Assessment of color discrimination of different light sources

Bustamante, Pedro; Acosta García, Ignacio Javier; León Rodríguez, Jesús; Campano, Miguel Ángel

Abstract

Light quality is a key parameter of building design, which is mainly defined by the perceived luminance and the color rendering. Nowadays, there is a wide variety of metrics that do not converge in the color rendition evaluation of current light sources. The obsolescence of the Color Rendering Index promoted the rise of new procedures to provide an accurate evaluation. However, the score provided by most of these metrics does not distinguish between color deviation and hue discrimination, giving a single value to assess the overall color perception allowed by a light source. In this context, a new study is proposed, based on the evaluation of seven different light sources, comparing the results of the most recent color rendering metrics and those observed using a Farnsworth–Munsell trial carried out with 115 participants. The results obtained show that there is a notable divergence between color rendition and hue discrimination, although there is a clear proportionality between both. Moreover, a clear relationship is observed between color discrimination and the correlative color temperature of light sources, providing a better hue distinction with cool light sources, even though the psychological preferences of the participants do not coincide with the optimal scenario for color discrimination.

Full text

buildings Article Assessment of Color Discrimination of Different Light Sources Pedro Bustamante , Ignacio Acosta * , Jesús León and Miguel Angel Campano   Citation: Bustamante, P.; Acosta, I.; León, J.; Campano, M.A. Assessment of Color Discrimination of Different Light Sources. Buildings 2021,11, 527. https://doi.org/10.3390/ buildings11110527 Academic Editor: Lambros T. Doulos Received: 11 October 2021 Accepted: 1 November 2021 Published: 8 November 2021 Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. Copyright: © 2021 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https:// creativecommons.org/licenses/by/ 4.0/). Instituto Universitario de Arquitectura y Ciencias de la Construcción, Universidad de Sevilla, 41004 Sevilla, Spain; [email protected] (P.B.); [email protected] (J.L.); [email protected] (M.A.C.) *Correspondence: [email protected]; Tel.: +34-64-7550-654 Abstract: Light quality is a key parameter of building design, which is mainly defined by the perceived luminance and the color rendering. Nowadays, there is a wide variety of metrics that do not converge in the color rendition evaluation of current light sources. The obsolescence of the Color Rendering Index promoted the rise of new procedures to provide an accurate evaluation. However, the score provided by most of these metrics does not distinguish between color deviation and hue discrimination, giving a single value to assess the overall color perception allowed by a light source. In this context, a new study is proposed, based on the evaluation of seven different light sources, comparing the results of the most recent color rendering metrics and those observed using a Farnsworth–Munsell trial carried out with 115 participants. The results obtained show that there is a notable divergence between color rendition and hue discrimination, although there is a clear proportionality between both. Moreover, a clear relationship is observed between color discrimination and the correlative color temperature of light sources, providing a better hue distinction with cool light sources, even though the psychological preferences of the participants do not coincide with the optimal scenario for color discrimination. Keywords: colorimetry; color rendition; daylighting; light spectra; Farnsworth–Munsell 1. Introduction and Objectives 1.1. Background At present, lighting technology is rapidly improving the energy efficiency of LED lamps, focusing on the reduction of energy consumption and the equivalent CO 2 emission [ 1 ]. However, in most cases, this development does not consider the implications of the current luminaires in color perception [ 2 ] and in human health [ 3 , 4 ] and well-being [ 5 ]. As argued by several researchers, urban and architectural lighting should take into account not only the quantity and distribution of light but also its quality [ 6 – 8 ] in providing a comfortable environment for users. In addition, the spectral distribution of the light sources is crucial for giving a safe environment in roadways and pedestrians areas, allowing a suitable color perception and hue discrimination [9,10]. Most of the luminaires currently on the market are based on LED technology, whose lamps generate a different spectral distribution compared to the older sodium-vapor, incandescent, halogen and fluorescent lamps, producing a noticeable variation in color perception. Specifically, LED lamps produce a notable variation in their chromatic perception depending on the short-wavelength spectrum [ 11 ]. LED light sources are affordable and produce a higher luminous flux with a lower energy consumption compared to the previous models. This shows the need for an accurate evaluation of the effects promoted by these new lamps in the field of color rendition [12]. Nowadays, the Color Rendering Index (CRI) is the most widespread metric for determining the hue deviation of any light source. This concept, presented in 1974 [ 13 ] and subsequently recognized by the Commission internationale de l’eclairage (CIE) [ 14 ], was proposed as a method for quantifying the color performance attained by fluorescent lamps. Based on the deviation of eight color samples in the CIE diagram, CRI uses a variable light Buildings 2021,11, 527. https://doi.org/10.3390/buildings11110527 https://www.mdpi.com/journal/buildings Buildings 2021,11, 527 2 of 17 source reference with a theoretically perfect rendition to determine the performance of the lamp under study. However, some inaccuracies can be observed in the CRI calculation, mostly in the non-uniform color distribution of the color space [ 15 ], the low saturation of the color sample selected for evaluating the hue deviation [ 16 ] and the choice of the light source of reference [ 17 ]. Considering these limitations, this metric was updated in 1999 to include six new illuminants [ 18 ], although it did not provide a satisfactory description of the color rendition of LED lamps. Subsequently, in 2010, the Color Quality Scale (CQS) [ 19 ] was proposed in order to provide an accurate calculation of color rendition for LED lamps. This new concept establishes 15 new color samples with a higher saturation than in previous metrics, an updated color space based on a CIE lab and a new Chromatic Adaptation Transform (CAT) recommended by the Color Measurement Committee (CMC), CMCCAT2000. This metric arose from the need to answer several issues related to color performance, among them the higher levels of naturalness and attractiveness provided by LED lamps in comparison with halogen light sources, despite the CRI score suggesting otherwise [20]. Two years later, Smet et al. determined an update of the CRI called CRI2012 [ 21 ], articulated in 210 real samples and on the colorimetric color appearance model (CAM) CRI-CAM02UCS uniform color space (UCS) [ 22 ]. This metric shows more accurate results than the original definition of CRI. One of the most recent procedures for providing a full description of the color perception allowed by a light source is TM-30-20, developed by the Illuminating Engineering Society (IES) [ 23 ]. This procedure compares the results for 99 samples from the CIE color space and establishes a continuous illuminant reference which varies depending on the color temperature of the light source under study. IES is currently promoting the use of this new procedure among luminaire manufacturers [ 24 ]. After the first proposal of this metric, TM-30-15 [ 25 ], in 2015 and prior to the previous update in 2018, the CIE developed the Color Fidelity Index (CIE 2017) [ 26 ] based on an optimized version of the color sample proposed by the IES aiming to improve the results obtained by the CRI. This new metric does not address an extensive analysis as in the case of TM-30-20, although it provides a more accurate calculation of color fidelity. Most of the metrics are based on the analysis of the sample deviation in a color space, but this is not the case with the Daylight Spectrum Index (DSI) [ 27 ]. This new concept, developed by Acosta et al., determines the color affinity of a studied lamp with daylighting, comparing the Spectral Power Distribution (SPD) of both sources according to the color sensitivity functions f(L), f(M) and f(S). Therefore, the aim of this definition is to determine the similarity of the color perception produced by a light source to that generated by daylighting, considering the natural source as the sole reference for producing a perfect rendition. In order to design luminaires with optimal color discrimination, an accurate measurement procedure is required. Accordingly, Thornton proposed the Color Discrimination Index (CDI), defined as the area enclosed by the eight CRI samples and normalized according to CIE Illuminant C [ 28 ]. Subsequent research by Boyce et al. [ 29 ] and Rea et al. [ 30 ] converge with Thornton’s proposal, although neither CRI nor CDI provide acceptable results for determining color discrimination. In an attempt to improve the understanding of the color discrimination allowed by a light source, Rea et al. identified the Gamut Area Index (GAI) [ 31 ] which is determined as the ratio between the surfaces limited by the eight color samples defined by CRI for the studied lamp and a reference, usually defined as daylighting. This metric is interesting, since the accuracy of the results obtained by means of GAI were tested using the Farnsworth-Munsell 100 Hue Test (FM-100) [ 32 ], determining better results than CRI with respect to color discrimination [33]. Given this context, it can be concluded that the gamut indices do not provide a suitable prediction of the ability of a light source to discretize colors. Previous studies warn of this Buildings 2021,11, 527 3 of 17 concern especially for highly composed spectra [ 34 ], which are of particular relevance since LED lamps usually produce this type of spectral distribution. Moreover, color performance is not the only variable to consider for a lighting design. Depending on the context, chromatic preference can vary, so the color rendition can be affected by boundary conditions [ 35 ]. According to this statement, Schanda et al. [ 36 ] assessed color fidelity for a picture gallery, selecting a multi-light-emitting diode for this particular case. For the same context, Feltrin et al. [ 37 ] concluded that the Correlated Color Temperature (CCT) has a noticeable impact on the perceived brightness of the artworks and is more decisive than the overall hue content or the color of the background. In a different scenario, Szabóet al. [ 38 ] analyzed the color preference for a shop, defining the suitable SPD for LED luminaires. Most recently, color preference was analyzed for a retail display, a supermarket and a restaurant by Lin et al. [ 2 ], with each case study obtaining different results. The research by Royer et al. [ 39 ] should also be noted, as they evaluate color preference with 25 participants. The results of this study conclude that the current color rendition metrics do not meet the criteria for color preference but can be predictable according to calculation models based on the metrics defined by TM-30-20; the Fidelity Index (Rf) and the Gamut Index (Rg). The best way to determine the accuracy of the color rendition metrics relies on the assessment of surveys and objective trials, as deduced from the following studies: Houser et al. [ 40 ] carried out in-depth research, analyzing 40 surveys to evaluate whiteness perception under different LED lamps, confirming that very short-wavelength light is necessary to induce whiteness. Jost-Boissard et al. [ 20 ] evaluated the color quality promoted by LED lamps, analyzing a wide range of warm and cool light sources from over 80 surveys . At the same time, Dangol et al. [ 41 ] studied the accuracy of CRI, CQS and CRI2012 by means of 20 surveys using different LED lamps with a CCT from warm to cool. The authors established a high correlation between the metrics studied. One of the most recent examples is the study by Gu et al. [ 42 ], which analyzed several metrics using 10 surveys and concluded that CAM02-UCS color space is one of the best for the evaluation of hue deviation. Considering the development of tests for determining the ability of a light source to discretize color, it is worth noting that the tests must provide an objective quantification of the results obtained [ 43 ]. Following this, the research by Esposito et al. [ 44 ] defined a novel measure of color discrimination, Rd, determining a score according to the numbers of transpositions carried out in the FM-100 trial. Therefore, an Rd close to 0 means that the light source provides almost perfect color discrimination, while a score greater than 16 represents a poor discrimination of hues. As seen from the above, color rendition metrics are constantly evolving, given that there are no solid criteria for determining the chromatic performance of a light source [ 45 ]. Moreover, most of the metrics focus on the quantification of the color deviation [ 33 ], ignoring the need to distinguish colors with similar hues, brightness and saturation. 1.2. Aim and Objectives Considering this general background, a new study is proposed based on the assessment of the color discrimination provided by seven light sources with different spectrometry, comparing the results of the most recent color rendering metrics and those observed according to a FM-100 trial carried out by 115 participants, totaling 805 surveys. The proposed test can determine the ability to distinguish different color ranges in an objective and quantifiable way. The proposed research aims to determine the relationship between the color deviation defined by the current metrics and the color discrimination of three different hue ranges, considering other variables, such as the CCT and the color preferences of the participants. Although this study follows a similar methodology to that of previous articles [27,31,46] , it offers new nuances highlighting the novelty of the results described below: Buildings 2021,11, 527 4 of 17 • Two recently proposed metrics are evaluated, TM-30-20 and DSI. The precision of these metrics had not previously been evaluated for color discrimination. • The study sample, made up of 805 surveys and color tests, is noticeable larger than in previous research [ 20 , 40 , 42 , 47 ], giving considerable accuracy for the conclusions obtained. • This study establishes a new quantification of the score provided by the FM-100 trial [ 43 ] in order to adapt the results to the proposed methodology, aiming to provide an objective assessment of the color discrimination, following the procedure established by Esposito et al. [44]. • Finally, this research provides a relationship between the scores given by most of the current color rendering metrics and the ability to discretize the hues, considering other characteristics of the light source, such as CCT and SPD. 2. Methodology 2.1. Light Source Testing Box The assessment of the color discrimination is based on the analysis of 115 colorimetric surveys for 7 individual light sources, making a total of 805 surveys, where respondents answer questions on color rendition, color temperature perception, saturation of the samples and chromatic preference for two scenarios in a light source testing box. Figure 1shows a flowchart that describes the methodology carried out in this research. Buildings 2021, 11, x FOR PEER REVIEW 4 of 17 • Two recently proposed metrics are evaluated, TM-30-20 and DSI. The precision of these metrics had not previously been evaluated for color discrimination. • The study sample, made up of 805 surveys and color tests, is noticeable larger than in previous research [20,40,42,47], giving considerable accuracy for the conclusions obtained. • This study establishes a new quantification of the score provided by the FM-100 trial [43] in order to adapt the results to the proposed methodology, aiming to provide an objective assessment of the color discrimination, following the procedure established by Esposito et al. [44]. • Finally, this research provides a relationship between the scores given by most of the current color rendering metrics and the ability to discretize the hues, considering other characteristics of the light source, such as CCT and SPD. 2. Methodology 2.1. Light Source Testing Box The assessment of the color discrimination is based on the analysis of 115 colorimetric surveys for 7 individual light sources, making a total of 805 surveys, where respondents answer questions on color rendition, color temperature perception, saturation of the samples and chromatic preference for two scenarios in a light source testing box. Figure 1 shows a flowchart that describes the methodology carried out in this research. Figure 1. Flowchart of the proposed methodology. In addition, the participants also carry out a color discrimination exercise: the FM- 100 trial, which consists in the arrangement of a selection of color samples based on similarity in hue. It measures the ability to isolate and organize color caps with small variations in the nuances of the hues. The color sample has constant values for luminosity and saturation, and the hues are selected from the Munsell color system. As described in the background, several previous studies [31,43] use the FM-100 trial to analyze the capability of a light source to render colors as well as the accuracy of proposed colorimetric metrics. The survey sample is made up of 54 men and 61 women aged between 20 and 27 years old, all of them volunteer university students, since age significantly affects the decrease of the sensitivity of the short-wavelength photoreceptors [48]. Thus, it is assumed that the lens density of the retina is similar for all participants. Prior to the color discrimination test, the survey includes questions on visual impairment, confirming that all participants have suitably clear eyesight. To ensure there are no respondents suffering from color blindness, each survey includes a random Ishihara test [49,50], ensuring that all the analyzed surveys have been completed by participants with suitable color discrimination. The light source testing box, seen in Figure 2, is made of white coated medium-den- sity fiberboard (MDF) with inner dimensions of 60 cm wide by 60 cm deep by 60 cm high. The white paint has a constant reflectance of 89% from 700 to 430 nm, decreasing almost linearly from 430 to 400 nm up to a value close to 50%. The neutral appearance of the Figure 1. Flowchart of the proposed methodology. In addition, the participants also carry out a color discrimination exercise: the FM-100 trial, which consists in the arrangement of a selection of color samples based on similarity in hue. It measures the ability to isolate and organize color caps with small variations in the nuances of the hues. The color sample has constant values for luminosity and saturation, and the hues are selected from the Munsell color system. As described in the background, several previous studies [ 31 , 43 ] use the FM-100 trial to analyze the capability of a light source to render colors as well as the accuracy of proposed colorimetric metrics. The survey sample is made up of 54 men and 61 women aged between 20 and 27 years old, all of them volunteer university students, since age significantly affects the decrease of the sensitivity of the short-wavelength photoreceptors [ 48 ]. Thus, it is assumed that the lens density of the retina is similar for all participants. Prior to the color discrimination test, the survey includes questions on visual impairment, confirming that all participants have suitably clear eyesight. To ensure there are no respondents suffering from color blindness, each survey includes a random Ishihara test [ 49 , 50 ], ensuring that all the analyzed surveys have been completed by participants with suitable color discrimination. The light source testing box, seen in Figure 2, is made of white coated medium-density fiberboard (MDF) with inner dimensions of 60 cm wide by 60 cm deep by 60 cm high. The white paint has a constant reflectance of 89% from 700 to 430 nm, decreasing almost linearly Buildings 2021,11, 527 5 of 17 from 430 to 400 nm up to a value close to 50%. The neutral appearance of the testing box aims to minimize the visual judgement closely related to the lit environment [ 51 ]. Six electric light sources are located in the top of the box, hidden by a white panel on the front of the box and an opal diffuser below the luminaire space. Therefore, avoiding any direct visualization of the lamp, a single-blind test can be developed to prevent any potential prejudice of the respondents. The lamps run along a guided tray in order to situate the analyzed light source exactly in the center of the testing box aided by magnetic stops. The luminous flux of the lamps is controlled by several dimmers in order to provide the same illuminance value in the testing box for all lamps, irrespective of their efficiency. Finally, the participants are placed in front of the test box, sitting 50 cm apart in natural daylight conditions or in an empty dark room with a constant temperature and humidity environment [52]. Buildings 2021, 11, x FOR PEER REVIEW 5 of 17 testing box aims to minimize the visual judgement closely related to the lit environment [51]. Six electric light sources are located in the top of the box, hidden by a white panel on the front of the box and an opal diffuser below the luminaire space. Therefore, avoiding any direct visualization of the lamp, a single-blind test can be developed to prevent any potential prejudice of the respondents. The lamps run along a guided tray in order to situate the analyzed light source exactly in the center of the testing box aided by magnetic stops. The luminous flux of the lamps is controlled by several dimmers in order to provide the same illuminance value in the testing box for all lamps, irrespective of their efficiency. Finally, the participants are placed in front of the test box, sitting 50 cm apart in natural daylight conditions or in an empty dark room with a constant temperature and humidity environment [52]. Figure 2. Analysis of color rendering of a cool, neutral and warm LED lamp in the light source testing box. Upper line: Objects used for the scenarios of trial 1: Two paintings and fruits; lower line: FM-test samples and color checker. 2.2. Light Sources Analyzed As seen in Figure 3, both the daylight conditions and the electric light sources located inside the testing box are measured using a Konica Minolta CL-70F spectrometer (Konica Minolta, Tokyo, Japan) in order to adjust the luminous flux to a constant value close to 500 lx. A PCE-CSM 8 reflectance spectrophotometer (PCE Instruments, Alicante, Spain) is used to determine the spectral reflectance of the color samples as well as the hue variation of the FM-100 color cards. Spectral resolutions of both equipment are listed in Table 1. Figure 3. Measuring the SPD and illuminance of the light source and the spectral reflectance of the color samples. Figure 2. Analysis of color rendering of a cool, neutral and warm LED lamp in the light source testing box. Upper line: Objects used for the scenarios of trial 1: Two paintings and fruits; lower line: FM-test samples and color checker. 2.2. Light Sources Analyzed As seen in Figure 3, both the daylight conditions and the electric light sources located inside the testing box are measured using a Konica Minolta CL-70F spectrometer (Konica Minolta, Tokyo, Japan) in order to adjust the luminous flux to a constant value close to 500 lx . A PCE-CSM 8 reflectance spectrophotometer (PCE Instruments, Alicante, Spain) is used to determine the spectral reflectance of the color samples as well as the hue variation of the FM-100 color cards. Spectral resolutions of both equipment are listed in Table 1. Table 1. Properties of the equipment used for this study. Instrument Spectral Wavelength Range Output Wavelength Pitch Accuracy Konica Minolta CL-70F spectrometer 380 to 780 nm 1 nm Ev (Illuminance): ±5% ±1% per digit xy: 0.003 (at 800 lx) PCE-CSM 8 reflectance spectrophotometer 400 to 700 nm 10 nm ∆ E*ab (CIELAB distance metric) 0.2 The first light source assessed corresponds to daylighting, with a variable CCT between 5500 and 6600 K, achieving a similar SPD to the standard spectrum D65. Daylight conditions were measured for a north orientation matching the typical sky conditions of spring and summer in Seville (southern Spain), the location where the trial is carried out. All tests were developed under daylight conditions avoiding direct solar incidence inside Buildings 2021,11, 527 6 of 17 the testing box. Figure 4represents the spectral measurements of daylight inside the testing box for three specific days during which the tests were carried out. As can be deduced, the short wavelength was affected by the spectral reflectance of the white paint, slightly reducing the power distribution of daylight from 380 to 430 nm. Buildings 2021, 11, x FOR PEER REVIEW 5 of 17 testing box aims to minimize the visual judgement closely related to the lit environment [51]. Six electric light sources are located in the top of the box, hidden by a white panel on the front of the box and an opal diffuser below the luminaire space. Therefore, avoiding any direct visualization of the lamp, a single-blind test can be developed to prevent any potential prejudice of the respondents. The lamps run along a guided tray in order to situate the analyzed light source exactly in the center of the testing box aided by magnetic stops. The luminous flux of the lamps is controlled by several dimmers in order to provide the same illuminance value in the testing box for all lamps, irrespective of their efficiency. Finally, the participants are placed in front of the test box, sitting 50 cm apart in natural daylight conditions or in an empty dark room with a constant temperature and humidity environment [52]. Figure 2. Analysis of color rendering of a cool, neutral and warm LED lamp in the light source testing box. Upper line: Objects used for the scenarios of trial 1: Two paintings and fruits; lower line: FM-test samples and color checker. 2.2. Light Sources Analyzed As seen in Figure 3, both the daylight conditions and the electric light sources located inside the testing box are measured using a Konica Minolta CL-70F spectrometer (Konica Minolta, Tokyo, Japan) in order to adjust the luminous flux to a constant value close to 500 lx. A PCE-CSM 8 reflectance spectrophotometer (PCE Instruments, Alicante, Spain) is used to determine the spectral reflectance of the color samples as well as the hue variation of the FM-100 color cards. Spectral resolutions of both equipment are listed in Table 1. Figure 3. Measuring the SPD and illuminance of the light source and the spectral reflectance of the color samples. Figure 3. Measuring the SPD and illuminance of the light source and the spectral reflectance of the color samples. Buildings 2021, 11, x FOR PEER REVIEW 6 of 17 Table 1. Properties of the equipment used for this study. Instrument Spectral Wavelength Range Output W avelength Pitch Accuracy Konica Minolta CL-70F spectrometer 380 to 780 nm 1 nm Ev (Illuminance): ±5% ± 1% per digit xy: 0.003 (at 800 lx) PCE-CSM 8 reflectance spectrophotometer 400 to 700 nm 10 nm ΔE*ab 0.2 The first light source assessed corresponds to daylighting, with a variable CCT between 5500 and 6600 K, achieving a similar SPD to the standard spectrum D65. Daylight conditions were measured for a north orientation matching the typical sky conditions of spring and summer in Seville (southern Spain), the location where the trial is carried out. All tests were developed under daylight conditions avoiding direct solar incidence inside the testing box. Figure 4 represents the spectral measurements of daylight inside the testing box for three specific days during which the tests were carried out. As can be deduced, the short wavelength was affected by the spectral reflectance of the white paint, slightly reducing the power distribution of daylight from 380 to 430 nm. Figure 4. SPD of the daylight conditions perceived inside the testing box. In addition to daylight, six electric lamps were assessed by the participants in this study. In order to evaluate a wide range of luminaire types, three LED lamps—with a warm, neutral and cool CCT—are arranged in the testing box, together with an incandescent lamp and two compact fluorescent lamps with cool and warm CCTs. Figure 5 shows the SPDs for the lamps selected. Figure 5. SPDs of the electric light sources tested. Figure 4. SPD of the daylight conditions perceived inside the testing box. In addition to daylight, six electric lamps were assessed by the participants in this study. In order to evaluate a wide range of luminaire types, three LED lamps—with a warm, neutral and cool CCT—are arranged in the testing box, together with an incandescent lamp and two compact fluorescent lamps with cool and warm CCTs. Figure 5shows the SPDs for the lamps selected. Neither the multi-channel LED lamps nor the high-pressure sodium-vapor and metal halide bulbs are evaluated in the testing box due to the limitations of the box dimensions, boot time and lower frequency of the application to indoor spaces. The main characteristics of the light sources tested, as well as the color rendition for most the metrics, are shown in Table 2. Buildings 2021,11, 527 7 of 17 Buildings 2021, 11, x FOR PEER REVIEW 6 of 17 Table 1. Properties of the equipment used for this study. Instrument Spectral Wavelength Range Output W avelength Pitch Accuracy Konica Minolta CL-70F spectrometer 380 to 780 nm 1 nm Ev (Illuminance): ±5% ± 1% per digit xy: 0.003 (at 800 lx) PCE-CSM 8 reflectance spectrophotometer 400 to 700 nm 10 nm ΔE*ab 0.2 The first light source assessed corresponds to daylighting, with a variable CCT between 5500 and 6600 K, achieving a similar SPD to the standard spectrum D65. Daylight conditions were measured for a north orientation matching the typical sky conditions of spring and summer in Seville (southern Spain), the location where the trial is carried out. All tests were developed under daylight conditions avoiding direct solar incidence inside the testing box. Figure 4 represents the spectral measurements of daylight inside the testing box for three specific days during which the tests were carried out. As can be deduced, the short wavelength was affected by the spectral reflectance of the white paint, slightly reducing the power distribution of daylight from 380 to 430 nm. Figure 4. SPD of the daylight conditions perceived inside the testing box. In addition to daylight, six electric lamps were assessed by the participants in this study. In order to evaluate a wide range of luminaire types, three LED lamps—with a warm, neutral and cool CCT—are arranged in the testing box, together with an incandescent lamp and two compact fluorescent lamps with cool and warm CCTs. Figure 5 shows the SPDs for the lamps selected. Figure 5. SPDs of the electric light sources tested. Figure 5. SPDs of the electric light sources tested. Table 2. Main colorimetric characteristics of the light sources studied in the testing box. Abbreviation DL L27 L40 L65 IN FL65 FL25 Description Daylight CIE D65 LED 2700K LED 4000K LED 6500K Incandescent Fluorescent 6500K Fluorescent 2500K CCT K 5500–6500 2754 4199 5692 2538 6307 2406 CRI Ra 100 83 84 83 99 87 84 GAI D65 100 47 72 83 42 105 49 GAI CRI 100 91 86 87 97 106 112 CQS 100 84 84 81 99 86 78 CIE 224 2017 100 85 84 83 99 86 72 TM-30-20 Rf 100 85 84 83 99 86 72 TM-30-20 Rg 100 96 92 92 99 103 106 DSI 100 80 85 87 83 73 57 In order to guarantee the single-blind test, the lamps are switched on at random to avoid participants identifying the luminaires based on their switch-on position. The time frame for evaluation of color perception is set to 60 s, while the interval for the FM-100 trial is 90 s long so that respondents have the same boundary conditions when assessing color preference and chromatic deviation. 2.3. Color Samples The survey and test procedures are based on the perception and color discrimination deduced from several objects and scenarios contained in the testing box. On the one hand, two well-known examples of paintings—Girl with a Pearl Earring (1665, Johannes Vermeer) and The Starry Night (1889, Vincent van Gogh)—are used to represent the color preference on skin as well as cool hues. On the other hand, a second scenario with fruit shows warm and neutral hues, with red, orange, yellow and green as predominant, natural and recognized colors. The assessment of these scenarios also provides an approach to the respondents’ color preference, irrespective of the hue deviation or discrimination promoted by the studied light sources. Figure 6shows the spectral reflectance measured with the reflectance spectrophotometer on the most representative color areas for both the paintings and fruits sample, highlighting the measured points and average results for skin, blue hues and brown in the case of Girl with a Pearl Earring and the blue and yellow hues in The Starry Night. Buildings 2021,11, 527 8 of 17 Buildings 2021, 11, x FOR PEER REVIEW 8 of 17 Figure 6. Spectral reflectance values of color samples. From above to below: Girl with a Pearl Earring, The Starry Night and fruit scenario. The second trial is based on the analysis of the FM-100 test, where respondents have to order caps with different hues according to their affinity with the color references. Seven different cap combinations were used for this study in order to ensure the singleblind test. Each FM trial shows three lines of hues, red, green and blue, corresponding to the sensitivity response of the color photoreceptors. Both FM caps and light sources were selected at random in each trial. These trials provide a subsequent objective quantification of the ability of a light source to discretize similar colors [31,44]. Figure 6. Spectral reflectance values of color samples. From above to below: Girl with a Pearl Earring, The Starry Night and fruit scenario. The second trial is based on the analysis of the FM-100 test, where respondents have to order caps with different hues according to their affinity with the color references. Seven different cap combinations were used for this study in order to ensure the single-blind test. Each FM trial shows three lines of hues, red, green and blue, corresponding to the sensitivity response of the color photoreceptors. Both FM caps and light sources were selected at random in each trial. These trials provide a subsequent objective quantification of the ability of a light source to discretize similar colors [31,44]. Buildings 2021,11, 527 9 of 17 2.4. Quantification of the Results Following the methodology described above, the color perception and discrimination of hues are assessed by means of surveys and tests. In order to quantify the color rendition, a value of 50% is given for a “sufficient” rendering, while a value of 100% is considered for an “excellent” performance. Accordingly, the rating values between both limits are determined linearly between 50 and 100%. Moreover, assuming that daylight provides a perfect color rendering, as deduced from this study and previous ones [ 27 , 33 ], all scores obtained are modified according to the average score of natural light as Equation (1) states: Pi(MOD)(%)=Pi·100 PDL(AVE) (1) where Pi(MOD) is the value of color rendering considered for the studied light source, Piis the color rendering value obtained from the sample of surveys and P DL(AVE) is the average score of the color rendering of daylighting. The analysis of the FM-100 trial requires a different approach to that described above. For this quantification, the method proposed by Esposito et al. [ 44 ] is applied, which depends on the number of transpositions of the color caps. Accordingly, a light source causing an arrangement of one transposition in the FM-100 trial would be attributed with an error score of 4, while two transpositions correspond to an error of 8, three transpositions to a score of 12 and so on. The total error score corresponds to the sum of all tray-specific scores, as deduced from Equation (2): Rd= n ∑ i=1 Rd,i(2) where R d is the score that corresponds to the number of transpositions measured for each tray in the FM-100 trial. The score obtained will be translated into a percentile value from 0 to 100%. 3. Analysis of Results 3.1. Color Rendering of the Light Sources According to the results obtained from the surveys and following the methodology described above, the subjective perception of the color rendition allowed by the tested light sources is shown in Figure 7a, representing the maximum and minimum values as well as the average results weighted depending on the maximum score provided to daylight. The standard error is also shown on the secondary vertical axis. It should be noted that the subjective color renditions do not necessarily have to correspond to the quantification of color rendering as understood by current metrics, since the subjective preference of the respondent can affect the final score. As deduced from Figure 7a, the standard error of the results obtained for all light sources was between 1.7 and 1.9%, including daylight (DL), with an average score of 1.8%. This deviation is considered sufficient to address the color rendition defined by the subjective perception of the respondents. It should be noted that this study was limited by the scenarios proposed so that conclusions cannot be applied universally. In addition, Figure 7b shows the perceived CCT of the 7 tested light sources, defining maximum, minimum and average scores from very warm lamps ( − 50%) to very cool lamps (+50%), considering 0% a perfect neutral appearance of the color temperature. The real CCT value is also shown on the secondary vertical axis. As expected, daylight (DL) gives the maximum color rendition, followed by the neutral white LED lamp (L40), which shows a performance of 97%. The cool (L65) and warm (L27) LED luminaires obtain scores of 92 and 90%, respectively. It can be deduced that the tested LED sources provide a higher color rendering than the rest of the lamps, with an average score of 93%. Moreover, it is worth noting that the incandescent lamp (IN) does not achieve a perfect color performance as defined by most of the metrics. Finally, it can also be deduced that, according to the studied scenarios, the cool fluorescent lamp Buildings 2021,11, 527 16 of 17 17. Royer, M.P. What Is the Reference? An Examination of Alternatives to the Reference Sources Used in IES TM-30-15. LEUKOS 2016,13, 71–89. [CrossRef] 18. CIE. Colour Rendering (TC1-33 Closing Remarks); Commission Internationale de l’Éclairage: Vienna, Austria, 1999. 19. Davis, W.; Ohno, Y. Color quality scale. Opt. Eng. 2010,49, 033602. [CrossRef] 20. Jost-Boissard, S.; Avouac, P.; Fontoynont, M. Assessing the colour quality of LED sources: Naturalness, attractiveness, colourfulness and colour difference. Light. Res. Technol. 2014,47, 769–794. [CrossRef] 21. Smet, K.; Schanda, J.; Whitehead, L.; Luo, R. CRI2012: A proposal for updating the CIE colour rendering index. Light. Res. Technol. 2013,45, 689–709. [CrossRef] 22. Li, C.; Ronnier Luo, M.; Li, C.; Cui, G. The CRI-CAM02UCS colour rendering index. Color Res. Appl. 2012 ,37, 160–167. [CrossRef] 23. Illuminating Engineering Society. IES Method for Evaluating Light Source Color Rendition, IES Technical Memorandum (TM) 30-20, IESNA; IES: New York, NY, USA, 2020. Available online: https://store.ies.org/product/tm-30-20-ies-method-for-evaluating- light-source-color-rendition/ (accessed on 17 July 2021). 24. Royer, M.P. IES TM-30-15 Is Approved—Now What? LEUKOS 2016,12, 3–5. [CrossRef] 25. Illuminating Engineering Society. IES Method for Evaluating Light Source Color Rendition, IES Technical Memorandum (TM) 30-15, IESNA; IES: New York, NY, USA, 2015. Available online: https://www.ies.org/about-outreach/position-statements/ps-11-18- ies-position-on-tm-30-18-ies-method-for-evaluating-light-source-color-rendition/ (accessed on 21 January 2020). 26. CIE. CIE 2017 Colour Fidelity Index for Accurate Scientific Use; Commission Internationale de l’Éclairage: Vienna, Austria, 2017. 27. Acosta, I.; León, J.; Bustamante, P. Daylight spectrum index: A new metric to assess the affinity of light sources with day-lighting. Energies 2018,11, 2545. [CrossRef] 28. Thornton, W.A. Color-Discrimination Index. J. Opt. Soc. Am. 1972,62, 191–194. [CrossRef] [PubMed] 29. Boyce, P. Illuminance, lamp type and performance on a colour discrimination task. Light. Res. Technol. 1976 ,8, 195–199. [CrossRef] 30. Boyce, P.; Simons, R. Hue discrimination and light sources. Light. Res. Technol. 1977,9, 125–140. [CrossRef] 31. Rea, M.S.; Freyssinier-Nova, J.P. Color rendering: A tale of two metrics. Color Res. Appl. 2008,33, 192–202. [CrossRef] 32. Farnsworth, D. The Farnsworth-Munsell 100-Hue and Dichotomous Tests for Color Vision. J. Opt. Soc. Am. 1943 ,33, 568–574. [CrossRef] 33. Rea, M.; Freyssinier, J. Color rendering: Beyond pride and prejudice. Color Res. Appl. 2010,35, 401–409. [CrossRef] 34. Royer, M.P.; Houser, K.W.; Wilkerson, A.M. Color discrimination capability under highly structured spectra. Color Res. Appl. 2011 , 37, 441–449. [CrossRef] 35. Royer, M.P.; Wei, M. The Role of Presented Objects in Deriving Color Preference Criteria from Psychophysical Studies. LEUKOS 2017,13, 143–157. [CrossRef] 36. Schanda, J.; Csuti, P.; Szabó, F. Colour fidelity for picture gallery illumination, Part 1: Determining the optimum light-emitting diode spectrum. Light. Res. Technol. 2014,47, 513–521. [CrossRef] 37. Feltrin, F.; Leccese, F.; Hanselaer, P.; Smet, K.A.G. Impact of Illumination Correlated Color Temperature, Background Lightness, and Painting Color Content on Color Appearance and Appreciation of Paintings. LEUKOS 2019,16, 25–44. [CrossRef] 38. Szabó, F.; Kéri, R.; Schanda, J.; Csuti, P.; Wilm, A.; Baur, E. A study of preferred colour rendering of light sources: Shop lighting. Light. Res. Technol. 2015,48, 286–306. [CrossRef] 39. Royer, M.; Wei, M.; Wilkerson, A.; Safranek, S. Experimental validation of colour rendition specification criteria based on ANSI/IES TM-30-18. Light. Res. Technol. 2019,52, 323–349. [CrossRef] 40. Houser, K.W.; Wei, M.; David, A.; Krames, M. Whiteness Perception under LED Illumination. LEUKOS 2014 ,10, 165–180. [CrossRef] 41. Dangol, R.; Bhusal, P.; Halonen, L. Performance of colour fidelity metrics. Light. Res. Technol. 2014,47, 897–908. [CrossRef] 42. Gu, H.; Luo, M.R.; Liu, X. Testing different colour rendering metrics using colour difference data. Light. Res. Technol. 2016 ,49, 539–560. [CrossRef] 43. Esposito, T. An Adjusted Error Score Calculation for the Farnsworth-Munsell 100 Hue Test. LEUKOS 2019 ,15, 195–202. [CrossRef] 44. Esposito, T.; Houser, K. A new measure of colour discrimination for LEDs and other light sources. Light. Res. Technol. 2017 ,51, 5–23. [CrossRef] 45. De Beer, E.; Van Der Burgt, P.; Van Kemenade, J. Another Color Rendering Metric: Do We Really Need It, Can We Live without It? LEUKOS 2016,12, 51–59. [CrossRef] 46. O’Connor, D.A.; Davis, R.G. Lighting for the elderly: The effects of light source spectrum and illuminance on color discrimination and preference. LEUKOS J. Illum. Eng. Soc. North Am. 2005,2, 123–132. [CrossRef] 47. Dangol, R.; Islam, M.; LiSc, M.H.; Bhusal, P.; Puolakka, M.; Halonen, L. Subjective preferences and colour quality metrics of LED light sources. Light. Res. Technol. 2013,45, 666–688. [CrossRef] 48. Panda-Jonas, S.; Jonas, J.B.; Jakobczyk-Zmija, M. Retinal Photoreceptor Density Decreases with Age. Ophthalmology 1995 ,102, 1853–1859. [CrossRef] 49. Ishihara, S. Tests for Color-Blindness; Hongo Harukicho: Tokyo, Japan, 1917. 50. Birch, J. Efficiency of the Ishihara test for identifying red-green colour deficiency. Ophthalmic Physiol. Opt. 1997 ,17, 403–408. [CrossRef] [PubMed] 51. Chen, W.; Huang, Z.; Liu, Q.; Pointer, M.R.; Liu, Y.; Gong, H. Evaluating the color preference of lighting: The light booth matters. Opt. Express 2020,28, 14874–14883. [CrossRef] [PubMed] Buildings 2021,11, 527 17 of 17 52. ISO. ISO 7730:2005—Ergonomics of the Thermal Environment—Analytical Determination and Interpretation of Thermal Comfort Using Calculation of the PMV and PPD Indices and Local Thermal Comfort Criteria; International Organization for Standardization: Geneva, Switzerland, 2005. 53. Huang, Z.; Chen, W.; Liu, Q.; Wang, Y.; Pointer, M.R.; Liu, Y.; Liang, J. Towards an optimum colour preference metric for white light sources: A comprehensive investigation based on empirical data. Opt. Express 2021,29, 6302–6319. [CrossRef]