Citation: Elangovan, M.; Srimanickam, B.; ˇ Cep, R.; Saranya, A.; Ramachandran, M. Experimental Study of a Hybrid Solar Collector Using TiO2/Water Nanofluids. Energies 2022,15, 4425. https:// doi.org/10.3390/en15124425 Academic Editors: Gianpiero Colangelo and George Kosmadakis Received: 21 May 2022 Accepted: 16 June 2022 Published: 17 June 2022 Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. Copyright: © 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https:// creativecommons.org/licenses/by/ 4.0/). energies Article Experimental Study of a Hybrid Solar Collector Using TiO2/Water Nanofluids Muniyandy Elangovan 1,* , Baskaran Srimanickam 1, Robert ˇ Cep 2,* , Amirtharajan Saranya 3 and Manickam Ramachandran 4 1Department of Mechanical Engineering, Vel Tech Rangarajan Dr. Sagunthala R&D Institute of Science and Technology, Chennai 600062, India; [email protected] 2Department of Machining, Assembly and Engineering Metrology, Faculty of Mechanical Engineering, VSB-Technical University of Ostrava, 708 00 Ostrava, Czech Republic 3Department of Physics, Vel Tech Rangarajan Dr. Sagunthala R&D Institute of Science and Technology, Chennai 600062, India; [email protected] 4Data Analytics Lab, REST Labs, Kaveripattinam, Krishnagiri 635112, India; [email protected] *Correspondence: [email protected] (M.E.); [email protected] (R. ˇ C.) Abstract: A case study of solar collector outdoor test of the experimental technique conducted at Avadi, Chennai. To lower the temperature of solar PV panels, water, and water-based nanofluids were utilized concurrently. Higher cell temperatures restrict the effectiveness of solar PV systems since only a minor amount of power from the sun is gathered as electricity from the energy conversion, and the remaining energy is squandered as heat. The study aimed to develop and build a hybrid collector while also analyzing its electrical and thermal energy performance. The effort was invested in improving the system’s performance; the PVT collector was tested at volume concentrations of two, such as 0.5 and 1.0 L per minute (LPM). The PV/T collector determined thermal efficiency as highest was 48.38 percent and 54.03 percent, respectively, at 0.5 LPM and 1.0 LPM of volume flow rates. The PV/T collector’s highest electrical efficiency was 18.32 percent and 19.35 percent, respectively, for 0.5 LPM and 1.0 LPM of volume flow rates. The results demonstrate that nanofluid has more excellent thermal conductivity than a base fluid with a little change in the fluid viscosity and density. Keywords: standalone hybrid collector; TiO 2 ; flow rate; nanofluid; thermal performance; electrical; energy; renewable 1. Introduction The increase in global energy requirements every year, and the gradual depletion of traditional fuels necessitates technological advancements based on alternative energy sources [ 1 ]. Solar collectors for industries and households are frequently used to heat water with solar energy. Out of two collectors, one is called a Solar flat plate collector and the other is called an evacuated tube collector. To increase productivity, two different power conversion systems, known as hybrid power or photovoltaic thermal systems, can be coupled together [ 2 , 3 ]. Solar renewable energy is a popular renewable source because it is free, feasible, durable, has a low maintenance cost, is environmentally friendly, and has a wide range of applications. However, it has drawbacks, such as increasing the solar panel’s temperature by 10 degrees Celsius, resulting in a 0.5 percent decrease in electrical efficiency for silicon cells because cooling of the solar panel may be required for improved efficiency. Cooling liquids such as air or water are used in the solar panel system to reduce the temperature [ 4 – 9 ]. There are two ways that the performance of a solar panel can be increased. First is solar panel cooling, and another is a medium for storing waste heat. Air and water are commonly used to cool solar panels as a traditional cooling method. Nonetheless, it has its own set of virtues and merits. As a result of the foregoing encounters, Energies 2022,15, 4425. https://doi.org/10.3390/en15124425 https://www.mdpi.com/journal/energies
Energies 2022,15, 4425 2 of 12 many researchers worldwide have been using nanomaterials as a superior cooling fluid to improve thermal and electrical performance. As a result, overall performance can be improved. The following are some examples of successful studies conducted around the world. Choi and Estman [ 10 ] pioneered nanofluids as a cooler in PVT systems, which sparked considerable interest due to their superior thermophysical properties examined to the standard fluids. The solid-liquid synthesized nanoparticles in a company with diameters typically ranging from 1–100 nm drifting in water [11]. Many experiments demonstrated that water nanofluid has a significantly larger heat transfer coefficient occurs than basic fluids [ 12 – 14 ]. The enrichment of heat transfer was done by nanofluids in hybrid collectors, with a few negative impacts, such as increased pressure drop in the system [ 15 ], a limited period of its stability, and a higher cost of nanoparticles. Sardarabadi et al. [ 16 ] experimented with water as a base fluid with PVT systems and at various concentrations of SiO 2 nanofluid. It was concluded that overall performance attained 3.6 to 7.9 percent for 1 to 3 wt. percent. Ghadiri et al. [ 17 ] examined water and ferrofluid with varying compositions using an indoor PVT system. The overall efficiency was 45 percent when compared to a hybrid system. Sardarabadi et al. [ 18 ] used deionized water to dissolve three types of nanoparticles (AL2O3, TiO2, and ZnO). Al-shamani et al. [ 19 ] experimented with various nanofluids at different flow rates. According to the results, sic had the highest electrical performance of about 13.52 percent and the overall maximum efficiency of 78.24 percent. Soltani et al. [ 20 ] demonstrated an investigational study in a hybrid system using water nanofluid. It was discovered that full enactment and power generation increased by 3.13 percent and 52.4 percent, respectively. The authors also revealed that SiO 2 improved total performance and power generation by 3.29 percent and 43.36 percent, respectively. Al-Waeli et al. [ 21 ] used collectors to investigate three types of nanofluids. Al-Waeli et al. [ 22 ] demonstrated the influence of Silicon chloride/water nanofluid on hybrid systems, which improved electrical energy efficiency to 23.9 percent and heat power efficiency to 99.23 percent. It also discovered that it had a superior overall performance of approximately 88.9 percent when compared to a PV system. Mohammad Sardarabadi et al. [ 23 ] examined the silica nanofluid’s efficiency in a PVT system experimentally. It concluded with a 7.9 percent improvement in overall performance and a 24.3 percent improvement in exergy. For long-term stability, Ag/water nanofluid was processed by electrical explosion of wire [ 24 , 25 ]. The system was evaluated using a thermodynamic study, specifically energy and exergy efficiency. This experiment was carried out using various flow patterns and concentrations. Muhammad Azam investigated a mathematical model of a chemically reactive Maxwell nanofluid for axisymmetric flow using the Cattaneo-Christov heat flux model and a revised nanofluid model. [ 26 ]. The impact of Arrhenius activation energy and melting events on chemically reactive Falkner-Skan flow of cross nanofluid across a moving wedge with viscous dissipation and nonlinear radiation impacts are studied using a theoretical numerical communication [ 27 ]. The primary goal of this paper is to investigate the effects of melting phenomena and nonlinear chemical reactions on transient bioconvection flow of a sutterby nanoliquid with gyrotactic microorganisms and heat source/sink [ 28 ]. Muhammad Azam [ 29 ] studied the unsteady bio-convection flow of nanofluid under the impact of microorganisms and nonlinear radiation using mathematical modeling and simulation. The research goal is to demonstrate manganese chloride as a coolant to improve the PVT collector performance. The manganese chloride nanofluid has been experimentally explored for the first time to cool and improve the performance of a single glazing surface PVT system. The developed PVT collector and PV module were tested outdoors at the Chennai meteorological station using 0.5 wt. percent concentrations of nanofluids and pure water as coolants at 0.5 and 1.0 L per minute. The energetic study of a hybrid collector with nanofluid coolants was carried out, and comparisons to PV modules and water-cooled PVT systems were. It was also discovered that the findings of this inquiry were equivalent to those published in peer-reviewed journals.
Energies 2022,15, 4425 3 of 12 2. Experimental Study Procedure The findings are from tests conducted in Avadi, near Chennai (The Capital of Tamil Nadu, Southern India). Chennai city is located on the thermal equator and the coast, which prevents seasonal temperature variations from becoming considerable. The average relative humidity is 69%, the average ambient temperature ranges from 24.8 ◦ C to 33.1 ◦ C, and the average number of sunshine hours is 7.8. The suggested approach was built, produced, and tested to determine the efficiency of nano-PCM and nanofluid PVT systems, then compared to liquid PVT systems and freestanding PV modules. In addition, water as a cooler with varied flow rates was tested in the PVT system, while nano-PCM and nanofluid with varying concentrations and flow rates were tested in the hybrid collector. The finished system is a self-contained PV module that usually works—an experimental setup at the specific location in Figure 1. As per the Indian subcontinent is located in the northern hemisphere of the earth where a 13-degree inclination is measured. In this study, there is no variation in inclination. Energies 2022, 15, x FOR PEER REVIEW 3 of 14 pure water as coolants at 0.5 and 1.0 L per minute. The energetic study of a hybrid collector with nanofluid coolants was carried out, and comparisons to PV modules and watercooled PVT systems were. It was also discovered that the findings of this inquiry were equivalent to those published in peer-reviewed journals. 2. Experimental Study Procedure The findings are from tests conducted in Avadi, near Chennai (The Capital of Tamil Nadu, Southern India). Chennai city is located on the thermal equator and the coast, which prevents seasonal temperature variations from becoming considerable. The average relative humidity is 69%, the average ambient temperature ranges from 24.8 °C to 33.1 °C, and the average number of sunshine hours is 7.8. The suggested approach was built, produced, and tested to determine the efficiency of nano-PCM and nanofluid PVT systems, then compared to liquid PVT systems and freestanding PV modules. In addition, water as a cooler with varied flow rates was tested in the PVT system, while nano-PCM and nanofluid with varying concentrations and flow rates were tested in the hybrid collector. The finished system is a self-contained PV module that usually works—an experimental setup at the specific location in Figure 1. As per the Indian subcontinent is located in the northern hemisphere of the earth where a 13-degree inclination is measured. In this study, there is no variation in inclination. Figure 1. Experimental setup at the specific location. A multi-silicon glass panel with 1640 mm × 992 mm × 35 mm was purchased to construct a Photovoltaic Thermal Collector. Because of the platform’s insulating effect, a 0.4 mm copper sheet was used for heat absorption on the back of the solar panel. Furthermore, the external and internal diameters of the copper tube are 1.0 cm and 0.8 cm, respectively, and are placed to observe heat behind the solar panel. Table 1 shows the performance of the solar panel under normal test conditions. The photovoltaic thermal system was oriented 13 degrees south. Every day, between 8 a.m. and 5 p.m., readings for all weather conditions and output power were obtained for fifteen minutes. A copper tube connected to a solar panel is shown in Figure 2. This copper tube is used because of high heat conduction from the solar panel to the water which is passing through the pipe. When placing the copper pipe, it must be taken care that the entire length is in contact with the Figure 1. Experimental setup at the specific location. A multi-silicon glass panel with 1640 mm × 992 mm × 35 mm was purchased to construct a Photovoltaic Thermal Collector. Because of the platform’s insulating effect, a 0.4 mm copper sheet was used for heat absorption on the back of the solar panel. Furthermore, the external and internal diameters of the copper tube are 1.0 cm and 0.8 cm, respectively, and are placed to observe heat behind the solar panel. Table 1shows the performance of the solar panel under normal test conditions. The photovoltaic thermal system was oriented 13 degrees south. Every day, between 8 a.m. and 5 p.m., readings for all weather conditions and output power were obtained for fifteen minutes. A copper tube connected to a solar panel is shown in Figure 2. This copper tube is used because of high heat conduction from the solar panel to the water which is passing through the pipe. When placing the copper pipe, it must be taken care that the entire length is in contact with the solar panel, and a special arrangement using a clamp was used to make sure that the pipe is always in contact with the solar panel. To increase heat transmission and reduce material costs, the nanofluid was used in the solar panel system. The single-phase method explains the heat conductivity and properties of nanofluid TiO 2 . The basic assumption of this technique is thermal equilibrium is maintained for nanoparticles and base fluid, causing the suspension to behave like
Energies 2022,15, 4425 4 of 12 a regular fluid. The fluid characteristics are then presumed to have been altered as a result of the introduction of nanoparticles. The essential part of the single-phase method under these assumptions is determining the effective thermo-physical characteristics of the nanofluids. Therefore, the selection of competent drivers with reasonable costs that may be sold together is an essential consideration. Figure 3shows the image of SEM of TiO2nanoparticles. Table 1. Details of the solar panel. Parameter Value Unit Pmax 260 Watts Amps in Pmax 8.42 Amps Volts in Pmax 30.9 Volts Current in Maximum Load 8.89 Amps Voltage in Maximum Load 37.7 Volts Weight 18.2 Kilogram Energies 2022, 15, x FOR PEER REVIEW 4 of 14 solar panel, and a special arrangement using a clamp was used to make sure that the pipe is always in contact with the solar panel. Figure 2. Photographic view of the copper tube along with the solar panel. Table 1. Details of the solar panel. Parameter Value Unit Pmax 260 Watts Amps in Pmax 8.42 Amps Volts in Pmax 30.9 Volts Current in Maximum Load 8.89 Amps Voltage in Maximum Load 37.7 Volts Weight 18.2 Kilogram To increase heat transmission and reduce material costs, the nanofluid was used in the solar panel system. The single-phase method explains the heat conductivity and properties of nanofluid TiO2. The basic assumption of this technique is thermal equilibrium is maintained for nanoparticles and base fluid, causing the suspension to behave like a regular fluid. The fluid characteristics are then presumed to have been altered as a result of the introduction of nanoparticles. The essential part of the single-phase method under these assumptions is determining the effective thermo-physical characteristics of the nanofluids. Therefore, the selection of competent drivers with reasonable costs that may be sold together is an essential consideration. Figure 3 shows the image of SEM of TiO2 nanoparticles. Figure 2. Photographic view of the copper tube along with the solar panel. Energies 2022, 15, x FOR PEER REVIEW 5 of 14 Figure 3. Photographic view of the copper tube along with the solar panel. 3. Analytical Methodology Electrical and thermal energy analyses were carried out in this methodology, which are detailed below [30–34]. The governing differential equation for the behavior of the systems are based on: 1. Steady-state operation. 2. The inlet mass flow rate into the solar thermal storage tank is constant. 3. The radiation heat transfer is negligible. 4. The dust deposition on the solar panel is meager. 3.1. Performance of Electrical Energy The ratio of electrical energy is electrical power, and the panel energy observation and equation are given below. = (1) (2) = (3) 3.2. Performance of Thermal Energy The efficiency of thermal energy is employed to characterize the performance of a PV/T system. ℎ = (4) = = (− ) (5) = (6) These equations are based on the solar radiation falling on the particular area of the solar panel being well defined in the solar radiation observations. These observations are known as . The mass flow rate of coolant, heat carrying capacity of the coolant difference of inlet, and the output of the coolant are combined, producing what is known as heat energy generation . 3.3. Uncertainty Analysis Figure 3. Photographic view of the copper tube along with the solar panel.
Energies 2022,15, 4425 5 of 12 3. Analytical Methodology Electrical and thermal energy analyses were carried out in this methodology, which are detailed below [ 30 – 34 ]. The governing differential equation for the behavior of the systems are based on: 1. Steady-state operation. 2. The inlet mass flow rate into the solar thermal storage tank is constant. 3. The radiation heat transfer is negligible. 4. The dust deposition on the solar panel is meager. 3.1. Performance of Electrical Energy The ratio of electrical energy is electrical power, and the panel energy observation and equation are given below. ηelec =Pmax . Qs (1) Pmpmpmax (2) . Qs=Acol IG(3) 3.2. Performance of Thermal Energy The efficiency of thermal energy is employed to characterize the performance of a PV/T system. ηther = . Qu . Qs (4) . Qu=. mCp∆T=. mCp(To−Ti)(5) . m=ρAcolV(6) These equations are based on the solar radiation falling on the particular area of the solar panel being well defined in the solar radiation observations. These observations are known as . Qs . The mass flow rate of coolant, heat carrying capacity of the coolant difference of inlet, and the output of the coolant are combined, producing what is known as heat energy generation . Qu. 3.3. Uncertainty Analysis The individual calibration distortion parameters for the PVT collector are shown in Table 2. Uncertainties analysis is required to confirm the accuracy of each experimental setup. Data extraction mistakes, example calibration problems, data processing errors, and unique instrument ambiguities are all examples of errors. The majority of the inaccuracies in this study were produced by the overestimation of each variable, such as temperature, solar irradiation, stress, and fluid velocity. The most significant uncertainty in predicting solar collector efficiency is about 3.6 percent (Table 3). Table 2. Individual calibration distortion parameters for the PVT collector. Sensor Distortion Type Ambient air temperature ±0.2 ◦C K-thermocouple Heat pipe temperature ±0.2 ◦C K-thermocouple Rotameter ±2.3% UKL Solar power meter ±4 W/m2TM-206 Inlet & outlet temperature ±0.2 ◦C K-thermocouple Data logger ±3.4% Agilent 34980A
Energies 2022,15, 4425 6 of 12 Table 3. Percentage increase of thermal efficiency %. Sl. No Working Fluid Thermal Efficiency (%) Average At Extreme Solar Radiation 1 0.5 LPM 25.76% 35.31% 2 1.0 LPM 29.88% 40.96% 3 0.05% TiO2with 0.5 LPM 36.32% 49.79% 4 0.05% TiO2with 1.0 LPM 40.70% 55.80% 4. Results and Discussion According to the findings, the temperature gradient panels grew throughout the day as sun irradiation increased. The pattern of air temperature and solar radiation is similar; however, the PV surface temp/radiation factor for PV panels is substantially more significant than for cooled panels. Furthermore, the temperature differential between the cooling PV panel and the baseline panel dropped; for example, at midday, the difference was 12.6 ◦ C, but at the end of the day, it was only 7.2 ◦ C due to Nanofluid obstructing the cooling function. This study also includes several other parametric tests detailed below. In Figure 4, the solar radiation intensity for chosen days was given for comparison as an example of a similar metrological state. Every 15 s, the data is collected and used for further analysis. The environmental data, solar intensity, and weather conditions from the initial days were gathered, which are shown in Figure 4. From this graph, the diurnal average incoming solar radiation dispersion over the experiment period is a whistle shape. It was observed during the test that the smallest values were 307.18 W/m 2 , recorded on morning 7, and 219 W/m 2 on evening 5. The daily average air temperature rises from 29.36 to 34.23 degrees Celsius from 9 a.m. to 5:00 p.m. Energies 2022, 15, x FOR PEER REVIEW 7 of 14 Figure 4. Average experimental day of the weather information at a specific location. The incident solar radiation on chosen days is depicted in Figure 5 at a certain point in the experimental research in a sample of identical metrological situations. Solar radiation is an essential factor in boosting the performance of both fluids. The solar radiation and ambient temperature at the exact area displayed similar patterns throughout the day. Figure 5. Three experimental test days of solar radiation in W/m2. The TiO2 nanofluid utilized had an ideal volume level of 0.05 percent. Figure 6 demonstrates trends in electrical efficiencies, such as freestanding PV, two types of water flow rates, and TiO2 nanofluid volume concentration. The system efficiency was increased by 67.25 percent on average during the trial day when the optimal concentration of the chosen Nanofluid was used compared to the non-cooled module. The fluctuation in solar cell efficiency with respect to time and air mass flow rate is demonstrated in Figure 7. The graph demonstrates that the increased mass flow rate in the PVT collector results in lower cell temperature and greater cell efficiency. 0 200 400 600 800 1000 1200 7 8 9 10 11 12 13 14 15 16 17 18 Solar Radiation (W/m2) Time of the day (hrs) Exp. Test Day 1 Exp. Test Day 2 Figure 4. Average experimental day of the weather information at a specific location. The incident solar radiation on chosen days is depicted in Figure 5at a certain point in the experimental research in a sample of identical metrological situations. Solar radiation is an essential factor in boosting the performance of both fluids. The solar radiation and ambient temperature at the exact area displayed similar patterns throughout the day.
Energies 2022,15, 4425 7 of 12 Energies 2022, 15, x FOR PEER REVIEW 7 of 14 Figure 4. Average experimental day of the weather information at a specific location. The incident solar radiation on chosen days is depicted in Figure 5 at a certain point in the experimental research in a sample of identical metrological situations. Solar radiation is an essential factor in boosting the performance of both fluids. The solar radiation and ambient temperature at the exact area displayed similar patterns throughout the day. Figure 5. Three experimental test days of solar radiation in W/m2. The TiO2 nanofluid utilized had an ideal volume level of 0.05 percent. Figure 6 demonstrates trends in electrical efficiencies, such as freestanding PV, two types of water flow rates, and TiO2 nanofluid volume concentration. The system efficiency was increased by 67.25 percent on average during the trial day when the optimal concentration of the chosen Nanofluid was used compared to the non-cooled module. The fluctuation in solar cell efficiency with respect to time and air mass flow rate is demonstrated in Figure 7. The graph demonstrates that the increased mass flow rate in the PVT collector results in lower cell temperature and greater cell efficiency. 0 200 400 600 800 1000 1200 7 8 9 10 11 12 13 14 15 16 17 18 Solar Radiation (W/m2) Time of the day (hrs) Exp. Test Day 1 Exp. Test Day 2 Figure 5. Three experimental test days of solar radiation in W/m2. The TiO 2 nanofluid utilized had an ideal volume level of 0.05 percent. Figure 6 demonstrates trends in electrical efficiencies, such as freestanding PV, two types of water flow rates, and TiO 2 nanofluid volume concentration. The system efficiency was increased by 67.25 percent on average during the trial day when the optimal concentration of the chosen Nanofluid was used compared to the non-cooled module. The fluctuation in solar cell efficiency with respect to time and air mass flow rate is demonstrated in Figure 7. The graph demonstrates that the increased mass flow rate in the PVT collector results in lower cell temperature and greater cell efficiency. Energies 2022, 15, x FOR PEER REVIEW 8 of 14 Figure 6. Efficiency of PV and PVT modules with working fluids. As illustrated in Figure 7, cooling devices lowered the average temperatures of PV and PVT modules, whether employing filtered water or introducing nanofluid into the liquid. The temperature of the PV and PVT panels increased as the solar radiation levels increased during the day. Even though the maximum surface temperature of the modules has followed the same trajectory as the solar radiation, the temperature of PV is significantly greater for PV panels than for cooling panels. The PV panel and the regular panel difference in temperature decrease during the day. The temperature difference at midday was 16 °C, and at the end of the day was 15 °C, because the heat stored in the Nanofluid began to have a reverse impact. The average temperature of the trial day, a freestanding PV module, and the highest nanofluid concentration with a high-volume flow rate were 51.3 °C and 38.8 °C, respectively. Figure 6. Efficiency of PV and PVT modules with working fluids. As illustrated in Figure 7, cooling devices lowered the average temperatures of PV and PVT modules, whether employing filtered water or introducing nanofluid into the liquid. The temperature of the PV and PVT panels increased as the solar radiation levels increased during the day. Even though the maximum surface temperature of the modules
Energies 2022,15, 4425 8 of 12 has followed the same trajectory as the solar radiation, the temperature of PV is significantly greater for PV panels than for cooling panels. The PV panel and the regular panel difference in temperature decrease during the day. The temperature difference at midday was 16 ◦ C, and at the end of the day was 15 ◦ C, because the heat stored in the Nanofluid began to have a reverse impact. The average temperature of the trial day, a freestanding PV module, and the highest nanofluid concentration with a high-volume flow rate were 51.3 ◦ C and 38.8 ◦C, respectively. Energies 2022, 15, x FOR PEER REVIEW 9 of 14 Figure 7. PV and PVT module temperature with different working fluids. Figures 8 and 9 depict various working fluids and their electrical efficiency and sun radiation in the morning and afternoon. According to the diagram, when solar radiation increases, electrical performance decreases, which is especially important during the frontline and after midday. Excessive sunshine has a significant negative effect on the electrical solar panels’ performance. Solar radiation is an excellent parameter for influencing the electrical properties of water and water-nanofluid mixtures. Figure 7. PV and PVT module temperature with different working fluids. Figures 8and 9depict various working fluids and their electrical efficiency and sun radiation in the morning and afternoon. According to the diagram, when solar radiation increases, electrical performance decreases, which is especially important during the frontline and after midday. Excessive sunshine has a significant negative effect on the electrical solar panels’ performance. Solar radiation is an excellent parameter for influencing the electrical properties of water and water-nanofluid mixtures. Figure 10 depicts the fluctuation of input and output fluid temperatures with varying volume flow rates and concentrations. The inlet air temperature linearly followed the ambient air temperature. The variation in ∆ T was caused by the different concentration and volume flow rates of the nanofluids. In general, lower rates of water and nanofluid mixed with water resulted in the most significant temperature changes, whereas higher volume flow rates resulted in the smallest. According to the following graphic, an 11.8 ◦ C difference was achieved at a water flow rate of 0.5 LPM at noon. As a result, a 13.3 ◦ C difference was obtained at 0 LPM on the testing day’s midday. Furthermore, around midday on the trial day, a difference of 12.5 ◦C was achieved with water mixed with a nanofluid of 0.5 LPM. After that, at midday on the trial day, a difference of 9.3 TiO 2 manganese oxide. The PVT collector was tested at two different volume concentrations, 0.5 and 1.0 Liters per minute (LPM). The highest thermal efficiency of the system was determined to be 48.38 percent and 54.03 percent, respectively, at the volumes of 0.5 LPM and 1.0 LPM. The highest electrical efficiency of the PV/T collector was determined to be 18.32 percent and 19.35 percent, respectively, for 0.5 LPM and 1.0 LPM of volume flow rates. The results demonstrate that nanofluid has more excellent thermal conductivity than a base fluid with a little increase in viscosity and fluid density. It was achieved in water mixed with nano 1.0 LPM.
Energies 2022,15, 4425 9 of 12 Energies 2022, 15, x FOR PEER REVIEW 9 of 14 Figure 7. PV and PVT module temperature with different working fluids. Figures 8 and 9 depict various working fluids and their electrical efficiency and sun radiation in the morning and afternoon. According to the diagram, when solar radiation increases, electrical performance decreases, which is especially important during the frontline and after midday. Excessive sunshine has a significant negative effect on the electrical solar panels’ performance. Solar radiation is an excellent parameter for influencing the electrical properties of water and water-nanofluid mixtures. Figure 8. Various working fluids and their electrical efficiency and solar radiation during the forenoon of the day. Energies 2022, 15, x FOR PEER REVIEW 10 of 14 Figure 8. Various working fluids and their electrical efficiency and solar radiation during the forenoon of the day. Figure 9. Various working fluids and their electrical efficiency and solar radiation during the afternoon of the day. Figure 10 depicts the fluctuation of input and output fluid temperatures with varying volume flow rates and concentrations. The inlet air temperature linearly followed the ambient air temperature. The variation in ΔT was caused by the different concentration and volume flow rates of the nanofluids. In general, lower rates of water and nanofluid mixed with water resulted in the most significant temperature changes, whereas higher volume flow rates resulted in the smallest. According to the following graphic, an 11.8 °C difference was achieved at a water flow rate of 0.5 LPM at noon. As a result, a 13.3 °C difference was obtained at 0 LPM on the testing day’s midday. Furthermore, around midday on the trial day, a difference of 12.5 °C was achieved with water mixed with a nanofluid of 0.5 LPM. Figure 9. Various working fluids and their electrical efficiency and solar radiation during the afternoon of the day. Figure 11 depicts a PVT module thermal efficiency with various working fluids. Equations (4)–(6) are used to assess multiple equations to get the hybrid collector thermal efficiency. It is estimated using quantifiable criteria such as the temperature differential between the exit and intake air, air mass flow rate, air-specific heat, solar panel area, and solar radiation. When the flow rate changes from 0.5 LPM to 1.0 LPM, the thermal