www.ijcsrr.org 5816 *Corresponding Author: Rizky Aprylianto Susilo Volume 08 Issue 11 November 2025 Available at: www.ijcsrr.org Page No. 5816-5835 Analysis of Harmonic Improvement in the Computer Laboratory of Samarinda State Polytechnic with the Addition of a Static VAR Compensator Rizky Aprylianto Susilo1, Geofany Valdano2, Hari Subagyo3, Wahyu Setiawan4 1,2,3,4 Department of Electrical Engineering, Samarinda State Polytechnic ABSTRACT: An electrical system is said to have a high level of reliability if it is capable of supplying electrical energy continuously and in accordance with user needs. The quality of electrical power can be disrupted by the use of non-linear loads, such as computer devices, electronic devices, and energy-saving lamps. Harmonic problems in power quality arise due to the interaction between the sinusoidal waves of the system and the characteristics of non-linear loads, such as those found in the Computer Laboratory of the Samarinda State Polytechnic, which results in high harmonic current values. To determine the actual conditions, electrical parameters were measured. The results of the measurements showed a total current harmonic distortion value of 33.65% in phase R, 15.85% in phase S, and 92.99% in phase T. The individual current harmonic distortion in phase R decreased from 28.39% to 4.53%, to 3.76% in phase S, and to 2.63% in phase T on Thursday at 15:00 WITA. To overcome this, the use of a Static Var Compensator (SVC) is proposed as a solution to reduce the level of harmonics in the electrical system at the Computer Laboratory of the Samarinda State Polytechnic. The simulation was conducted using Matlab R2023a software through the Simulink feature. The results obtained show that the Static Var Compensator can reduce harmonics well, as seen from the harmonic values on Thursday, where before the Static Var Compensator was installed, the harmonics in phase R were 9.81%, phase S were 10.98%, and phase T were 9%. KEYWORDS: harmonisa, matlab/simulink, Static Var Compensator. I. INTRODUCTION A complete electric power system is classified into generation, transmission, and distribution for easy control and to maintain a reliable and stable system. Utility networks operate depending on generation systems that differ in type, such as conventional or renewable power plants, or a combination of renewable and conventional systems.[1]. The quality of electrical power is influenced by several factors, including voltage, current, frequency, power loss, power factor, harmonics, and grounding systems. Electrical power is said to be of good quality if the voltage, current, and frequency values remain stable in a particular network. However, in practice, these three parameters are not always stable. [2]. Harmonics are periodic distortions that appear in voltage and current waveforms composed of a number of sine waves with frequencies that are integer multiples of the fundamental frequency. As a result of this frequency composition, the waveform becomes less than a pure sine wave. The presence of harmonic distortion can cause losses in electrical systems. [3]. A transformer is an electrical device that functions to transfer and convert electrical energy from one circuit or more to another electrical circuit through magnetic coupling, utilizing the principle of electromagnetic induction. In the industrial world, transformers are used to increase voltage (step-up transformers) and decrease voltage (step-down transformers). [4]. An electrical load is the amount of electrical energy consumed by equipment or devices used in an electrical power system. In general, electrical loads are divided into several types, such as resistive loads (e.g., lights and heaters), inductive loads (e.g., electric motors), and capacitive loads (e.g., capacitors). These loads are very important because they affect the performance and stability of the electrical power system. [5]. Based on the background discussion above, a study was conducted entitled “Analysis of Harmonic Improvement with the Addition of a Static Var Compensator at the Computer Laboratory of the Samarinda State Polytechnic”. International Journal of Current Science Research and Review ISSN: 2581-8341 Volume 08 Issue 11 November 2025 DOI: 10.47191/ijcsrr/V8-i11-38, Impact Factor: 8.048 IJCSRR @ 2025 www.ijcsrr.org 5817 *Corresponding Author: Rizky Aprylianto Susilo Volume 08 Issue 11 November 2025 Available at: www.ijcsrr.org Page No. 5816-5835 II. LITERATURE REVIEW A. General Overview This section discusses the analysis of a number of previous studies that are relevant to the issues in this study. The findings from these studies were used as a starting point in designing this study. One of the references used was a journal article by Motlanthe and Muremi entitled “Application of Static Var Compensator with Harmonic Filter in the Heavy Industry”. This journal discusses the application of Static Var Compensator (SVC) equipped with harmonic filters in the heavy industry sector, particularly mining. The study shows that the use of SVC with harmonic filters can improve power quality by improving the power factor and reducing harmonic distortion at the interconnection point. The results of the study indicate a significant decrease in the Total Harmonic Distortion (THD) value after the installation of the SVC system with filters, proving that this technology is effective in addressing power quality issues in industrial environments. [6]. Research conducted by Gede Kresna Dharma Yudha in his thesis entitled “Simulation of Shunt Active Filter Use with PI Control to Reduce Total Harmonic Distortion (THD) in the Electrical Engineering Building at Udayana University” discusses the application of shunt active filters as a solution to reduce harmonic interference caused by the use of non-linear loads, such as computers, lights, and air conditioners. The study explains that harmonic resonance can cause distortion to increase by 4 to 10 times under full load conditions, thus requiring an effective mitigation strategy. Using simulations on MATLAB Simulink software, the active shunt filter controlled using PI control successfully reduced the Total Harmonic Distortion of current (THDi) from the initial condition, which exceeded the IEEE 519-2014 standard limit, ranging from 14.73% to 13.53%, to 3.29% to 4.53%. Meanwhile, the Total Harmonic Distortion voltage (THDv) value in the system has been within the standard limit since the beginning of testing. These results indicate that the use of an active shunt filter with PI control is effective in suppressing harmonics and improving the quality of electrical power in building installations. [7]. Then, research written by Onur Turan, entitled “Modeling a Static Var Compensator consisting of TCR and TSC,” discusses modeling simulation systems using Matlab/Simulink applications to reveal the benefits of Static Var Compensators. Based on the research conducted, it shows that static var compensators can provide stable voltage regulation, correct poor power factors, prevent the need for reactive power sources from the network, and prevent unnecessary power increases, thereby reducing additional costs. Through modeling and simulation using Matlab/Simulink software, this research provides deeper knowledge about the role and usefulness of static var compensators in optimizing the performance of electrical power systems. This research is used as a reference for this thesis to model electrical systems using Matlab/Simulink software. [8]. B. Harmonic Harmonics are a type of distortion in periodic current, voltage, or power waves, consisting of sinusoidal waves with frequencies that are integer multiples of the fundamental frequency or source frequency, resulting in waveforms that are no longer purely sinusoidal. Harmonics can be defined as interference frequencies that are multiples of the fundamental wave frequency. These waves ride on the fundamental wave and cause the formation of an imperfect waveform, which is the result of a combination of the fundamental wave and the harmonic distortion waves. [9]. especially to the equipment connected to it. The presence of harmonics can cause various effects, increasing the temperature of electrical equipment. [10]. A sinusoidal wave with a frequency that is an integer multiple of the fundamental frequency of the system, where the first harmonic is 50 Hz, the second harmonic has a frequency twice the fundamental frequency, namely 100 Hz, and the third harmonic has a frequency three times the fundamental frequency, namely 150 Hz. [11]. Based on the above description, the sum waveform of the harmonic frequencies can be observed in Figure 1. International Journal of Current Science Research and Review ISSN: 2581-8341 Volume 08 Issue 11 November 2025 DOI: 10.47191/ijcsrr/V8-i11-38, Impact Factor: 8.048 IJCSRR @ 2025 www.ijcsrr.org 5818 *Corresponding Author: Rizky Aprylianto Susilo Volume 08 Issue 11 November 2025 Available at: www.ijcsrr.org Page No. 5816-5835 Voltage (V) or Current (I) Fundamental Wave Third Harmonic Fundamental + Third Harmonic t (s) x y Figure 1 Harmonic waves The fundamental wave with a frequency of 50 Hz is the base frequency of a periodic signal. This wave has the simplest sinusoidal shape and is the main part of the signal. In the illustration, the black wave represents a pure sinusoidal current wave without harmonic mixing. Meanwhile, the third harmonic wave, which has a frequency of 100 Hz, is three times the fundamental frequency. This wave has a more complex shape and has the potential to interfere with the original signal if not handled properly. This wave is visualized in yellow, where it is the result of a combination between the fundamental wave and the third harmonic (fundamental + third harmonic) with a frequency of 150 Hz, producing a new, more complex waveform. This sum wave is shown in red. [11]. C. Individual Harmonic Distortion (IHDi) Individual Harmonic Distortion (IHD), also known as harmonic factor (FH), is the ratio between the RMS value of a particular harmonic component and the average value of the fundamental component (first order). [12]. Based on the above description, the IHDi formula is written in the following equation(1). 𝐼𝐻𝐷𝑖 (%)=𝐼ℎ 𝐼1 x 100% (1) Description : 𝐼𝐻𝐷𝑖 = Individua Harmonic Distortion Current (%) 𝐼ℎ = Current Harmonic Component – h in RMS (I) 𝐼1 = Current at Fundamental Frequency in RMS (I) h = Harmonic Order to – D. Total Demand Distortion (TDD) 𝑇𝐻𝐷𝑖=√∑=2 𝑰ℎ 2∞ ℎ𝑰L x 100% (2) E. Standard Limit To Harmonic Harmonic standardization is a guideline that refers to a harmonic limit in an electrical network system with the aim of preventing things that are detrimental to the system itself. The standard used is IEEE std 519-2014, which is a recommended guideline for harmonic control in electrical power systems. This standard aims to assist in designing efficient and reliable electrical systems for both linear and non-linear loads. It describes various possible current waveforms that can appear throughout the system. This standard also sets the desired wave distortion limits as a reference in system design. Furthermore, IEEE 519-2014 regulates the power quality that must be met at the point where the power source is connected to the load. [13].The limits for individual current harmonic distortion given in Table 1, which is the IEEE std 519-2014 standard, are as follows: International Journal of Current Science Research and Review ISSN: 2581-8341 Volume 08 Issue 11 November 2025 DOI: 10.47191/ijcsrr/V8-i11-38, Impact Factor: 8.048 IJCSRR @ 2025 www.ijcsrr.org 5819 *Corresponding Author: Rizky Aprylianto Susilo Volume 08 Issue 11 November 2025 Available at: www.ijcsrr.org Page No. 5816-5835 Table I. Harmonic Current Distortion Limits According To Ieee 519 2014 Standard [13]. To determine the THD current limit, the short circuit ratio (〖SC〗_ratio) must be calculated using the equation(3). 𝑆𝐶𝑟𝑎𝑡𝑖𝑜 = 𝐼𝑆𝐶 𝐼𝐿 (3) Description: I_SC = Short-circuit current at a specific point in the electrical power system. I_L = Nominal load current in the system. However, before calculating the short circuit ratio (〖SC〗_ratio) or the ratio between short circuit capacity and load current, it is necessary to first calculate the short circuit current value at a specific point in the electrical power system and the nominal load current in the system using equations (4) and (5) as follows : 𝐼𝑆𝐶 = 𝑘𝑉𝐴×100 √3×𝑘𝑉×𝑍 (4) Description : S_trafo = Transformer Power Capacity (kVA) Z = Transformer Impedance (%) V = (Volt) F. Static Var Compensator (SVC) A Static Var Compensator (SVC) is an electrical device used to provide fast reactive power compensation in high-voltage power transmission networks. SVCs are part of flexible AC transmission systems that serve to regulate voltage and stabilize the system. The term “static” refers to the fact that there are no moving parts in an SVC during operation or when making compensation changes, as the entire compensation process is fully controlled by a power electronics system. [14]. SVC consists of a capacitor bank controlled by a triac called a Thyristor Switched Capacitor (TSC) and a reactor bank controlled by a triac called a Thyristor Controlled Reactor (TCR). This compensator draws reactive power from the network by regulating voltage, improving stability, controlling overvoltage, and reducing voltage flickers. Because Static Var Compensators use switching for reactive power control, they are also called static VAR (reactive power) switches or systems. [15]. SVC is primarily used in power systems to improve voltage control and system stability. In recent years, many researchers have proposed techniques to improve stability with SVC to suppress electromechanical fluctuations in power systems. Generally, the SVC structure consists of a combination of a thyristor controlled reactor (TCR) and/or a thyristor switched capacitor (TSC) structure. [16]. Figure 2 shows a general schematic block diagram of the SVC control system. In this study, the static VAr compensator formed by the TCR and TSC structures is modeled. The SVC system can be seen in Figure 2. Maximum harmonic current distortion in percent of 𝑰𝑳 Individual harmonic order (𝒐𝒅𝒅 𝒉𝒂𝒓𝒎𝒐𝒏𝒊𝒄𝒔) 𝒂,𝒃 Scratio 3≤h<11 11≤h<17 17≤h<23 23≤h<35 35≤h≤50 TDD <20 4,0 2,0 1,5 0,6 0,3 5,0 20<50 7,0 3,5 2,5 1,0 0,5 8,0 50<100 10,0 4,5 4,0 1,5 0,7 12,0 100<1000 12,0 5,5 5,0 2,0 1,0 15,0 >1000 15,0 7,0 6,0 2,5 1,4 20,0 International Journal of Current Science Research and Review ISSN: 2581-8341 Volume 08 Issue 11 November 2025 DOI: 10.47191/ijcsrr/V8-i11-38, Impact Factor: 8.048 IJCSRR @ 2025 www.ijcsrr.org 5820 *Corresponding Author: Rizky Aprylianto Susilo Volume 08 Issue 11 November 2025 Available at: www.ijcsrr.org Page No. 5816-5835 Thyristor Switched Capasitor (TSC) Thyristor Controlled Reacctor (TCR) Harmonic Filter Mechanically Switched Reactor Mechanically Switched Reactor Step down Transformer Grid Connection Figure 2 Static Var Compensator System Configuration 1) Main Component Of SVC In an elecrical power system, an svc consists of several core components that play an important role in regulating reactive power. The main components that from part of a Static Var Compensator (SVC) are: 1. Thyristor Controlled Reactor (TCR) TCR is an element that functions to control the inductive reactor in the SVC. By adjusting the thyristor firing angle, this component can control the amount of inductive reactive power absorbed by the system. 2. Thyristor Switched Capacitor (TSC) TSC utilizes thyristors to connect or disconnect capacitors from the system. These components function to gradually generate capacitive reactive power through controlled switching techniques. 3. Thyristor Switched Reactor (TSR). TSC uses thyristors to connect or disconnect capacitors from the system. TSC is used to gradually generate inductive reactive power using a switching method. 4. Harmonic Filter Harmonic filters serve to minimize or reduce harmonic distortion caused by SVC control devices such as TCR, TSC, and TSR. Harmonic filters consist of a combination of resistors, inductors, and capacitors that are specifically designed to reduce harmonic content in the system. III. RESEARCH METHOD A. Place And Time Research The research was conducted at the Samarinda State Polytechic by collecting data on the electrical system of the Samarinda State polytechnic Computer Laboratory. The research was conducted from January to June 2025. B. Types and Sources of Data Data collection methods are writing techniques used to gather comprehensive, accurate, and easily understandable data and information about activities related to the implementation of a thesis. In this study, quantitative data was used, involving measurements and calculations. The data collected consiste of several power quality parameters, such as voltage, current, frequency, and harmonics. C. Research Of Stage The research preparation stage is the initial design stage related to Harmonic Reduction in the electrical system of the Computer Laboratory at the Samarinda State Polytechnic. This stage includes the preparation of a research framework, formulation of International Journal of Current Science Research and Review ISSN: 2581-8341 Volume 08 Issue 11 November 2025 DOI: 10.47191/ijcsrr/V8-i11-38, Impact Factor: 8.048 IJCSRR @ 2025 www.ijcsrr.org 5821 *Corresponding Author: Rizky Aprylianto Susilo Volume 08 Issue 11 November 2025 Available at: www.ijcsrr.org Page No. 5816-5835 hypotheses, operationel definitions and measurement of variables, as well as the research format in the from of , methods and operational framework activities. The research implementation period is from March 18, 2025, to March 21, 2025. D. Toold And Equipment Table 2 lists several instruments and equipment used in this study. Table 2 Equipment and Materials E. Research Operation Flowchart mulai Penelitian pendahuluan • Studi Literatur • Studi kasus Pengumpulan data: • Data Refrensi • Data Lapangan Mengolah data • Data Lapangan • PQ ONE • Matlab R2023a • Microsoft office Pemodelan sistem • Perancangan Rangkaian Listik dan Static Var Compensator Apakah Harmonisa sesuai standar? Hasil dan Pembahasan Hasil Penelitian Selesai Perbaikan Simulasi Static Var Compensator Hasil Studi Pustaka Tidak Ya Simulasi Rangkaian Figure 3 Operational Research Flowchart Figure 3 shows a flowchart of the research operational framework that serves to describe the stages of research in a systematic and structured manner. This diagram simplifies the issues until the analysis and conclusion drawing process.. The diagram shown in Figure 3 simplifies the problem to the process of analysis and conclusion drawing. It can be seen that the research began with an introduction containing literature studies and case studies, followed by data collection in the form of No Tool Material 1 Laptop Juornal Reference 2 Matlab Simulink Software IEEE Std 519-2014 3 PQ One Software 4 Microsoft Office Software 5 Power Quality Analyser (PQA) International Journal of Current Science Research and Review ISSN: 2581-8341 Volume 08 Issue 11 November 2025 DOI: 10.47191/ijcsrr/V8-i11-38, Impact Factor: 8.048 IJCSRR @ 2025 www.ijcsrr.org 5822 *Corresponding Author: Rizky Aprylianto Susilo Volume 08 Issue 11 November 2025 Available at: www.ijcsrr.org Page No. 5816-5835 reference data and field data. The field data itself consisted of load types and power quality parameters found in the Computer Laboratory, with power quality measurement data collected using a Power Quality Analyzer (PQA) measuring device. After conducting circuit simulation tests and observing the harmonic values before and after using the Static Var Compensator, the research can proceed to the results and discussion if the values have reached the nominal standard limits for sudden voltage drops and surges. If the nominal limits have not been reached, then the Static Var Compensator will be remodeled and the simulation will be repeated. After that, the results of the Static Var Compensator and electrical system modeling simulation will be discussed, along with a discussion of power quality parameters in the Computer Laboratory. The final part of the research concludes with a summary of the research results. F. Data Collection Stage Next, the data collection stage involved gathering reference data, field data, and data from literature studies on Harmonisa improvements with the addition of a Static Var Compensator, as follows: 1. The data collection stage involves searching for reference data and data from literature studies related to previous research as a reference for the data needed to perform a Harmonisa improvement analysis with the addition of a Static Var Compensator.. 2. Designing comprehensive strategies and work programs aimed at improving the effectiveness and efficiency of activities, including scheduling that supports the smooth collection of data. This step also ensures anticipation of possible obstacles that may arise during the implementation of the research. 3. Then, the location survey and power quality parameter measurement stages at the Computer Laboratory with the following requirements: • Permission to collect data and monitor measuring instruments at the Computer Laboratory. • Permission to borrow a Power Quality Analyzer (PQA) measuring instrument G. Data Processing Stage The data processing stage is an activity carried out to examine the results of testing and measurement modeling to solve problems in this study. This stage includes: 1. Reference data, literature study data, and field data are analyzed using MS Office 2021 software: MS Word. The data is then input into Matlab Simulink software for SVC modeling and electrical system simulation in the Computer Laboratory. 2. The results of data processing in the form of SVC modeling and electrical systems in the Computer Laboratory are analyzed to determine the comparison of harmonics before and after mitigation H. Analysis And Discussion Stage The analysis and discussion stage involves reviewing and examining the measurement results. This stage includes: 1. For the analysis stage, the measurement data that has been input into the Matlab Simulink program is compared during the voltage transition stability with the conditions after the Static Var Compensator is installed, thereby producing a simulation model in accordance with the standard nominal harmonic parameter values specified. 2. The final stage consists of the results and discussion, which will show the research results in the form of an electrical simulation model of the Computer Laboratory, and measurement data before and after using the Static Var Compensator based on the test results and analysis using the Matlab Simulink program (software). I. Clossing Stage The final stage involves drawing conclusions in the form of a summary of the research results in the form of a simulation model based on the results of analysis and testing of harmonization improvements at the Computer Laboratory, and a summary of suggestions for further development and research. J. Data Collection Results 1) Harmonized Data International Journal of Current Science Research and Review ISSN: 2581-8341 Volume 08 Issue 11 November 2025 DOI: 10.47191/ijcsrr/V8-i11-38, Impact Factor: 8.048 IJCSRR @ 2025 www.ijcsrr.org 5823 *Corresponding Author: Rizky Aprylianto Susilo Volume 08 Issue 11 November 2025 Available at: www.ijcsrr.org Page No. 5816-5835 Table 2. Third-Order Individual Harmonic Data on Thursday at 3:00 PM Order Thursday, March 20, 2025 at 3:00 PM IHDi-f (%) R S T 3 58.34 71.90 60.37 4 25.46 42.33 28.75 5 47.42 51.02 54.05 6 10.77 17.08 14.20 7 32.33 32.86 34.54 8 7.55 11.62 6.34 9 25.81 26.33 24.48 10 4.59 10.05 5.22 11 20.95 22.09 18.58 12 3.46 6.56 3.59 13 18.38 16.95 15.59 14 3.02 5.83 2.70 15 12.46 10.64 12.34 16 2.00 4.42 2.59 17 6.95 6.11 7.23 18 1.54 3.32 1.36 19 8.82 5.67 6.94 20 1.23 3.18 1.21 21 7.04 6.30 7.34 22 1.03 2.29 1.13 23 6.54 4.65 7.88 24 0.80 2.21 0.76 25 4.44 3.64 4.48 26 0.73 1.97 0.84 27 4.44 3.72 3.94 28 0.75 1.70 0.71 29 3.91 3.18 4.76 30 0.63 1.70 0.55 31 3.46 2.31 3.77 32 0.65 1.28 0.64 33 4.18 3.06 4.07 34 0.44 1.24 0.56 35 3.90 3.05 3.20 36 0.46 1.03 0.48 37 3.76 3.17 2.54 38 0.41 0.84 0.65 39 4.68 2.10 2.27 40 0.40 0.94 0.67 41 2.77 1.43 3.85 42 0.39 0.70 0.58 43 4.20 3.19 3.19 44 0.40 0.78 0.43 45 4.19 2.93 1.37 International Journal of Current Science Research and Review ISSN: 2581-8341 Volume 08 Issue 11 November 2025 DOI: 10.47191/ijcsrr/V8-i11-38, Impact Factor: 8.048 IJCSRR @ 2025 www.ijcsrr.org 5824 *Corresponding Author: Rizky Aprylianto Susilo Volume 08 Issue 11 November 2025 Available at: www.ijcsrr.org Page No. 5816-5835 Order Thursday, March 20, 2025 at 3:00 PM IHDi-f (%) R S T 46 0.39 0.59 0.46 47 1.92 1.23 2.77 48 0.37 0.58 0.51 49 2.86 2.25 2.40 50 0.34 0.66 0.46 2) Computer Laboratory Equipment Data And 800kVA Transformer of Samarinda State Polytechnic The Samarinda State Polytechnic Computer Laboratory is equipped with various electrical equipment to support lecture activities as shown in Table 4 below Table 4. Components in a Computer Laboratory Room Peralatan Listrik Lab. A Computers = 29 Air Conditioner 1/2 PK = 2 Air Conditioner 1 PK = 1 Proyektor = 1 Lab. B Computers = 26 Lamps = 6 Air Conditioner 1 PK = 2 Proyektor = 1 Cctv = 2 Lab. C Computers = 26 Lamps = 6 Air Conditioner 1 PK = 2 Proyektor = 1 Cctv = 2 Lab. D Computers = 26 Air Conditioner 1/2PK = 1 Air Conditioner 1 PK = 2 Proyektor = 1 Lab. E Computers = 26 Air Conditioner 1/2PK = 1 Air Conditioner 1 PK = 2 Proyektor = 1 Technician Room Computers = 4 Lamps = 5 Table 4 shows data on equipment in the Computer Laboratory of the Samarinda State Polytechnic that supports teaching needs. 3) Name Plate Transformator 800kVA Politeknik Negeri samarinda The 800kVA transformer at the Samarinda State Polytechnic has a nameplate that provides information on the transformer specifications, which are needed as parameters to determine the full load current in calculating the harmonic value. An image of the nameplate of the 800kVA transformer at the Samarinda State Polytechnic can be seen in Table 5. International Journal of Current Science Research and Review ISSN: 2581-8341 Volume 08 Issue 11 November 2025 DOI: 10.47191/ijcsrr/V8-i11-38, Impact Factor: 8.048 IJCSRR @ 2025 www.ijcsrr.org 5831 *Corresponding Author: Rizky Aprylianto Susilo Volume 08 Issue 11 November 2025 Available at: www.ijcsrr.org Page No. 5816-5835 Figure 11 Operational Research Flowchart Reactive power compensation is a crucial strategy in maintaining the stability and efficiency of electrical systems. In this context, simulations of electrical system improvements have been carried out using Static Var Compensators (SVCs). The simulated SVC consists of three Thyristor Switched Capacitor (TSC) units, each with a capacity of 107.32 VAr. This component is designed to automatically compensate for the system's reactive power requirements through integrated control. The main objective of this simulation is to analyze and optimize the performance of the electrical system by reducing harmonics and improving the power factor that does not meet standards. To achieve this goal, the simulation was run using MATLAB Simulink software. The approach used was to compare the performance of the electrical system before and after the integration of the SVC module. This allowed for an evaluation of the impact of SVC on critical system parameters. The simulation design included the integration of the SVC module into the electrical system of the Samarinda State Polytechnic computer laboratory. In addition to SVC, a step-down transformer was also used to ensure the system voltage was compatible with the SVC module specifications. This study involved comprehensive electrical parameter measurements, such as Individual Harmonic Distortion (IHDi) and Total Harmonic Distortion (THD), to obtain a complete picture of the effectiveness of SVC implementation. The THD and IHDi values in the simulation with the addition of a Static Var Compensator can be seen in Figure 12. Based on Figure 12, which shows the FFT (Fast Fourier Transform) Analyzer, the R phase harmonics after the installation of the Static Var Compensator, whereas before the installation of the Static Var Compensator in Figure 5, the harmonics value was 33.65%. However, after installing the Static Var Compensator in the electrical system simulation at the Samarinda State Polytechnic Computer Laboratory on Thursday at 3:00 PM WITA, the harmonic value improved, falling below the specified standard value with a harmonic value of 9.81%, a reduction of 23.84%. International Journal of Current Science Research and Review ISSN: 2581-8341 Volume 08 Issue 11 November 2025 DOI: 10.47191/ijcsrr/V8-i11-38, Impact Factor: 8.048 IJCSRR @ 2025 www.ijcsrr.org 5832 *Corresponding Author: Rizky Aprylianto Susilo Volume 08 Issue 11 November 2025 Available at: www.ijcsrr.org Page No. 5816-5835 Figure 12 Based on Figure 13, which shows the FFT (Fast Fourier Transform) Analyzer, the R phase harmonics after the installation of the Static Var Compensator, whereas before the installation of the Static Var Compensator in Figure 6, the harmonics value was 15.85%. However, after installing the Static Var Compensator in the electrical system simulation at the Samarinda State Polytechnic Computer Laboratory on Thursday at 3:00 p.m. WITA, the harmonic value improved, falling below the specified standard value to 10.98%, a reduction of 4.87%. Figure 13 Based on Figure 13, which shows the FFT (Fast Fourier Transform) Analyzer, the harmonic phase T after the installation of the Static Var Compensator, whereas before the installation of the Static Var Compensator in Figure 7, the harmonic value was 92.98%. However, after installing the Static Var Compensator in the electrical system simulation at the Samarinda State Polytechnic Computer Laboratory on Thursday at 3:00 p.m. WITA, the harmonic value improved, falling below the specified standard value of 9% with a harmonic value reduction of 83.98%. Phase T Harmonic Results in the Simulation After Using SVC International Journal of Current Science Research and Review ISSN: 2581-8341 Volume 08 Issue 11 November 2025 DOI: 10.47191/ijcsrr/V8-i11-38, Impact Factor: 8.048 IJCSRR @ 2025 www.ijcsrr.org 5833 *Corresponding Author: Rizky Aprylianto Susilo Volume 08 Issue 11 November 2025 Available at: www.ijcsrr.org Page No. 5816-5835 F. Comparison Results Before and After Using the Static Var Compensator After conducting an electrical system simulation at the Computer Laboratory of the Samarinda State Polytechnic, both with and without the use of a Static Var Compensator, the results showed significant differences in various parameters. The comparison between the conditions before and after using SVC aims to assess the effectiveness of the reactive power compensation method using SVC, in terms of energy efficiency, system stability, and the quality of the electrical power produced. Before installing SVC, the system experienced power quality problems, such as high levels of harmonic distortion in the current. This condition indicates that the system was not working efficiently. After the installation of the SVC, which consisted of three Thyristor Switched Capacitors (TSCs), the system underwent significant changes. The reactive power compensation performed by the capacitors in the SVC was able to reduce system harmonics more efficiently. Table 6 below presents a complete comparison of system parameters before and after the installation of the SVC. The purpose of this test is to test the accuracy of the current reading results on the PZEM-004Tv30 current sensor with an Ampere meter measuring device. The test results of the PZEM-004Tv30 current sensor can be seen in Figure 9. Table 6. Comparison of Electrical Parameters Before and After Installation of Static VAR Compensator parameters Before Using SVC After Using SVC R Phase Voltage (V) 235,60 235,60 S Phase Voltage (V) 233,56 233,56 T Phase Voltage (V) 237,06 237,06 R Phase Current (A) 14,22 50,14 S Phase Current (A) 13,26 24,77 T Phase Current (A) 2,68 30,74 Active Power (W) 6484,26 8203,56 Daya Apparent (VA) 6723,78 8562,78 Reactive Power (VAR) 1778,67 2454,13 THDi Phase R 33,65 9,81 THDi Phase S 15,85 10,98 THDi Phase T 92,99 9 IHDi 3rd (%) phase R 28,39 4,53 IHDi 3rd (%) phase S 8,5 3,76 IHDi 3rd (%) phase T 57,50 2,63 TDD (%) Phase R 0,414 0,120 TDD (%) Phase S 0,182 0,126 TDD (%) Phase T 0,125 0,020 The installation of SVC has a significant effect on reducing Total Harmonic Distortion (THDi). In phase R, THDi decreased from 33.65% to 9.81%, in phase S from 15.85% to 10.98%, and in phase T from 92.98% to 9%. The third-order Individual Harmonic Distortion (IHDi) value in phase R decreased from 28.39% to 4.53, in phase S from 8.75% to 3.76%, and in phase T from 57.50% to 2.63%. Total Demand Distortion (TDD) decreased from 0.414% to 0.120% in phase R and from 0.125% to 0.020% in phase T. Thus, after installing the SVC, all phases met the applicable harmonics standards. In addition, there was an increase in current in all phases after the use of SVC. The current in phase R increased from 14.22 A to 50.14 A, phase S from 13.26 A to 24.77 A, and phase T from 2.68 A to 30.74 A. This increase in current was a result of the increase in active power in the system. Although there was an increase in current, this was not considered a disturbance, but rather a consequence of improved system efficiency. Considering all of the above parameters, it can be concluded that the installation of a Static Var Compensator (SVC) has a positive impact on the power quality of the electrical system at the Samarinda State Polytechnic Computer Laboratory. The use of SVC has been proven to increase power efficiency and reduce harmonic distortion to within the established standard limits. International Journal of Current Science Research and Review ISSN: 2581-8341 Volume 08 Issue 11 November 2025 DOI: 10.47191/ijcsrr/V8-i11-38, Impact Factor: 8.048 IJCSRR @ 2025 www.ijcsrr.org 5834 *Corresponding Author: Rizky Aprylianto Susilo Volume 08 Issue 11 November 2025 Available at: www.ijcsrr.org Page No. 5816-5835 V. CONCLUSIONS AND RECOMMENDATION A. Conclusions Based on the results and discussion in terms of reducing harmonic values in the electrical system of the Samarinda State Polytechnic Computer Laboratory, as explained in Chapter IV above, the following conclusions can be drawn: Simulasi sistem kelistrikan sebelum menggunakan Static Var Compensator pada Laboratorium Komputer Politeknik Negeri Samarinda. Hasilnya mendekati dengan hasil pengukuran yang dilakukan. 1. Simulation of the electrical system before using a Static Var Compensator in the Samarinda State Polytechnic Computer Laboratory. The results are close to the measurement results. 2. The condition of the electrical system at the Computer Laboratory of the Samarinda State Polytechnic, according to the IEEE 519-2014 standard, is that the Total Demand Distortion is 8%, and from the calculations obtained, the TDD value is far below the specified limit, but in the 3rd order, the Individual Harmonic Distortion (IHDi) limit can be reduced well below the required standard of 7%. During the simulation, with the addition of SVC, the IHDi value in phase R, which was previously 28.39%, can be reduced to 4.53%, in phase S from 8.75% to 3.76%, and in phase T from 56.50% to 2.63%. This indicates that SVC can reduce harmonics at certain orders and total harmonic distortion of current. B. Recommendations The installation of a Static Var Compensator in the electrical simulation of the Samarinda State Polytechnic Computer Laboratory requires a total reactive power compensation of 321.98 Var, divided into 3 stages, so that each stage requires a compensation of 107.32 Var, using capacitors with a capacity of REFERENCES 1. Adel A., Elbaset, et al. “IEC 61850 Communication Protocol with the Protection and Control Numerical Relays for Optimum Substation Automation System.” Journal of Engineering Science and Technology Review, vol. 13, no. 2, Apr. 2020, pp. 1–12 2. T. Harmika, A. Sholichan, and L. Assaffat, “Measurement and Analysis of Load Imbalance and Electric Power Quality on 865 KVA Transformer at Universitas Muhammadiyah Semarang,” Proceedings of Unimus National Seminar, vol. 3, no. 0, 2020. 3. J. Sinaga, R. M. Siburian, and J. Sirait, "Analysis of the Effect of Harmonics on Electrical Load Operation," UDA Journal of Energy Technology, vol. 9, no. 2, pp. 88-97, 2020. 4. Y. P. Tondok, L. S. Patras, and F. Lisi, “Design of 125 kVA Distribution Transformer,” Journal of Electrical and Computer Engineering, vol. 8, no. 2, pp. 83–92, Aug. 2019, doi: https://doi.org/10.35793/jtek.v8i2.24895. 5. A. M. Eltamaly, A.-H. M. El-Sayed, Y. S. Mohamed, and A. N. A. Elghaffar, "A modified techniques of transmission system by static var compensation (SVC) for voltage control," in 2019 8th International Conference on Modeling Simulation and Applied Optimization (ICMSAO), 2019, pp. 1–6. 6. H. USMAN and NURADDEEN MAGAJI, “SIMULATION OF SHUNT ACTIVE POWER FILTER BASED FUZZY LOGIC CONTROLLER FOR MINIMIZATION OF TOTAL HARMONIC DISTORTION,” International Journal of Applied and Advanced Engineering Research, 2023. 7. K. Ramadhan, K. Yonathan, I. M. Ardita, F. H. Jufri and A. R. Utomo, "Voltage Stability Improvement Using Load Shedding and STATIC VAR COMPENSATOR (SVC): Study Case of Senayan-Sambas Power System," 2019 IEEE International Conference on Innovative Research and Development (ICIRD), Jakarta, Indonesia, 2019, pp. 1-5. 8. Turan, O., & Sarı, Y. (2021). Modelling a Static Var Compensator consist of TCR and TSC. Turkish Journal of Science and Technology, 16(1), 11-21. 9. F. R. Maulana, “Analysis of Harmonic Occurrence in Variable Frequency Drives and Its Impact on Three-Phase Induction Motor Speed Control,” Unila.ac.id, 2025. 10. P Harahap and B Oktrialdi, “Harmonisa in defibrillator equipment (DC Shock)using simulink Matlab,” IOP Conference Series Materials Science and Engineering, vol. 821, no. 1, pp. 012025–012025, Apr. 2020, doi: https://doi.org/10.1088/1757-899x/821/1/012025 International Journal of Current Science Research and Review ISSN: 2581-8341 Volume 08 Issue 11 November 2025 DOI: 10.47191/ijcsrr/V8-i11-38, Impact Factor: 8.048 IJCSRR @ 2025 www.ijcsrr.org 5835 *Corresponding Author: Rizky Aprylianto Susilo Volume 08 Issue 11 November 2025 Available at: www.ijcsrr.org Page No. 5816-5835 11. M. Jannah and R. Putri, "Penggunaan Single Tuned Filter Untuk Memperkecil Harmonisa yang Ditimbulkan Oleh Beban Non Linier Pada Transformator 400 kVA," Proceeding Seminar Nasional Politeknik Negeri Lhokseumawe, vol. 2, no. 1, pp. 116 - 122, 2018. 12. A. Hermawan, Mudjiono, C. Wiharya, and S. Seftiana, “Analysis of Load Balance and Harmonics at Graha Polinema, State Polytechnic of Malang,” Elposys: Journal of Electrical Systems, vol. 8, no. 3, pp. 47–52, Nov. 2021, doi: https://doi.org/10.33795/elposys.v8i3.76. 13. "IEEE Standard for Harmonic Control in Electric Power Systems," in IEEE Std 519-2022 (Revision of IEEE Std 5192014) , vol., no., pp.1-31, 5 Aug. 2022, doi: 10.1109/IEEESTD.2022.9848440. 14. Belati, E. A., Nascimento, C. F., de Faria, H., Watanabe, E. H., & Padilha Feltrin, A. (2018). Allocation of Static Var Compensator in Electric Power Systems Considering Different Load Levels. Journal of Control, Automation and Electrical Systems 15. Irreza Naderipour et al., “Optimal designing of Static Var Compensator to improve voltage profile of power system using fuzzy logic control,” Optimal designing of Static Var Compensator to improve voltage profile of power system using fuzzy logic control, vol. 192, pp. 116665–116665, Feb. 2020 16. R. A. Susilo, Transient Stability Analysis of Electric Power Systems Using Static Var Compensator, Samarinda, East Kalimantan: Rizky Aprylianto Susilo, 2018. Cite this Article: Susilo, R.A., Valdano, G., Subagyo, H., Setiawan, W. (2025). Analysis of Harmonic Improvement in the Computer Laboratory of Samarinda State Polytechnic with the Addition of a Static VAR Compensator. International Journal of Current Science Research and Review, 8(11), pp. 5816-5835. DOI: https://doi.org/10.47191/ijcsrr/V8-i11-38