Thermal and lighting consumption savings in classrooms retrofitted with shading devices in a hot climate

Calama-González, Carmen María; Suárez, Rafael; León-Rodríguez, Ángel Luis

Abstract

Most educational buildings in southern Spain do not meet current energy requirements as weak thermal envelopes and the lack of cooling systems lead to severe discomfort in classrooms, especially when temperatures are above 30 °C. Given that global warming is expected to worsen this situation in coming decades, one of the first steps to be taken is to protect window openings from high levels of solar radiation by adding shading devices to reduce indoor temperatures and improve visual comfort. The aim of this research is to evaluate the reduction in thermal and lighting consumption in a classroom where a solar protection system in the form of an egg-crate shading device was installed. Two classrooms—one with an egg-crate device and another with no shading system—were monitored and compared for a whole year. The use of an egg-crate device in these classrooms reduced indoor operative temperatures during warmer periods while also improving indoor natural illuminance levels. Moreover, annual electric air conditioning consumption decreased by approximately 20%, with a 50% reduction in electric lighting consumption. These savings in electricity were largely conditioned by the use patterns observed in these ambient systems.

Full text

energies Article Thermal and Lighting Consumption Savings in Classrooms Retrofitted with Shading Devices in a Hot Climate Carmen María Calama-González * , Rafael Suárez and Ángel Luis León-Rodríguez Instituto Universitario de Arquitectura y Ciencias de la Construcción, Escuela Técnica Superior de Arquitectura, Universidad de Sevilla, Av. Reina Mercedes 2, 410012 Seville, Spain; rsuar[email protected] (R.S.); [email protected] (Á.L.L.-R.) *Correspondence: [email protected]; Tel.: +34-954-559-517 Received: 23 August 2018; Accepted: 15 October 2018; Published: 17 October 2018   Abstract: Most educational buildings in southern Spain do not meet current energy requirements as weak thermal envelopes and the lack of cooling systems lead to severe discomfort in classrooms, especially when temperatures are above 30 ◦ C. Given that global warming is expected to worsen this situation in coming decades, one of the first steps to be taken is to protect window openings from high levels of solar radiation by adding shading devices to reduce indoor temperatures and improve visual comfort. The aim of this research is to evaluate the reduction in thermal and lighting consumption in a classroom where a solar protection system in the form of an egg-crate shading device was installed. Two classrooms—one with an egg-crate device and another with no shading system—were monitored and compared for a whole year. The use of an egg-crate device in these classrooms reduced indoor operative temperatures during warmer periods while also improving indoor natural illuminance levels. Moreover, annual electric air conditioning consumption decreased by approximately 20%, with a 50% reduction in electric lighting consumption. These savings in electricity were largely conditioned by the use patterns observed in these ambient systems. Keywords: school buildings; energy performance; energy savings; shading devices; solar radiation; daylight; illuminance; energy consumption; Mediterranean climate; overheating 1. Introduction European Directive 2012/27/EU [ 1 ] provides guidelines for developing retrofitting actions in public buildings within Europe. Educational buildings make up a large part of the building stock currently in need of refurbishment and therefore account for much of the overall energy consumption, and consequent expense to national budgets [2]. The increasing average world temperatures resulting from climate change noticeably affect the building sector, and an increase in cooling demands is expected in 2000–2100 [ 3 ]. In summer, high outdoor temperatures lead to increased air conditioning consumption [ 4 ] or worsened comfort conditions with high indoor temperatures. Several studies analysed solutions for improving energy efficiency and reducing energy consumption in schools, favouring passive techniques rather than mechanical solutions for improving energy performance [ 5 ]. Rospi et al. analysed several schools in southern Italy, calculating the difference between measured and simulated consumption. After assessing several passive strategies of the building envelope, the authors concluded that actions on windows result in higher primary energy savings [ 6 ]. This solution is of great importance in climates with higher solar radiation levels, given the high internal loads of school buildings (mainly due to high occupancy). In addition, in the absence of proper shading devices, there were noticeable heat gains through glazed surfaces. These systems Energies 2018,11, 2790; doi:10.3390/en11102790 www.mdpi.com/journal/energies Energies 2018,11, 2790 2 of 17 were therefore considered potential components for the reduction of energy consumption, but this is also conditioned by user patterns, as concluded in the laboratory experiments by Zeiler et al. [7]. While solar radiation through glazed surfaces severely affects indoor temperatures and visual comfort, heat gains through window openings improve natural illuminance levels and increase indoor temperatures in winter, causing visual discomfort and overheating in summer. Although solar energy facilitates the passive heating of buildings, excessive solar gains can lead to overheating and glare, so that solar control systems must therefore cover aspects such as thermal and visual comfort and energy saving. Although it should be possible to look out and maintain visual contact with the exterior while respecting the architectural aesthetics of the building, the main function of shading devices is to reduce solar gains in the summer season. Various authors have attempted to establish a classification [ 8 ] and comparative evaluation of different solar-control systems [ 9 ] using integrated solutions for energy, acoustic, and lighting performances [ 10 ]. Much of this analysis focuses on the impact on energy requirements [ 11 ] and energy demand [ 12 ] in office buildings. Dynamic control strategies are needed to promote optimum performance of these shading devices given the opposing requirements in winter and summer. Eltaweel and Su [ 13 ] proposed modifying the position and angle of Venetian blinds, using Grasshopper’s plugins to optimize daylight in office buildings, whereas other authors preferred simplified solutions which are easier to apply in building refurbishment. Freewan [14] compared the effect of different external vertical and diagonal fins and egg-crate devices behind a brise-soleil in an office building in Jordan, recording indoor ambient conditions (air temperature and illuminance level) and comparing these with an office with no shading device during July and August. Computer simulation was used to evaluate the performance of these shading devices and solar and daylight distribution. The effect of the use of curtains by occupants was also assessed. Egg-crate shading devices display a better annual energy performance, blocking sunlight in warmer periods while allowing it into the spaces in winter. Users prefer egg-crate models, as they contribute to creating vivid working environments while simultaneously maintaining a level of contact with the outside. Research to date has focused mostly on office buildings rather than on educational buildings, whose significant indoor thermal loads are due to high occupancy. Most studies used simulation tools [ 15 ] to evaluate the energy improvements of shading devices and interactions between cooling and lighting energy [ 16 ]. Moreover, controlled ambient analysis is also used in test rooms [ 17 ] to assess real scale models and the effects of different shading device configurations on thermal and lighting consumption [ 18 ]. Given the importance of these shading devices in retrofitting, classrooms with and without shading devices should be compared, bearing in mind real user patterns and annual performance. The presence of blinds, the most frequently used solar control devices in educational buildings in southern Spain, should also be taken into consideration in these assessments. In general, studies conducted support the view that the reaction of occupants to discomfort usually has a negative impact in terms of energy. This research aims to evaluate the potential for reducing lighting and air conditioning consumption, using low-cost shading devices in the retrofitting of educational buildings in a Mediterranean climate, studying real user patterns and considering occupants’ use of blinds. The impact of these devices on indoor natural illuminance, solar radiation levels, and operative temperatures was also analysed without considering user influence. 2. Methodology The ambient conditions of two identical classrooms in a school in Seville (southern Spain), with a Mediterranean climate, were monitored. An egg-crate solar protection system was installed on the outside of the window of one of these classrooms, while the second classroom was left in its original state. Both classrooms were evaluated simultaneously, considering identical climate conditions and following real use patterns. Ambient and thermal variables were monitored over a 12-month period to analyse the influence of the solar protection system, followed by a descriptive statistical analysis using the integrated development environment (IDE) of the Statistics Toolbox of the MATLAB Energies 2018,11, 2790 3 of 17 matrix software [ 19 ]. This research focused mainly on the analysis of electric consumption (kWh) from air conditioning (AC) and artificial lighting systems. This paper also includes the results of indoor operative temperatures (◦C) and indoor illuminance levels (lux). 2.1. Description of Case Study The case study monitored was Martínez Montañés Secondary School, a state school building managed by the Regional Government of Andalusia (Spain), which considers this school to be representative of those in the Mediterranean climate in the region. This school, built in 1967 and renovated in 1998, is located in the city of Seville (Figure 1a): latitude 37.37 ◦ N and longitude: − 5.97 ◦ W. The Köppen-Geiger Classification [ 20 ] places Seville in the Csa climate, with hot and dry summers and a maximum average temperature of 36.3 ◦ C in the warmest month, while the Spanish Technical Building Code [21] considers Seville a B4 climate zone. Two adjacent classrooms were monitored, both located in a south-facing module of the second floor of the building (Figure 1b), and each with a maximum capacity for 35 students. These 6.95 m wide and 6.85 m deep classrooms each had a total useful area of 45.65 m 2 and a clearance height of 3.20 m (Figure 2). Each classroom had four sliding window modules, with aluminium frames and 4 mm single glazing with no thermal bridge (U = 5.80 W/m 2· K). The 2.40 m high and 1.40 m wide window modules accounted for around 53% of the external façade surface of each classroom. Access doors from an indoor corridor were located opposite the predominantly south-facing windows. Energies 2018, 11, x FOR PEER REVIEW 3 of 17 following real use patterns. Ambient and thermal variables were monitored over a 12-month period to analyse the influence of the solar protection system, followed by a descriptive statistical analysis using the integrated development environment (IDE) of the Statistics Toolbox of the MATLAB matrix software [19]. This research focused mainly on the analysis of electric consumption (kWh) from air conditioning (AC) and artificial lighting systems. This paper also includes the results of indoor operative temperatures (°C) and indoor illuminance levels (lux). 2.1. Description of Case Study The case study monitored was Martínez Montañés Secondary School, a state school building managed by the Regional Government of Andalusia (Spain), which considers this school to be representative of those in the Mediterranean climate in the region. This school, built in 1967 and renovated in 1998, is located in the city of Seville (Figure 1a): latitude 37.37° N and longitude: −5.97° W. The Köppen-Geiger Classification [20] places Seville in the Csa climate, with hot and dry summers and a maximum average temperature of 36.3 °C in the warmest month, while the Spanish Technical Building Code [21] considers Seville a B4 climate zone. Two adjacent classrooms were monitored, both located in a south-facing module of the second floor of the building (Figure 1b), and each with a maximum capacity for 35 students. These 6.95 m wide and 6.85 m deep classrooms each had a total useful area of 45.65 m2 and a clearance height of 3.20 m (Figure 2). Each classroom had four sliding window modules, with aluminium frames and 4 mm single glazing with no thermal bridge (U = 5.80 W/m2·K). The 2.40 m high and 1.40 m wide window modules accounted for around 53% of the external façade surface of each classroom. Access doors from an indoor corridor were located opposite the predominantly south-facing windows. (a) (b) Figure 1. (a) Martínez Montañés Secondary School. The module of the classrooms monitored is shown in red. Base image: Google Earth Pro, 26 July 2017; (b) outdoor image of the rooms monitored: the four windows on the left, room without shading devices; the four windows on the right, and room with shading devices. The constructive composition of the façade is the same for both classrooms: 0.115 m perforated brick wall, 0.015 m interior mortar rendering, 0.05 m air chamber, 0.04 m partition brick wall, and 0.015 m gypsum plaster (U = 1.55 W/m2·K). The solar protection system of Polyvinyl Chloride (PVC) horizontal slatted shutters in these rooms was part of the original building construction. An additional external solar protection device, described in detail in Section 2.3, was installed in one of the classrooms (room A), while the other classroom (room B) maintained its original configuration with no external solar protection devices, and so was used as reference in the comparative analysis (Figure 3a). Figure 1. ( a ) Martínez Montañés Secondary School. The module of the classrooms monitored is shown in red. Base image: Google Earth Pro, 26 July 2017; ( b ) outdoor image of the rooms monitored: the four windows on the left, room without shading devices; the four windows on the right, and room with shading devices. The constructive composition of the façade is the same for both classrooms: 0.115 m perforated brick wall, 0.015 m interior mortar rendering, 0.05 m air chamber, 0.04 m partition brick wall, and 0.015 m gypsum plaster (U = 1.55 W/m 2· K). The solar protection system of Polyvinyl Chloride (PVC) horizontal slatted shutters in these rooms was part of the original building construction. An additional external solar protection device, described in detail in Section 2.3, was installed in one of the classrooms (room A), while the other classroom (room B) maintained its original configuration with no external solar protection devices, and so was used as reference in the comparative analysis (Figure 3a). Energies 2018,11, 2790 4 of 17 Energies 2018, 11, x FOR PEER REVIEW 5 of 17 Figure 2. Floor plan showing the location of the sensors in the classrooms monitored. 2.2. Shading Device Description The solar protection designed is a grid consisting of white methacrylate tongue-and-groove slats (Figure 3b,c) and manufactured using a laser cutting machine in the Digital Fabrication Laboratory (FabLab) of the Higher Technical School of Architecture of the University of Seville. The 3-mm-thick and 30-mm-deep slats were assembled in a 43 × 43 mm rectangle, and an external auxiliary 1640 × 2440 mm structure in S275 JR corrosion-proof steel was incorporated into the solar protection prototype. This structure, made up of 45 × 10 mm metal pieces with an interior metal anchorage of 45 × 10 mm, left four empty 805 × 1205 mm slots where the lattices were placed. L.55.45.10 mm steel pieces were welded to each corner to separate the auxiliary structure from the building envelope, while the shading device and window glazing were 0.35 m apart and placed 0.20 m from the external façade line. The egg-crate device was made up of 16 1200 × 800 mm lattices in total. 2.3. Monitoring System A monitoring system following EN ISO 7726: 2001 [22] was set up, with nine nodes or data loggers to store the information monitored at 10-min intervals. Both classrooms had two monitoring panels, with two hubs in each. The first hub was connected to the electric consumption of the classroom lighting system. The second recorded measurements for an indoor detection sensor, four illuminance sensors (three indoors and one outdoors), four sensors measuring blind aperture level, and four sensors controlling window openings, while the third hub included five indoor surface temperature sensors. Finally, the fourth hub was made up of four indoor humidity sensors, four indoor air temperature sensors, an indoor carbon dioxide detector, an outdoor pyranometer (vertical and parallel to the façade) and an outdoor pyrgeometer. The pyranometer in room A was placed behind the egg-crate device to measure the efficiency of the shading device, while the pyranometer in room B recorded the global solar radiation reaching the façade in the absence of obstacles. Figure 2. Floor plan showing the location of the sensors in the classrooms monitored. Energies 2018, 11, x FOR PEER REVIEW 4 of 17 (a) (b) (c) Figure 3. (a) Indoor view of the classroom with no egg-crate devices (room B); (b) indoor view of the solar protection designed (room A); and (c) egg-crate device designed for each window. A direct expansion heat pump was installed for the air conditioning systems in both classrooms, connected to two wall indoor units and an exterior inverter unit. These systems had a cold/heat capacity of 6.8/7.8 kW, with an energy efficiency of SEER (Seasonal Energy Efficiency Ratio) 6.1 (A++) and SCOP (Seasonal Coefficient Of Performance) 3.8 (A). Finally, it should be noted that both classrooms still preserved the original lighting system consisting of four luminaires, each with two 2 × 36 W fluorescent lamps. Figure 3. Cont. Energies 2018,11, 2790 5 of 17 Energies 2018, 11, x FOR PEER REVIEW 4 of 17 (a) (b) (c) Figure 3. (a) Indoor view of the classroom with no egg-crate devices (room B); (b) indoor view of the solar protection designed (room A); and (c) egg-crate device designed for each window. A direct expansion heat pump was installed for the air conditioning systems in both classrooms, connected to two wall indoor units and an exterior inverter unit. These systems had a cold/heat capacity of 6.8/7.8 kW, with an energy efficiency of SEER (Seasonal Energy Efficiency Ratio) 6.1 (A++) and SCOP (Seasonal Coefficient Of Performance) 3.8 (A). Finally, it should be noted that both classrooms still preserved the original lighting system consisting of four luminaires, each with two 2 × 36 W fluorescent lamps. Figure 3. ( a ) Indoor view of the classroom with no egg-crate devices (room B); ( b ) indoor view of the solar protection designed (room A); and (c) egg-crate device designed for each window. A direct expansion heat pump was installed for the air conditioning systems in both classrooms, connected to two wall indoor units and an exterior inverter unit. These systems had a cold/heat capacity of 6.8/7.8 kW, with an energy efficiency of SEER (Seasonal Energy Efficiency Ratio) 6.1 (A++) and SCOP (Seasonal Coefficient Of Performance) 3.8 (A). Finally, it should be noted that both classrooms still preserved the original lighting system consisting of four luminaires, each with two 2 ×36 W fluorescent lamps. 2.2. Shading Device Description The solar protection designed is a grid consisting of white methacrylate tongue-and-groove slats (Figure 3b,c) and manufactured using a laser cutting machine in the Digital Fabrication Laboratory (FabLab) of the Higher Technical School of Architecture of the University of Seville. The 3-mm-thick and 30-mm-deep slats were assembled in a 43 × 43 mm rectangle, and an external auxiliary 1640 × 2440 mm structure in S275 JR corrosion-proof steel was incorporated into the solar protection prototype. This structure, made up of 45 × 10 mm metal pieces with an interior metal anchorage of 45 × 10 mm, left four empty 805 × 1205 mm slots where the lattices were placed. L.55.45.10 mm steel pieces were welded to each corner to separate the auxiliary structure from the building envelope, while the shading device and window glazing were 0.35 m apart and placed 0.20 m from the external façade line. The egg-crate device was made up of 16 1200 × 800 mm lattices in total. 2.3. Monitoring System A monitoring system following EN ISO 7726: 2001 [ 22 ] was set up, with nine nodes or data loggers to store the information monitored at 10-min intervals. Both classrooms had two monitoring panels, with two hubs in each. The first hub was connected to the electric consumption of the classroom lighting system. The second recorded measurements for an indoor detection sensor, four illuminance sensors (three indoors and one outdoors), four sensors measuring blind aperture level, and four sensors controlling window openings, while the third hub included five indoor surface temperature sensors. Finally, the fourth hub was made up of four indoor humidity sensors, four indoor air temperature sensors, Energies 2018,11, 2790 6 of 17 an indoor carbon dioxide detector, an outdoor pyranometer (vertical and parallel to the façade) and an outdoor pyrgeometer. The pyranometer in room A was placed behind the egg-crate device to measure the efficiency of the shading device, while the pyranometer in room B recorded the global solar radiation reaching the façade in the absence of obstacles. An additional monitoring panel with the ninth data logger was incorporated into the system. This data logger used several sensors measuring power consumption (W), voltage (V), and electricity intensity (A) to calculate the electric consumption of the air conditioning (AC) and lighting system in the classroom. Table 1shows the technical characteristics of the sensors used in the process for monitoring the ambient and energy variables of the classrooms. Table 1. Probes in the rooms monitored. Device #Per Class (Total) Location Unit Range Accuracy Thermocouple 6 (12) Walls and ceiling surfaces ◦C−30 + 350 ±1±0.75% Thermometer 4 (8) Interior matrix ◦C−40 + 80 ±0.2 ◦C (0–40 ◦C) ±0.2 ◦C (40–80 ◦C) Hygrometer 4 (8) Interior matrix % 0–100 ±1.5% (0–90%) ±2.5% (90–100%) Lux meter 4 (8) Indoor and outdoor lux 0–200,000 ±4.0% CO2detector 1 (2) On surface: east Wall ppm 0–2000 ±(40 ppm + 4.8% of reading) Presence detector 2 (4) North walls Y/N 4–15 m - Window opening control 4 (8) Windows Y/N - - Blind level sensor 4 (8) Blinds Mm 200–8000 ±25 mm Pyranometer 1 (2) Outdoor W/m20–4000 ±2.0% Pyrgeometer 1 Outdoor W/m2−300 + 100 ±3.0% (−10 + 40 ◦C) Voltmeter 1 (2) Electrical panel V - - Ammeter 1 (2) Electrical panel A - - Potentiometer 1 (2) Electrical panel W - - Energy 1 (2) Electrical panel kWh - - The information regularly stored in the data loggers was uploaded every 30 min to a File Transfer Protocol (FTP) server by mobile card via a static IP address. Data recorded were processed and exported to the Microsoft Excel 2016 ® [ 23 ] format, before being analysed and interpreted using MATLAB matrix software (R2017 a, The Mathworks Inc., Natick, MA, USA) [ 19 ]. The data monitored was accessed remotely by downloading the files from the FTP server or through an html portal, which also allows the configuration to be easily monitored. Outdoor variables were measured using a local weather station 450 m away located above test cells managed by the research group. As described in a previous paper by the authors [ 17 ], this system measures outdoor ambient variables for air temperature, relative humidity, CO 2 levels, and wind speed and direction. Table 2includes technical information on the sensors from the local weather station. Table 2. Probes in the weather station. Device # Orientation Unit Range Accuracy Thermometer 2 N ◦C−40 + 80 ±0.15 ±0.1% Hygrometer 1 - % 0–100 ±3% (0.70%) ±5% (71.10%) CO2detector 1 - ppm 0–2000 ±2.0% Anemometer 1 - m/s 0–50 ±0.5 Vane 1 - ◦0–360 ±2.5 Energies 2018,11, 2790 7 of 17 2.4. Infiltration Tests A Blower Door test was carried out to characterize the airtightness of the building envelope in both classrooms, following ISO 9972 [ 24 ]. Once the natural air gates were sealed, the room was depressurised using a 50 Pa pressure fan and indoor air was extracted until the differential pressure was balanced with the outdoor air. Subsequently, the differential pressure decreased continuously through a gradual reduction in fan velocity. This test aimed to establish a curve showing the relation between differential pressure and extracted airflow. A Minneapolis Blower Door Model 4/230 V System (The Energy Conservatory, Minneapolis, MN, USA) which uses TECTITE Express software (The Energy Conservatory, Minneapolis, MN, USA) was used to obtain measurements with windows and doors closed. Table 3shows the infiltration test results. Airtightness of the envelope was similar in both classrooms, with values ranging between 0.13 and 0.20 Air Changes per Hour (ACH) for a pressure level of 50 Pa. Based on these values, both classrooms can therefore be considered comparable. Table 3. Infiltration test results. Room Air Leakage Rate at 50 Pa (V50, m3/h) Infiltration Rate at 50 Pa (n50, ACH) A. Shading device 552 (±0.2%) 3.77 B. No shading devices 578 (±0.2%) 3.96 2.5. Monitoring Periods Used in Analysis of Results Both classrooms were monitored over a 12-month period (from May 2017 to April 2018). As this experiment is still ongoing, the analysis presented in this paper is considered to be an initial approach to the results obtained regarding the electric consumption of air conditioning and lighting systems in the classrooms. The values for daily evolution in indoor operative temperatures, natural illuminance and solar radiation levels recorded during a typical and representative day are also shown. For the purposes of this analysis, the study has been divided into the following sections: 2.5.1. Seasonal Analysis of Electric Air Conditioning and Lighting Consumption Three representative periods—winter, summer, and mid-season—were analysed from the total annual monitoring and classified by outdoor temperature range. The selection process for the summer period took into consideration the fact that the academic calendar finishes in mid-June and that the school remained closed during the rest of the summer, that is, the months of July and August. The characteristics of the periods analysed can be seen in Table 4. Table 4. Characteristics of protocols analysed. Periods Description Tout (◦C) Hours Recorded Occupied Hours Winter 1 December to 28 February 1.9–26.2 2160 897/964 Mid-Season 1 March to 30 April 5.2–36.5 1464 336/429 Summer 1 May to 23 June 9.4–46.4 1296 328/335 Note: Occupied hours shown refer to Room A/Room B. This section also shows the evolution of natural illuminance, solar radiation levels and indoor operative temperatures recorded simultaneously in both classrooms for the same day in mid-season, 18 April 2018. The analysis was carried out when the highest outdoor temperatures (the most unfavourable outdoor conditions) were reached, during an unoccupied period (without user influence), in free-running conditions (no air conditioning), and with a blind aperture level of 100% (blinds fully open). The mid-season period was selected for the striking similarity in the activation of air conditioning and lighting systems in both rooms. Energies 2018,11, 2790 8 of 17 2.5.2. Annual Analysis of Air Conditioning and Lighting Consumption Finally, the influence of solar protection on the annual consumption of air conditioning and lighting systems was analysed from May 2017 to April 2018. Users had a great influence on indoor ambient through actions such as modifying blind level aperture or switching on the artificial lighting system depending on different activities to be carried out in the classroom. In addition, the difference between the percentages of occupied hours of the classrooms, shown in the previous table, inevitably resulted in uncertainties which must be kept to a minimum in order to ascertain the real influence of the solar protection designed. Data were filtered considering the hours in which both classrooms were occupied simultaneously, making it possible to calculate the real annual savings of the air conditioning and artificial lighting systems (kWh) due to the shading devices, as the annual occupied hours considered were the same for both classrooms. 3. Analysis of Consumption Results This section analyses the influence of the egg-crate shading device on thermal and energy variables in the classroom. Air conditioning and lighting consumption monitoring results are presented, both for the classroom with shading devices (room A) and for that without egg-crate devices (room B), considering the same outdoor conditions. The impact of solar protection on indoor operative temperatures, natural illuminance and solar radiation levels were also analysed in both classrooms during an entire unoccupied day, following the criteria stated in Section 2.5. 3.1. Seasonal Analysis of Electric Air Conditioning and Lighting Consumption This section includes a general analysis of the hours when the air conditioning and lighting systems were active. A seasonal study was carried out to examine the use patterns in both classrooms, as Table 5shows. Table 5. Percentage of occupied hours and activation of air conditioning and lighting systems. Data shown for each period and classroom analysed. Variables Room A (Shading Devices) Room B (No Shading Devices) Winter Mid-Season Summer Winter Mid-Season Summer Total occupied hours (%) 41.5 22.9 25.3 44.6 29.3 25.8 AC ON when occupied hours (%) 6.1 3.3 5.2 3.3 0.0 7.5 AC OFF when occupied hours (%) 93.9 96.7 94.8 96.7 100.0 92.5 Lights ON when occupied hours (%) 31.3 55.5 38.7 31.5 53.2 60.2 Lights OFF when occupied hours (%) 68.7 44.5 61.3 68.5 46.8 39.8 This table shows the percentages of occupied hours (%) from the total of hours recorded (fifth column in Table 4), which are similar in both classrooms, especially in winter and summer. Moreover, it also indicates the percentage of hours (%) in which the air conditioning and lighting systems were on, as determined from the percentage of hours of occupancy for each classroom. The percentage of hours in which the air conditioning system was ON was higher in room A, with shading devices, both for winter and mid-season. In contrast, the activity of the air conditioning system was 2.3% higher in summer in the room B, without shading devices. The artificial lighting system was active for similar percentages of hours in both classrooms in the winter and mid-season periods. In contrast, lights were on during 21.5% more hours in the classroom with no shading devices (room B) in the summer. Table 6shows the solar radiation levels (W/m 2 ) and the average blind aperture level (%) when the air conditioning system was ON for each period and classroom. In the classroom with no shading device (room B), with solar radiation levels below 200 W/m 2 and blind aperture levels up to 25%, air conditioning was in use during more than 50% of hours in winter, approximately 9% in mid-season, and approximately 64% of the hours in summer. In the case of the room with shading devices (room A), these values accounted for 25% of the hours in winter, 11% Energies 2018,11, 2790 9 of 17 in mid-season, and almost 30% in summer. These results also reflect the significant influence of users in the control of some of the variables monitored, including the blind aperture level mentioned earlier. Table 6. Statistical analysis of the percentage of occupied hours in which the air conditioning system was ON, considering specific solar radiation and blind aperture levels. Data shown for each period and classroom analysed. Variables % Hours of Total Hours Analysed Room A (Shading Devices) Room B (No Shading Devices) AC ON When . . . Winter Mid-Season Summer Winter Mid-Season Summer Solar radiation ≤200 W/m2 Blinds ≤25% 25.4 11.3 28.7 55.4 8.8 64.0 25% < Blinds ≤ 50% 44.7 9.3 7.0 4.0 5.4 0.6 Blinds > 50% 5.4 4.8 10.9 2.9 3.0 0.6 Solar radiation > 200 W/m2 Blinds ≤25% 3.6 0.3 0.0 8.7 1.2 20.0 25% < Blinds ≤ 50% 6.4 0.3 0.0 1.0 0.0 0.9 Blinds > 50% 1.1 0.3 0.0 0.4 0.0 0.3 AC OFF 13.4 73.7 53.4 27.6 81.6 13.6 Note: Blind level of 100% means that blinds were fully open. Table 7shows the percentage of hours when the artificial lighting system was on. Data obtained were classified by blind aperture level which was higher in the classroom with shading devices (room A) than in that of the classroom with no egg-crate devices (room B). This was especially important in summer and mid-season, with values above 50% of the hours. Table 7. Statistical analysis of the percentage of occupied hours in which the lighting system was on, considering a specific blind aperture level. Data shown for each period and classroom analysed. Variables % Hours of Total Hours Analysed Room A (Shading Devices) Room B (No Shading Devices) Lights ON When . . . Winter Mid-Season Summer Winter Mid-Season Summer Blinds ≤25% 10.6 28.7 14.9 27.8 33.3 57.5 25% < Blinds ≤50% 15.9 12.8 13.1 2.3 14.0 1.8 Blinds > 50% 4.7 14.0 10.7 1.3 5.8 0.9 Lights OFF 68.8 44.5 61.3 68.6 46.9 39.80 Note: Blind level of 100% means that blinds were fully open. Figure 4represents cumulative distributions of solar radiation levels (x-axis) considering the blind aperture levels (y-axis) in both rooms, reflecting the use of blinds when a specific solar radiation level was reached on the unobstructed façade. In winter (Figure 4a), blind aperture levels were constantly set at 50% open in the room with egg-crate devices, regardless of solar radiation levels. As solar radiation levels increased, the blind aperture levels gradually increased in the room with no solar protection and lower blind aperture levels were registered for longer periods. In summer (Figure 4b), considering the same solar radiation levels, blind aperture levels tended to be lower in the room with no shading devices. With solar radiation of 150 to 300 W/m 2 , blind levels were usually set at 30% open in the room with egg-crate shading devices. Finally, at solar radiation levels of 100 to 300 W/m 2 , blind aperture levels were usually 50% open in the room with egg-crate devices in mid-season, while with cumulative values of 350 to 750 W/m 2 , blinds were normally fully open in this room. Therefore, blind aperture levels in the room with egg-crate shading devices remained more constant in time when compared with the other room. The increase in blind aperture levels of the room with no egg-crate devices was more gradual when solar radiation levels were higher. With solar radiation levels above 370 W/m 2 , blind aperture levels were usually higher in the room with egg-crate devices. Energies 2018,11, 2790 16 of 17 • In this regard, although egg-crate protection increased indoor illuminance by diffusing visible radiation and improving consistency in illuminance (without providing shade to the classroom), users generally ensured that blind aperture levels remained high. • Similarly, the air conditioning system (cool mode) was switched ON more frequently in the classroom with no solar protection in summer, at low blind aperture levels. In winter, in the classroom with solar protection devices, the air conditioning system (heat mode) was usually turned ON with low solar radiation levels and intermediate blind aperture levels. • Considering a typical mid-season day with clear sky conditions, no occupation, blinds fully open, and outdoor temperatures around 30 ◦ C (with no user influence), there was a reduction of approximately 59% in solar radiation levels in the room with egg-crate devices. This resulted in indoor temperatures approximately 1 ◦ C lower and indoor illuminance levels up to 130 lux higher than with no shading devices. While the reduction in solar radiation was especially significant from 10:00 to 17:00 h in the classroom with egg-crate devices, illuminance levels were noticeably higher from 12:00 to 16:00. In conclusion, the egg-crate shading device installed outside the windows resulted in significant energy savings, with fair illuminance levels, and is a low-cost solution which can be quickly assembled, making it suitable for the energy retrofitting of educational buildings in a Mediterranean climate. However, further research is needed to properly analyse the influence of the egg-crate device over indoor environment quality and energy variables, especially as regards natural illuminance, operative temperatures and solar radiation levels. Author Contributions: Á.L.L.-R. and R.S. conceived and designed the experiments; Á.L.L.-R., R.S., and C.M.C.-G. performed the experiments; all authors analysed the data; all authors have written, reviewed, and approved the final manuscript. Funding: This research was funded by the Spanish government through the Research and Development project “Energy Rehabilitation of Tertiary Buildings in Mediterranean Climate by Optimizing Solar Protection Systems” (ref BIA2014-53949-R). This research was also funded by the Ministry of Economy and Competitiveness, Spanish Government and the European Regional Development Fund. Conflicts of Interest: The authors declare no conflicts of interest. The founding sponsors had no role in the design of the study; in the collection, analyses, or interpretation of data; in the writing of the manuscript, and in the decision to publish the results. References 1. Directive 2012/27/EU of the European Parliament and of the Council. Available online: http://eur-lex. europa.eu/legal-content/EN/TXT/PDF/?uri=CELEX:32012L0027&from=EN (accessed on 5 July 2018). 2. Dimoudi, A.; Kostarela, P. Energy monitoring and conservation potential in school buildings in the C’ climatic zone of Greece. Renew. Energy 2009,34, 289–296. [CrossRef] 3. Isaac, M.; van Vuuren, D.P. Modeling global residential sector energy demand for heating and air conditioning in the context of climate change. Energy Policy 2009,37, 507–521. [CrossRef] 4. International Energy Agency. Energy Technology Perspectives 2012 Pathways to a Clean Energy System; International Energy Agency: Paris, France, 2012. 5. Samuel, D.L.; Nagendra, S.S.; Maiya, M.P. Passive alternatives to mechanical air conditioning of building: A review. Build. Environ. 2013,66, 54–64. [CrossRef] 6. Rospi, G.; Cardinale, N.; Intini, F.; Negro, E. Analysis of the energy performance strategies of school buildings site in the Mediterranean climate: A case study the schools of Matera city. Energy Build. 2017 ,152, 52–60. [CrossRef] 7. Zeiler, W.; Vissers, D.; Maaijen, R.; Boxem, G. Occupants’ behavioural impact on energy consumption: Human-in-the-loop comfort process control. Archit. Eng. Des. Manag. 2014,10, 108–130. [CrossRef] 8. Bellia, L.; Marino, C.; Minichiello, F.; Pedace, A. An Overview on Solar Shading Systems for Buildings. Energy Procedia 2014,62, 309–317. [CrossRef] 9. Kuhn, T.E. State of the art of advanced solar control devices for buildings. Sol. Energy 2017 ,154, 112–133. [CrossRef] Energies 2018,11, 2790 17 of 17 10. Carletti, C.; Sciurpi, F.; Pierangioli, L. The Energy Upgrading of Existing Buildings: Window and Shading Device Typologies for Energy Efficiency Refurbishment. Sustainability 2014,6, 5354–5377. [CrossRef] 11. Bellia, L.; De Falco, F.; Minichiello, F. Effects of solar shading devices on energy requirements of standalone office buildings for Italian climates. Appl. Therm. Eng. 2013,54, 190–201. [CrossRef] 12. Yun, G.; Yoon, K.C.; Kim, K.S. The influence of shading control strategies on the visual comfort and energy demand of office buildings. Energy Build. 2014,84, 70–85. [CrossRef] 13. Eltaweel, A.; Su, Y. Controlling venetian blinds based on parametric design; via implementing Grasshopper’s plugins: A case study of an office building in Cairo. Energy Build. 2017,139, 31–43. [CrossRef] 14. Freewan, A.A. Impact of external shading devices on thermal and daylighting performance of offices in hot climate regions. Sol. Energy 2014,102, 14–30. [CrossRef] 15. Kirimtat, A.; Koyunbaba, B.K.; Chatzikonstantinou, I.; Sariyildiz, S. Review of simulation modeling for shading devices in buildings. Renew. Sustain. Energy Rev. 2016,53, 23–49. [CrossRef] 16. Tzempelikos, A.; Athienitis, A.K. The impact of shading design and control on building cooling and lighting demand. Sol. Energy 2007,81, 369–382. [CrossRef] 17. León-Rodríguez, Á.L.; Suárez, R.; Bustamante, P.; Campano, M.Á.; Moreno-Rangel, D. Design and performance of test cells as an energy evaluation model of facades in a mediterranean building area. Energies 2017,10, 1816. [CrossRef] 18. Carletti, C.; Sciurpi, F.; Pierangioli, L.; Asdrubali, F.; Pisello, A.L.; Bianchi, F.; Sambuco, S.; Guattari, C. Thermal and lighting effects of an external venetian blind: Experimental analysis in a full scale test room. Build. Environ. 2016,106, 45–56. [CrossRef] 19. MATLAB R2017 a Software; The Mathworks Inc.: Natick, MA, USA, 2017. 20. Peel, M.C.; Finalyson, B.L.; MacMahon, T.A. Updated world map of the Köppen-Geiger climate classification. Hydrol. Earth Syst. Sci. 2007,11, 1633–1644. [CrossRef] 21. Spanish Government. Spanish Technical Building Code. Basic Document: Energy Savings (Código Técnico de la Edificación. Documento Básico: Ahorro de Energía); Spanish Government: Madrid, Spain, 2009. 22. EN ISO 7726:2001: Ergonomics of the Thermal Environment. Instruments for Measuring Physical Quantities; British Standards Institution: London, UK, 2001. 23. Microsoft Excel 2016®Software; Microsoft: Redmond, WA, USA, 2016. 24. International Organization for Standardization. ISO 9972: Thermal Performance of Buildings—Determination of Air Permeability of Buildings—Fan Pressurization Method; ISO: Geneva, Switzerland, 2015. © 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).