Full text
1 Behaviour of a concrete wall containing micro‐encapsulated PCM 1 after a decade of its construction 2 Luisa F. Cabezaa, Lidia Navarroa, Anna Laura Pisellob,c, Lorenzo Olivierid,e, Cesar 3 Bartoloméf, José Sánchezg, Servando Álvarezg, Jose Antonio Tenorioe 4 a GREiA Research Centre, INSPIRES Research Centre, Universitat de Lleida, Pere de Cabrera s/n, 5 25001 Lleida, Spain 6 b CIRIAF—Interuniversity Research Center, University of Perugia, Via G. Duranti 63, 06125 Perugia, 7 Italy 8 c Department of Engineering, University of Perugia, Via G. Duranti 93, 06125 Perugia, Italy 9 d Department of Construction and Technology in Architecture, Escuela Técnica Superior de Arquitectura, 10 Universidad Politécnica de Madrid, Av. de Juan de Herrera 4, 28040 Madrid, Spain 11 e Instituto de Ciencias de la Construcción Eduardo Torroja – CSIC, Serrano Galvache 4, 28033 Madrid, 12 Spain 13 f IECA, Instituto Español del Cemento y sus Aplicaciones, Calle de José Abascal 53, 28003 Madrid, 14 Spain 15 g Grupo de Termotécnia, Universidad de Sevilla, Escuela de Ingenieros Camino de los Descubrimientos 16 s/n. 41092, Seville, Spain 17 18 Abstract 19 20 Today, our society has the duty of reducing the energy consumed in the building sector. A 21 promising technology to achieve this goal is the implementation of thermal energy storage (TES) 22 solutions in buildings envelope. Lately, much literature dealing with the effect of the inclusion of 23 latent heat storage materials in construction materials to provide higher thermal inertia has 24 appeared, mostly focusing on the evaluation of the thermal properties, density, or porosity of these 25 new materials. However, few of them evaluated the long stability properties of the materials with 26 embedded PCM when included in a building, very much needed since the lifetime of a building 27 is about 50 years. Therefore, in this study, an evaluation of a house‐like cubicle of concrete with 28 micro‐encapsulated PCM after a decade of its construction is carried out. The results are compared 29 to the tests done in 2005 concluding that the thermal performance of this cubicle presented no 30 degradation in the PCM effect.31 32 Keywords: building; energy efficiency; thermal energy storage; long lasting performance 33 34 35 36 37 This is an Accepted Manuscript of an article published by Elsevier in Solar Energy, Volume 200, April 2020, available at: https://doi.org/10.1016/j.solener.2019.12.003 Copyright 2019. Intern. Solar Energy Society, Elsevier. En idUS Licencia Creative Commons CC BY-NC-ND
2 1. Introduction 38 39 Buildings use 32% of global final energy demand, and generate 30% of energy‐related CO2 40 emissions, and approximately one‐third of the black carbon emissions. Over 60% of residential 41 and almost 50% of commercial buildings use thermal energy, with higher contribution from water 42 heating in residential buildings and from cooling in commercial ones. The drivers of the heating 43 and cooling energy demand in buildings show a clear tendency where the decrease of the energy 44 demand is a need [1]. 45 46 Thermal energy storage (TES) is one of the highlighted technologies to achieve energy demand 47 decrease in buildings. It is well known that improvements in the building envelope have high 48 influence in the energy demand reduction. The use of phase change materials (PCM) in the 49 building envelope has been widely studied to take profit of the latent heat stored during the phase 50 change. The implementation of PCM as a passive system became a way to provide thermal inertia 51 to the building at a specific temperature, in this case the comfort building temperature range [2]. 52 53 Different methodologies can be used to insert PCM in buildings. Direct incorporation, immersion, 54 vacuum impregnation, encapsulation, shape‐stabilisation, and form stable composites are the 55 identified methods. However, when including PCM into a construction material during the mixing 56 process, such as concrete or cement mortar, the one that prevents the leakage problem is using 57 micro‐encapsulation PCM. This method consists in encapsulating PCM in small particles (1 μm 58 ‐ 1000 μm) with a thin solid shell which is made from natural and synthetic polymers [3]. More 59 details can be found in Marani and Nehdi, 2019 [4]. 60 61 Several studies have been also dedicated to the performance analysis and enhancement of 62 composites made by cement or concrete based components and PCM based inclusions in a variety 63 of ways and for different uses. Most of them are aimed at improving building thermal inertia, 64 since the PCM contribution is able to dampen down thermal waves entering and exiting the 65 building envelope at reasonable cost, as recently demonstrated [5,6]. PCM can be effectively 66 integrated into structural and non-structural elements, which is the reason why several 67 experiments and case studies concern their characterization in walls, ceilings, roofs, windows [7]. 68 In this regard, the reduction of mechanical properties of concrete when PCM is added should be 69 considered; the literature reports a reduction of up to 51% [8]. More details can be found in 70 Berardi and Gallardo, 2019 [9]. Very little research is done in also evaluating the durability of the 71 mortars or concrete after the addition of PCM [10]. 72 73
3 The most typical PCM materials are organic or inorganic. Organic PCM are usually paraffin and 74 fatty acids, while inorganic PCM are usually salt hydrates. This second material are frequently 75 associated to high volume change rates during the thermal transitions and large subcooling, which 76 compromises both their effect and the quality of prediction models which are elaborated in order 77 to better predict their field behaviour, after inclusion into the cement based matrix. Therefore, 78 organic PCM (paraffin mainly) are the most acknowledged from the scientific community and 79 the practical field of application nowadays [11]. Since the large majority of these investigations 80 concern microcapsuled PCM or aggregated microcapsulated PCM, they have been gaining a 81 massive success thanks to a variety of experimental data, now available for verification. In details, 82 several studies have been focused on the variability of concrete mechanical behaviour with 83 varying the quantity of PCM or its thermal performance analysis associated to structural and 84 microstructural reliability of the material. Since microcapsulated additives may be responsible for 85 new voids and possible cracking effects, resulting in the material weak sections. In general, a 86 PCM content higher than 3% may be responsible for more than 50% reduction in the original 87 strength capability (i.e. compression and bending strength) which for sure needs to be taken into 88 account when designing structural components [12,13]. At the same time, given the PCM 89 capability to absorb released heat, they may be helpful in reducing curing-related cracks due to 90 their function of hydration heat absorber. Such promising function may be achieved by means of 91 a relatively smaller quantity of PCM, i.e. less than 2% [14]. Therefore, PCM inclusions may be 92 seen as a promising way to produce lightweight concretes with enhanced thermal mass by 93 improving both the mechanical and thermal performance of building envelope. To ensure 94 durability of the system, the breakage of the microcapsules during concrete production needs to 95 be avoided; to achieve this goal, robust microcapsules have been developed [15]. 96 97 All these analyses were also confirmed by large scale experiment in test-buildings or prototype 98 rooms, also named as cubicles [16,17]. This experiment configuration allowed to estimate the 99 TES capability of composite solutions even when applied to building envelope components and 100 energy systems in operating conditions, with varying climate and occupancy boundaries [18,19]. 101 In this panorama, Cabeza et al. (2007) [13] published an experimental study about two cubicles 102 made of prefabricated concrete panel, one of them was constructed with a conventional concrete 103 and the other one had 5wt.% of micro‐encapsulated PCM. Both cubicles were tested under real 104 summer weather conditions. Results showed that the cubicle with PCM provided more stable 105 temperature conditions in the internal ambient and a delay of the maximum peak temperature. 106 Time-zero experiments are becoming popular for the reasons explained above, i.e. to demonstrate 107 the effect of TES incorporation in more real conditions, e.g. in full scale continuously monitored 108 buildings. At the same time, durability assessment is still missing while studying the scientific 109 literature of the sector, since those few studies concerning TES or PCM performance during the 110
4 course of the time are pretty focused on TES-materials in particular, and not on the composite 111 system when integrated into building envelope or HVAC system [20]. That is the reason why this 112 paper wants to fill this gap by investigating the long-term behaviour of TES-doped system 113 represented by a concrete ceiling slab with PCM-incorporation aimed at stabilizing indoor air 114 temperature, energy saving and improving indoor comfort conditions, following the work 115 presented by Cellat et al. [21]. Therefore, in this paper, the durability of building materials with 116 PCM and the behaviour of the micro‐capsules inside these matrixes are investigated, since they 117 are not usually taken into account in most of the published studies so far. 118 119 However, these properties are considered of significant interest for builders, architects and 120 building engineers, to achieve better acceptance on these new materials. Therefore, the 121 experiment of this study represent a follow up of a previous experiment carried out more than one 122 decade before, in summer conditions, with the precise purpose to observe any evidence of 123 difference or degradation in the concrete with PCM cubicle. Additionally, a critical comparison 124 between the initial performance of the concrete with PCM system and the current status is 125 presented. 126 127 2. Experimental set‐up 128 129 In the experimental setup of Puigverd de Lleida (Spain), two house‐like cubicles made of 130 prefabricated concrete panels of 0.12 m of thickness were used in this study. These cubicles were 131 built in 2005 within a European project framework (MOPCON). Both cubicles have the same 132 dimensions (2.4×2.4×2.4 m) and orientation (N‐S, 0°), but one of them have conventional 133 concrete, and the other one 5wt.% of micro‐encapsulated PCM in the concrete matrix (Figure 1). 134 This fact allows the authors to evaluate and compare the effect of PCM incorporation in these 135 construction systems. The windows are also distributed with the same pattern in both cubicles, 136 having one at the east and west wall, and four windows in the south wall, as well as the metallic 137 door located in the north facade. The monitoring of the cubicles is continuous and it is evaluated 138 evaluating the data in a weekly basis; the results are shown for selected weeks that allow showing 139 the performance of the cubicles in different periods of the year. 140 141
5 Figure 1. Construction of the cubicles with prefabricated concrete panels in 2005 at the experimental 142 setup of Puigverd de Lleida (Spain) 143 144 In this application, the PCM was implemented as a passive cooling system to avoid indoor 145 overheating in summer conditions. For this reason, just three panels of concrete with PCM were 146 installed in the southern and western walls, and in the roof. The selected PCM was a commercial 147 micro‐encapsulated (Micronal DS 5001) with a melting point of 26 °C, and a phase change 148 enthalpy of 110 kJ/kg [22]. 149 150 The cubicles were instrumented to be able to measure and analyse their thermal performance in 151 terms of temperature of internal wall surfaces (East, West, North, South walls, roof and floor) and 152 also external South wall temperature, and indoor temperature and humidity of the cubicle. 153 Moreover, the meteorological station registered outdoor temperature and humidity, global solar 154 radiation over the horizontal plane, wind velocity and direction. All the data were collected every 155 5 minutes and memorized in dedicated data loggers of the facility. 156 157 In order to analyse the performance of the concrete with PCM system after a decade of the cubicle 158 construction, the same experiments from Cabeza et al. (2007) [13] were performed in the facility. 159 During the summer period, the evaluation of both concrete cubicles was done in free floating 160 conditions, where no cooling system was operating, hence the evolution of the temperatures can 161 be compared. On the other hand, the compressive strength was tested in 2005 once the concrete 162 was hardened, following the European standard UNE‐EN 12390‐3 and UNE‐EN 12504‐1. 163 164 165
6 Figure 2. Concrete test samples extracted from both cubicles 166 167 The same mechanical tests were performed to compare the properties of the concrete with PCM 168 after a decade. Therefore, two cylindrical specimens were extracted from the field installation, 169 i.e. one from the conventional concrete cubicle, and the other one from the concrete with PCM 170 cubicle (Figure 2). 171 172 3. Results 173 174 3.1. Thermal analyses comparison 175 176 In the experiments performed during summer, as previously mentioned, free floating conditions 177 were tested in both cubicles. From the whole experimental campaign, key representative results 178 are showed in this study to demonstrate the thermal performance of the concrete with PCM system 179 after a decade. 180 181 The internal air temperature profiles collected in both the cubicles are reported in Figure 3. Since 182 the free floating conditions experiments do not have active cooling supply, both cubicles present 183 difficulties to maintain the ambient temperature inside the comfort zone. However, the internal 184 ambient temperature of the concrete with PCM cubicle is always dampened down thanks to the 185 PCM inclusion and its peaks are always below the ones in the conventional concrete cubicle. In 186 fact, the daily fluctuation of air temperature in the cubicle with PCM is never higher than 4°C and 187 its thermal peaks are lower than the reference cubicle by about 2°C. 188 189
7 190 Figure 3. Outside and internal ambient temperatures in both cubicles in 2016 191 192 By looking at the external surface temperature from the South wall, big differences can be also 193 seen between the two cubicles (Figure 4). Conventional concrete cubicles present relatively higher 194 temperature peaks compared to the concrete with PCM case. Maximum temperatures achieved in 195 the South external surface wall in conventional concrete cubicle are between 34 °C and 39 °C, 196 while in the one with PCM mostly are around 28 °C. Figure 4 shows the very clear PCM effect, 197 which is able to store the heat coming from high temperature peak hours and postpone the thermal 198 peaks and decreasing temperature wave by about 4-6 hours (on July 13th, 14th and 17th). The results 199 corroborated the behaviour of PCM when included in a building material. As stated by several 200 authors [23,24], the phase change temperature of a PCM depends on the heating and cooling rate, 201 therefore in Figure 4 some peaks show that the melting of the PCM is not exactly at 26 ºC as 202 expected, but it appears at the range between 26 ºC and 28 ºC. 203 204
8 205 Figure 4. Surface temperature from the external South wall of conventional concrete and concrete with 206 PCM cubicles (12 – 18 July 2016) 207 208 Another example of the PCM effect can be observed in Figure 5, where the solidification and 209 melting process are clearly reported for both studied periods. Additionally, a delay on the 210 maximum peak temperature is observed in the concrete with PCM cubicle compared to the 211 conventional concrete cubicle, e.g. by about 4-5 hours. From these experiments authors observed 212 that the PCM incorporated in the concrete matrix is correctly working, storing the heat from daily 213 peak hours and releasing it later, once the outdoors temperature is dropping down. When 214 comparing both studied periods, summer 2005 and summer 2016, both periods had similar solar 215 radiation (reaching 1000 W/m2 every day), but the external temperature was higher in 2016 216 (reaching 32-36 ºC during the day and dropping to 10-16 ºC during night) than in 2005 (reaching 217 26-32 ºC during the day and dropping to 12-16 ºC during night). Therefore, the indoor temperature 218 was higher also in 2016. This is why, the difference between the cubicle with PCM and that 219 without PCM was 1-3 ºC in 2005 and reached 5-7 ºC in 2016. These results show how the effect 220 of the PCM is higher with more extreme weather conditions. 221 222
9 223 224 Figure 5. External surface South wall temperature in both cubicles in 2005 and 2016 225 226 The results from the experiments presented in this study were compared to the ones published in 227 the study of Cabeza et al. (2007) [13]. The effect observed in experiments performed in 2005 228 were the same as the ones seen nowadays. As an example, the external surface temperature of the 229 south wall in the concrete with PCM cubicle shows lower peaks compared to the conventional 230 concrete. Also, the solidification and melting process of the PCM added in the concrete are clearly 231 reflected in the external surface temperature. In addition, the authors in Cabeza et al. (2007) [13] 232 concluded that the effect of PCM included in the concrete matrix contributed to a temperature 233 reduction in the internal ambient of the cubicle. 234 235 236 237 238 239