Including ampere measurements in generalized state estimators

Villa Jaén, Antonio de la; Gómez Expósito, Antonio

Abstract

Conventional state estimators (SEs) cannot take advantage of all available measurements, like currents flowing through circuit breakers and individual external injections. Current measurements are frequent at the lower voltage levels and their loss implies a reduction of the global redundancy and hence a deterioration of the SE filtering capability. In this paper, a methodology is presented allowing all current measurements to be included in the model. A generalized state estimator is used in which substations are compactly represented by means of an implicit model. To illustrate the performance of the proposed formulation, several simulations are presented. Results are validated by checking the accuracy of the estimated states and by showing the improved ability to detect and identify bad data and topology errors.

Full text

Assessment of Generalized State Estimators including Ampere Measurements Antonio de la Villa Ja´en, Antonio G´omez Exp´osito Abstract— Conventional State Estimators (SE) can not take advantage of all available measurements, like currents flowing through circuit breakers and individual external injections. Current measurements are frequent at the lower levels and their loss implies a reduction of the global redundancy and hence a deterioration of the SE filtering capability. In this paper, a methodology is presented allowing all current measurements to be included in the model. A Generalized State Estimator (GSE) is used and the substations are represented in an efficient way by means of an Implicit Model. To illustrate the performance of the proposed formulation, several simulations are presented. Results are validated by checking the accuracy of the estimated states and by showing the improved ability to detect and identify bad data and topology errors. Keywords— Substation Models, Generalized State Estimators, Topology Errors. I. Introduction EXISTING State Estimators resort to the bus-branch model of the system in which only nonzero impedances corresponding to lines and transformers remain. The state vector is composed of bus voltage magnitudes and phase angles. Based on the status of switching elements, electrical buses are determined beforehand by the Topology Processor (TP). One of the shortcomings of this conventional model lies in the fact that connectivity information is assumed correct, which complicates significantly the process of detecting and identifying topology errors. Also, certain measurements, like voltage magnitudes and power injections, must be aggregated into a single one, preventing in this way the possibility for individual bad data to be identified. In this context, it is possible to include branch current measurements, as shown for the first time in [1] and extended later in [2]. However, ampere measurements corresponding to circuit breakers, as well as certain individual current injections, can not be added to this model, because these data are associated to branches of null or unknown impedance, which are not retained. The Generalized State Estimator (GSE) paradigm is based on a detailed representation of substations at the physical level [3]. Two types of substation models exist: the complete or explicit model and the implicit one. The complete model augments the state vector with power flows through every circuit breaker (CB). The number of conventional state variables is also very large, as a consequence of the detailed model adopted. Such a large number of state variables is compensated by a proportional number A. Villa and A. G´omez are with the Department of Electrical Engineering, University of Seville, Seville, Spain. E-mail: a[email protected], [email protected]. 6 6 34 5 6 ? ? 12 Line Closed circuit breaker Fig. 1. Test system. 4 3 65 Line 32Line 41 Proper Tree Fig. 2. Proper tree of the detailed substation of extra topological constraints, representing CB statuses. The size of this full model is huge and, for this reason, only a reduced number of suspect substations are modeled in detail [4]. On the other hand, the implicit substation model developed in [5], [6] reduces the size of the problem significantly, making it possible the representation of all substations of the system and, hence, the inclusion of all internal measurements available. Topology consistency can be subsequently checked by unfolding the information provided by the implicit model. II. Review of the implicit model This model is aimed at minimizing the number of extra variables which must be included in the state vector to model topological connectivity. In order to elaborate the implicit model, a graph is used for each substation [6]. Nodes of this graph correspond with busbar sections (i.e. physical nodes) plus an extra node modeling the outer system, while branches represent lines, transformers, shunt elements, external injections and switching devices. On this graph, the so-called proper tree is built, allowing 0-7803-7967-5/03/$17.00 ©2003 IEEE Paper accepted for presentation at 2003 IEEE Bologna Power Tech Conference, June 23th-26th, Bologna, Italy the necessary state variables to be automatically selected so that the substation can be modeled at the physical level. Branches of the proper tree are selected keeping the following rules in mind: •Include as many closed CBs as possible. •For each electrical bus select one of the associated injections (a zero-injection branch should be retained for buses without external injections). •If necessary, complete the tree with open CBs. •Exclude regular non-zero impedance branches. In Fig. 1, a 3-bus network is shown in which one of the substations is represented in detail, along with its graph and proper tree. As explained in [5], the set of extra variables added to the state vector by the implicit model is composed only of power injections and power flows through closed CBs which are excluded from the tree. In terms of this slightly augmented state vector, any power flow (active or reactive), fij , within the substation can be expressed as fij =XfL(Vi, Vj, θi, θj) + Xfe(1) where fLis the power flow through regular branches with non-null impedance, which is a function exclusively of the classical state variables (Vi,Vj,θi,θj), and ferefers to the flows through the proper tree links [6]. The above expression is easily obtained for each branch by means of the respective cut-set equation. In the example of Fig. 1 only the power injection at bus 6 has to be added to the state vector. For instance, the power flow through CB 5-4 is expressed as: f54 =fL41 +fL32 −f6 where fLrefers indistinctly to active or reactive power and power flows through lines 4-1 and 3-2 are well-known nonlinear functions of state variables. Topological information associated with CB statuses are not explicitly handled by the implicit model. Instead, topology error analysis proceeds from the results provided by the SE. It is proved in [5] that Lagrange multipliers associated with topological constraints and their covariance matrix can be computed from λ=Tr µ(2) where ris the measurement residual vector, µis the vector of Lagrange multipliers corresponding to zero-injection constraints, and Tis the so-called Topology Sensitivity Matrix. Normalized multipliers can then be obtained and used for topology error detection and identification. III. Formulation of current measurements within the implicit model Ampere measurements corresponding to regular nonzero impedance branches can be expressed in terms of conventional state variables and branch parameters [1]. It has long been known that this kind of measurements gives rise to several numerical and convergence problems when included in state estimators with low redundancy (see for instance [1], [2]). In some cases, however, they are essential to assure full network observability, particularly at the subtransmission levels. On the other hand, when the GSE paradigm is adopted, there is a need for internal current measurements, i.e., those associated with switching devices, to be added to the model. This can be done by resorting to the basic equation: Iij =qp2 ij +q2 ij V(3) where Iij is the current through branch i-j within the substation, pij and qij are the active and reactive power flows and Vis the respective bus section voltage. Note that the implicit model allows the power flows pij and qij to be expressed in terms of the state variables obtained from the proper tree by means of (1). Jacobian entries corresponding to (4) and (5) can be obtained as linear combinations of existing Jacobian elements, as follows: ∂Iij ∂x =1 Iij V2pij ∂pij ∂x +qij ∂qij ∂x (4) ∂Iij ∂V =1 Iij V2[pij ∂pij ∂V +qij ∂qij ∂V ]−Iij V(5) where xdenotes any state variable other than V. Note that these terms get undefined for flat start, which is solved by adding ampere measurements only after the second iteration. IV. Assessment of Estimation Accuracy Accuracy of the estimated state with and without internal ampere measurements is analyzed and compared in this section. A. Gaussian errors For the system of Fig. 1, 300 measurement sets are generated by adding Gaussian noise (σ= 0.02) to the results of a load flow. Table I and II show the system parameters and the exact measurement set. For each set of measurements, two simulations are carried out, first using a conventional SE and then resorting to a GSE including current measurements. The measurement vectors are composed of the following elements: zSE = [V1, p12, q12, p23, q23, p1, q1, p14, q14, p21, q21] zGSE = [V1, p12, q12, p23, q23, p1, q1, p14, q14, p21, q21, I54, I63, I43] As the exact state is known in simulation environments the following performance index can be used to compare the results: Fig. 3. Estimated measurements errors provided by the SE. Fig. 4. Estimated measurements errors provided by the GSE. TABLE I SYSTEM DATA Line R X Bs Line 12 0.019 0.059 0.050 Line 23 0.010 0.030 0.028 Line 14 0.015 0.040 0.040 TABLE II EXACT MEASUREMENTS Measurement Value V1 1.0100 p12 1.0000 q12 0.2000 p21 -0.9804 q21 -0.1887 p23 0.7500 q23 0.1000 p1 3.0355 q1 0.5350 p14 2.0355 q14 0.3350 I54 2.2895 I63 0.5771 I43 0.2912 ε=P|bzi−zt i| |zt i| N(6) where |·| denotes absolute value, bziare the estimated measurements, zt iare the exact measurements and Nthe number of considered measurements. Figures 3 and 4 present the histograms corresponding to the 300 simulations performed. While the mean relative ?? 12 66 4 3 56 current measurement Fig. 5. Detailed substations and ampere measurements considered error of the unfiltered input measurements is 1.669%, that of the estimated measurements is 1.613% when the ordinary SE is adopted and reduces to 0.904% when the GSE, including current measurements, is employed. Note that the conventional estimator does not use any of the internal measurements available at the substation which is modeled in detail. Such a low redundancy explains its limited capability to filter measurement noise. Similar results are obtained when different error levels are simulated. In order to confirm the above conclusions, the experiments are repeated by successively modeling in detail the remaining two substations (Fig. 5 shows the oneline diagram for the whole system). In Fig. 6, a comparison is performed between both estimators for different error levels and a total of 500 simulations, when one, two or three substations are included in the GSE model. Note that the larger the number of substations added to the model, i.e. the higher the redundancy, the better the results. Fig. 6. Errors in: [.] SE, [*] GSE (Sub. 3), [o] GSE (Sub. 1 and 3), [+] GSE (Sub. 1,2 and 3) 4 3 65 Line 32Line 41 Proper Tree Fig. 7. Proper tree of substation with erroneus status in CB 4-3 B. Topology errors Results obtained in the presence of topology errors are reported in this section. In the test system of Fig. 1 an erroneous status is adopted for the circuit breaker 4-3, which is assumed open when it is really closed. This is called a split error, by which the conventional estimator assumes two rather than one electrical nodes within the substation. Figure 7 presents the proper tree associated to the graph of substation 3, when CB 4-3 is assumed open. Note that all links correspond to lines or open CB. For this reason, no new state variables are required for the implicit model to properly perform detailed representation of the substation and topology error identification. Table III shows the exact measurements and constraints, as well as the residuals and normalized multipliers obtained by means of both a standard SE and a GSE including current measurements. With the adopted measurement set, the SE cannot detect the topology error (note the null residuals). However, the presence of abnormally high normalised multipliers associated to the respective topological constraints (21.0 and 21.7), allows the GSE to correctly identify the wrong status assumed for the circuit breaker 3- 4. This is a consequence of ampere measurements through CBs 5-4 and 6-3 being considered by the GSE. TABLE III TOPOLOGY ERROR Meas./Const. Value S.E. G.S.E. V1 1.0100 0 5.9 p12 1.0000 0 7.1 q12 0.2000 0 1.5 p23 0.7500 0 12.3 q23 0.1000 0 3.1 p1 3.0355 0 1.3 q1 0.5350 0 0.2 p2 -0.2304 0 6.6 q2 -0.0887 0 0.6 p14 2.0355 0 8.8 q14 0.3350 0 1.9 I54 2.2895 - 16.1 I63 0.5771 - 18.7 p43 0 - 21.0 q43 0 - 20.7 TABLE IV BAD DATA Meas./Const. Value S.E. G.S.E. V1 1.0100 3.3 10.0 p12 1.0000 13.7 13.1 q12 0.2000 1.3 0.7 p23 0.7500 24.8 17.3 q23 0.1000 2.0 2.3 p14 2.4426 24.8 27.2 q14 0.3350 1.3 0.7 p21 -0.9804 12.9 12.8 q21 -0.1887 0.7 1.3 I54 2.2895 - 11.0 I63 0.5771 - 11.0 I43 0.2912 - 11.0 C. Bad data Assuming the measurement set is exact, the value of p14 is increased by 20% to simulate a bad data. Table IV shows the measurement set considered as well as the normalised residuals corresponding to both estimators. With a plain SE the bad data is detected but not identified (the low redundancy leads to a pair of residuals being 24.8). When the GSE and current measurements are employed, the error in p14 is detected and identified (the largest normalised residual, 27.2, corresponds to p14). V. Conclusions In order to include all existing measurements within the state estimation process in an efficient way, particularly ampere measurements, a generalized state estimator based on the recently introduced implicit model is adopted in this paper to represent substations. Experimental results show a significant improvement in the accuracy of estimated states and a reinforced capability to detect and identify both topological and analogue errors when internal current measurements are not discarded. References [1] J. M. Ruiz Mu˜noz, A. G´omez Exp´osito, “A line-current measurement based state estimator”. IEEE Transactions on Power Systems, Vol. 7, pp. 513 -519, May. 1992. [2] A. Abur, A. G´omez Exp´osito, “Detecting multiple solutions in State Estimation in the presence of current magnitude measurements”. IEEE Transactions on Power Systems, Vol. 12, pp. 370- 375, Feb. 1997. [3] A. Monticelli, “State Estimation in Electric Power System. A generalized Approach”. Kluwer Academic Publishers, 1999. [4] O. Alsac, N. Vempati, B. Stott, and A. Monticelli, “Generalized State Estimation”, IEEE Transactions on Power Systems, Vol. 13, No. 3, pp. 1069-1075, August 1998. [5] A. de la Villa,A. G´omez Exp´osito, “Implicitly Constrained Substation Model for State Estimation”, IEEE Transactions on Power Systems, Vol. 17, No. 3, pp. 850-856, Aug. 2002. [6] A. G´omez Exp´osito, A. de la Villa, “Reduced Substation Models for Generalized State Estimation”. IEEE Transactions on Power Systems, Vol. 16, No. 4, 839-846, Nov. 2001. Biographies Antonio de la Villa Ja´en was born in Riotinto, Spain, in 1960. He received his electrical and doctor engineering degrees from the University of Seville. He is presently an Assistant Professor at University of Seville. His primary areas of interest are computer methods for power system state estimation problems. Antonio G´omez Exp´osito was born in Spain, in 1957. He received his electrical and doctor engineering degrees from the University of Seville. Since 1982 he has been with the Dep. of Electrical Engineering, University of Seville, where he is currently a Professor and Head of the Dep. His primary areas of interest are optimal power system operation, state estimation and computer relaying. View publication statsView publication stats