Voltage sensitivity based technique for optimal placement of switched capacitors
Abstract
This paper is about the development of a fast but exact enough technique to solve the optimal allocation and sizing of capacitors on power systems, no matter the voltage level. The proposed methodology is mainly characterized by assuming a linear behaviour for the reactive problem and having an objective function that minimizes the sum of the voltage magnitude deviations from the specified voltage limits squared, for all those buses with over/under voltages. The proposed approach has been tested on the IEEE 14-bus and 30-bus systems, and on an existing distribution system with actual data. Results are compared with those of using an exact calculation of voltages
Full text
See discussions, stats, and author profiles for this publication at: https://www.researchgate.net/publication/255623764 VOLTAGE SENSITIVITY BASED TECHNIQUE FOR OPTIMAL PLACEMENT OF SWITCHED CAPACITORS Article CITATIONS 0 READS 32 3 authors: Manuel Rodríguez Montañés Endesa 7 PUBLICATIONS22 CITATIONS SEE PROFILE Jesús M. Riquelme Santos Universidad de Sevilla 83 PUBLICATIONS2,096 CITATIONS SEE PROFILE Esther Romero-Ramos Universidad de Sevilla 45 PUBLICATIONS824 CITATIONS SEE PROFILE All content following this page was uploaded by Esther Romero-Ramos on 26 May 2014. The user has requested enhancement of the downloaded file.
VOLTAGE SENSITIVITY BASED TECHNIQUE FOR OPTIMAL PLACEMENT OF SWITCHED CAPACITORS M. Rodr´ıguez Monta˜n´es J. Riquelme Santos E. Romero Ramos Isotrol University of Sevilla University of Sevilla Sevilla, Spain Sevilla, Spain Sevilla, Spain Abstract - This paper is about the development of a fast but exact enough technique to solve the optimal allocation and sizing of capacitors on power systems, no matter the voltage level. The proposed methodology is mainly characterized by assuming a linear behaviour for the reactive problem and having an objective function that minimizes the sum of the voltage magnitude deviations from the specified voltage limits squared, for all those buses with over/under voltages. The proposed approach has been tested on the IEEE 14-bus and 30-bus systems, and on an existing distribution system with actual data. Results are compared with those of using an exact calculation of voltages. Keywords - Capacitor placement, capacitor sizing, VAR planning, sensitivity factor, voltage profile. 1 Introduction PO wer distribution from electric power generators to consumers is accomplished via the transmission, subtransmission, and distribution lines. Voltage profile improvement and system losses reduction by capacitor installation depend greatly on how capacitors are placed and operated in the system [1, 2]. The general capacitor placement problem consists of determining the optimal location and size of capacitors to be installed and the efficient control schemes in the buses of the system [3]-[8]. Much mathematical research on the capacitor placement has been studied in distribution systems. A nonlinear programming such as gradient search method is proposed in [1]. Baran and Wu [2] decomposed capacitor placement problem into a master problem and a slave problem by using mixed integer programming. The master problem determines the location of the capacitors and the sla- ve problem determines the type and size of the capacitors. Simulated annealing is used in [3, 4] after formulating capacitor placement problem as a discrete combinational optimization problem. Huang et al. [5] proposes by tabu search (TS)-based solution algorithm and uses sensitivity analysis method to select the candidate installation locations of capacitors to reduce the search space. Also, many researchers proposed genetic algorithm (GA) application to search global optimal solution of capacitor placement problem [6, 7, 8]. Sundhararajan et al. [6] used sensitivity analysis to search the location of the capacitors and GA to determine the size of the capacitors, which somewhat depends on experiences in the selection of the probability parameters. Miu et al. [7] suggested the two-stage algorithms that combine the good qualities of GA and a fast sensitivity-based heuristic. This paper presents a linear reasoning for determining the optimal locations and sizes for capacitor placement for voltage profile improvement. Voltage sensitivity indices have been usually used as indicators of voltage stability and several indices of this kind have been proposed [9, 10]. One such voltage sensitivity index, dV/dQ, called the reactive voltage sensitivity factor (RPV S), was the first index used to predict voltage control problems [11]. This index also provides a means of allocating capacitors to improve bus voltages as we shall show. The analysis of the results after applying the proposed algorithm to different systems allow to conclude that the new methodology is quite fast and accurate so it can be used not only by the planner of the system, but also on real time to determine the best way to operate on all the switched capacitors being on the system to improve all voltages in a global way. The papers is structured as follows: section 2 defines bus voltage sensitivity factors and how computing them. Next, in section 3 the mathematical problem of optimization is posed, focused on minimizing voltage magnitude deviations from the specified voltage limits by using the bus voltage sensitivity factors. Once the minimization problem is solved, a heuristic algorithm looking for establishing the minimum number of allocations and switches is described. Section 4 applies the new methodology to three different cases, two IEEE test systems and an actual one. Results are finally commented and analyzed. 2 Bus voltage sensitivity factors A sensitivity which given the variation of node i voltage magnitude due to a unit reactive power injection to node j is called the reactive power voltage sensitivity (RPV Sij ) and denoted by (∆Vi/∆Qj). The linearized steady state system power voltage equations are given by, HN ML ∆θ ∆V=∆P ∆Q(1) where ∆Pand ∆Qare vectors of real and reactive bus power injection changes, while ∆θand ∆Vare vectors of bus voltage angle and magnitude changes. The Jacobian matrix in (1) is that used when the power flow equations are solved by the Newton-Raphson technique. Although system voltages are affected by both P and Q, P can be kept constant at each specified operating point and the voltage variations can be evaluated by considering the incremental relationship between Q and V. As a consequence, making null the incremental changes in P in (1), the following relation ∆Q−∆Vresults, ∆Q=L−MH−1N∆V=JR∆V(2) 15th PSCC, Liege, 22-26 August 2005 Session 16, Paper 4, Page 1
Load Linear Exact Absolute Linear Exact Absolute Linear Exact Absolute Buses method method error method method error method method error RPV Si4RP V Si9RPV Si12 4 0,0445 0,0482 0,0037 0,0206 0,0239 0,0033 0,0014 0,0019 0,0005 5 0,0268 0,0294 0,0026 0,0124 0,0146 0,0022 0,0008 0,0011 0,0003 7 0,0207 0,0226 0,0019 0,0599 0,0672 0,0073 0,0040 0,0052 0,0012 9 0,0206 0,0240 0,0034 0,1178 0,1356 0,0178 0,0078 0,0106 0,0028 10 0,0171 0,0210 0,0039 0,0978 0,1186 0,0208 0,0065 0,0092 0,0027 11 0,0089 0,0112 0,0023 0,0507 0,0631 0,0124 0,0034 0,0049 0,0015 12 0,0014 0,0018 0,0004 0,0078 0,0100 0,0022 0,2178 0,2390 0,0212 13 0,0031 0,0041 0,001 0,0178 0,0230 0,0052 0,0518 0,0619 0,0101 14 0,0130 0,0173 0,0043 0,0745 0,0979 0,0234 0,0269 0,0366 0,0097 Tabla 1: RPVS factors in each load bus of the IEEE 14-bus test system where JRis called the reduced Jacobian matrix of the system and its inverse directly relates the bus voltage magnitude and bus reactive power injection. Adopting the well-known strong interdependence between active powers and bus voltage angles, and between reactive powers and voltage magnitudes, the jacobian matrix in (1) is simplified to, H0 0L ∆θ ∆V=∆P ∆Q(3) and, in consequence, equation (2) is reduced to, ∆Q=L∆V(4) Finally, the matrix RP V S, which is associated to all the PQ nodes of the system, can be obtained from this last system, RPV S =∆V ∆Q=L−1(5) The former way of reasoning allows to compute a quasi-exact RPV Sij factors . The procedure will be the following, 1. For a given load and generator power profile, load flow equations (1) are solved to know the state variables θFand VFin all buses. 2. Matrix L is computed from θFand VF. 3. Matrix RP V S is determined by (5) If the equations of the Fast Decoupled Load Flow method (FDLF) were the starting point instead of the Newton- Raphson power flow equations, only the linearized, decoupled, reactive power model would be required. This one is represented by, B∆V=∆Q(6) where B is equal to the imaginary part of the nodal admittance matrix changed of sign. Then, matrix RP V S can be computed from the inverse of B , RPV S =(B )−1(7) The main advantage from computing RP V S matrix from (7) instead of (5) is that matrix B is constant while matrix Ldepends on the state variables. This implies a lot of saving of computational time when this issue becomes important. On the contrary, accuracy is reduced due to the assumed simplifications after adopting the FDLF method. Following in table 1 the RPVS factors in each load bus of the IEEE 14-bus test system are listed, both using (5) (“Exact method”) and (7) (“Linear method”). The bus voltage sensibilities regards to reactive power injections in buses 4, 9 and 12 are showed, that is, the factors RPV Si4, RPV Si9and RPV Si12 respectively, where irefers to any load bus. These three nodes have been chosen as there are capacitors banks in all of them, so it could be of interest to quantify how much voltage magnitudes change when the reactive power injection in any of these three buses is modified. Absolute errors between the exact and linear form of obtaining RPVS factors are also displayed. It can be concluded from these results, and also thanks to the final relative errors computed when the compensated voltage magnitudes are determined (see table 4 in section 4), that the error by using the matrix B is almost null. As a consequence, the linear methodolgy to determine the RPVS factors has been finally the implemented one. Nevertheless, the exact RPVS factors are saved to study the accuracy of the results after the whole problem is solved. It must noted that the higher the load level of the system, the larger the absolute error between the exact and the linear RPVS factors. This result was expected since the exact method takes into account the actual voltage magnitudes while the linear supposes voltage magnitudes equal to nominal voltages. On the other hand, it always results that exact RPV S factors are higher than the linear RPV S ones in buses whose voltages are less than the nominal value, and just the opposite in nodes with voltages larger than the nominal. These results allow to conclude that the final solution with the linear RPVS factors is always enclosed by the exact solution. All these considerations encourage to follow with the use of the linear RPVS factors to try to solve the proposed problem. 3 Optimization procedure Following, the optimization problem is posed by using the former RPVS factors. The objective consists of deducing the best buses where the new capacitors must be allocated and how much reactive power must be injected by 15th PSCC, Liege, 22-26 August 2005 Session 16, Paper 4, Page 2
those components in order to get the following aims: •Eliminating undervoltages •Avoiding overvoltages in any bus due to the increased injected reactive power on the system •Minimizing the number of capacitors to be installed and the number of switches on them. If Ndenotes the total number of buses in the power system, and Mthe number of load nodes, that is, the usually named PQ nodes, Cis the size of the set SCthat comprises all those nodes where capacitors can be allocated. This set is known in advance to the formulation of the problem and the inequality C≤Mis always met. For example, if the problem to solve consisted of determining the best switches over already installed capacitors, set SC would be perfectly defined by those nodes where shunt elements are allocated; in the contrast, if it were a planning problem, probably the best point of starting would be to define SCwith all the being PQ nodes. Once the load flow equations have been solved and RPVS factors have been obtained, the voltage mismatch vector ∆Viis computed for each load bus ias follows, 1. If Vi>Vmax i−→ ∆Vi=Vmax i−Vi 2. If Vi<Vmin i−→ ∆Vi=Vmin i−Vi 3. If Vmin i<V i<Vmax i−→ ∆Vi=0 Computing the vector ∆VMx1in this way, the overvoltages and undervoltages in the system are being quantified. Then, this vector is used to define a first version of the objective function as, f= M i ⎡ ⎣⎛ ⎝ C j RPV Sij ∆Qj⎞ ⎠−∆Vi⎤ ⎦ 2 (8) where the vector ∆QCx1is obtained from the RPVS matrix, RPV SMxC∆QCx1=∆VMx1(9) No consideration has been done yet in relation to minimize the investment in new capacitors. The following measures give answer to this question: •Buses iwith ∆Vi=0are eliminated from (8) and the related equation iin system (9) is also removed. This implies that those buses whose voltages are in limits are not forced to hold their actual values. •Due to the previous item, buses that initially ha- ve their voltages in limits could surpass the maximum specified voltage Vmax after the reactive power compensation. This undesirable effect can be avoided by adopting a practical maximum voltage, Vpmax, lower than the real maximum specified one, that is, Vpmax =Vpmax −tolmax. •Considering overvoltages into the optimization problem allows to penalize those capacitors more sensible to increase even more those overvoltages. So, the final minimizing problem results, f= M i ⎡ ⎣⎛ ⎝ C j RPV Sij ∆Qj⎞ ⎠−∆Vi⎤ ⎦ 2 (10) RPV SMxC ∆QCx1=∆VMx1(11) where Mis less than M and results after removing nodes with voltage magnitudes in limits. After solving this optimization problem, a vector of new injected reactive powers ∆QCx1is deduced. This solution is arranged from large to lowest size and new switched capacitors are allocated sequentially (following the order deduced) until all voltages are in limits. This form of proceeding ensures a minimum number of new capacitors. Again, RPVS factors are used to recalculate voltage magnitudes each time a new capacitor is considered to be placed, Vcomp i=VF i+RPV Sij ∗∆Qj(12) There are some computational issues related to the solution of (10) and (11). Some negative solutions could result after the resolution of the minimization problem, which implies inductive shunts compensating capacitors. Obviously this solution is impracticable. When this situation occurs, the minimization problem is solved again after removing those buses j∈SCwith negative solution. This is done until no negative solution results. This way to proceed guarantees the minimum number of switches to compensate undervoltages. As a consequence of this issue, again a practical minimum voltage higher than the real minimum specified one must be considered, Vpmin =Vpmin +tolmin . Other point is that switched capacitors banks instead of fixed capacitors could be the available compensation shunts. In this case, when the ∆Qjsolution is finally defined as the best reactive power injection, the number of switching times for the specified capacitor bank can be easily deduced. Summarizing, the whole process is as follows, 1. Initially, load flow problem is solved to know the state of the system: complex voltages, taps of transformers and reactive power injected by shunt capacitors being into the system. 2. Matrix of sensitivities is computed and used to define the objective function, either by a linear or an exact technique as it has been discussed in section 2. 3. Optimization problem is solved, equations (10) and (11), so a vector of new injected reactive powers is deduced. 4. The former solution is arranged from large to lowest size. 15th PSCC, Liege, 22-26 August 2005 Session 16, Paper 4, Page 3
5. New switched capacitors are allocated sequentially (following the order deduced in point 4) until all voltages, recomputed by (12), are in limits. 4 Case studies Three different systems will be analyzed with the proposed methodology, •[A] The IEEE 14-bus test system. •[B] The IEEE 30-bus test system. •[C] An actual 128-bus system from a Spanish utility. The voltage limits in all the cases have been set up at ±5% of nominal voltage, and the adopted maximum and minimum tolerance have been defined in such a way that the allowed voltage interval is reduced to 1.0<V i<1.03 for all buses i. Also it is supposed any load bus is sensible to allocate a new capacitor. The two IEEE test systems have been overloadedin order to have noticeable undervoltages. This allows to know more about the accuracy of the proposed methodology. Load Buses Initial Voltage ∆V∆Q 4 0.94640 0.0535 -1.4040 5 0.94870 0.0512 2.0067 7 0.96620 0.0332 0.2160 9 0.94180 0.0579 -0.1832 10 0.91930 0.0804 0.2830 11 0.92330 0.0765 0.2707 12 0.95760 0.0424 0.0170 13 0.92970 0.0702 0.4242 14 0.88280 0.1169 0.2776 Tabla 2: Initial voltages, ∆Vvector and ∆Qvector for the IEEE 14-bus test system The initial load state for the A system results in undervoltage levels for all load buses as it is showed in column one of table 2. From these voltages and the commented practical voltage limits, the vector ∆Vis computed, which is listed in the second column of this table 2. Then the optimization problem (10) and (11) is solved resulting the vector ∆Qdepicted in the third column of the table 2. Load Initial ∆VFinal Buses ∆V5 5,13 5,13,10 Voltage 4 0.0535 0 0.0009 0.0122 0.9878 5 0.0512 -0.018 -0.0023 0 1.0061 7 0.0332 0.0052 0.0022 0 1.0104 9 0.0579 0.0299 0.0193 0 1.0138 10 0.0804 0.0572 0.0484 0 1.0161 11 0.0765 0.0645 0.0599 0.0265 0.9735 12 0.0424 0.0405 0 0.0035 0.9965 13 0.0702 0.066 -0.0061 0 1.0183 14 0.1169 0.0993 0.049 0.038 0.9620 Tabla 3: Solution for the IEEE 14-bus test system by using the linear RP V S factors As it was argued previously, buses where a negative injected reactive power results are eliminated from set SC, buses 4 and 9 in this case. Then the optimization problem is again solved but with a new number Cof possible allocations for capacitors less than the initial one. Once no any negative elements of ∆Qis obtained, this vector is arranged from large to lowest size and new switched capacitors are allocated sequentially until all voltages are in limits. For this case this situation is reached after installing capacitors in buses 5, 13 and 10, and injecting a reactive power of 116.51, 67.40 and 46.24 Mvar respectively. The ∆Vvector after each compensation, and the final compensated voltages in PQ buses, obtained by (12), are showed in table 3. As it can be noted, there are no any under/overvoltages. In order to study the accuracy of the method when linear RPV S factors are used instead of the exact ones, the whole problem for the A case has been solved by computing the exact RP V S factors. In this case the optimal placement of capacitors are the buses 5, 13 and 11, with an injected reactive power of 126.89, 64.11 and 40.27 Mvar respectively. This new solution only differs from the previous one in the last bus where a new capacitor should be allocated, resulting bus 11 instead of bus 10. This difference is due to these nodes are very closed to each other. Table 4 illustrates about the two solutions. Moreover, the final voltages by using the RPV S factors and by solving the exact load flow equations are compared in both cases. It can be concluded as the obtained solution with the linear methodology is exact enough not only to deduce the number of capacitors to be installed and their allocation, but also to compute the final voltages. The maximum relative error is not higher than a 2%, which is very low if we take into account how much low the initial voltages were. This relative error has been defined as follows, Relative error(%) = Comp. voltage −Exact comp. voltage Exact comp. voltage 100 where “Comp. voltage” refers to those compensated voltages obtained from using RVPS factors (linear or exact ones), and “Exact comp. voltage” are those voltages computed from solving an exact load flow, both cases with the new capacitors already allocated. Once the accuracy of the proposed methodology has been countersigned in a certain way by the former results, for the other two tested cases not such detailed results will be written, but only the final solution. For the B case, with 24 PQ nodes, five buses have initially undervoltages lower tan 0.95. Figure 1 shows, among others, these initial voltages. The optimal solution, by using the linear factors, drives to allocate three new capacitors in buses 9, 21 and 30, being the injected reactive power, ∆Q9,21,30 =24.97 2.82 8.47 Mvar. The compensated voltage magnitudes are also depicted in figure 1, those using the linear RPV S factors as well as the exact ones computed by solving the load flow equations. Note as compensated voltages by using the proposed linear methodology are very closed to the exact ones once more. The C case has 111 PQ buses, and the simulated load profile gives undervoltages in 27 of them. When the proposed algorithm is applied, the reached solution consists of installing 5 new capacitors injecting a reactive power detailed in table 5. The large amount of reactive power obtained in bus 14030 is justified by a high reactive load connected in this bus that produces an extremely low initial voltage of 0.823 in this bus. Figure 2 is the counterpart 15th PSCC, Liege, 22-26 August 2005 Session 16, Paper 4, Page 4
Load ∆Q5,13,10 = 1.1651 0.6740 0.4624 ∆Q5,13,11 = 1.2689 0.6411 0.4027 Final ViRelative Final ViRelative Buses Linear RV PS Exact Load Flow error (%) Exact RV PS Exact Load Flow error (%) 4 0,9878 0,9857 0.21 0,9901 0,9845 0.57 5 1,0061 1,0032 0.29 1,0130 1,0051 0.79 7 1,0104 1,0097 0.07 1,0034 0,9983 0.51 9 1,0138 1,0139 -0.01 0,9996 0,9902 0.95 10 1,0161 1,0115 0.45 0,9889 0,9746 1.47 11 0,9735 0,9717 0.19 1,0131 0,9910 2.23 12 0,9965 0,9981 -0.16 0,9979 0,9944 0.35 13 1,0183 1,0006 1.77 1,0224 0,9941 2.85 14 0,9620 0,9583 0.39 0,9645 0,9415 2.44 Tabla 4: Comparative study of final voltages for the IEEE 14-bus test system by using RP V S factors or an exact load flow Figura 1: Voltage profiles for the 30-bus system to 1, now for the C system. Again, compensated voltages are quite good, being the most relative error of 3.26 %. This result is quite good taking into account the high level of load of the system. As in the rest of the tested systems the upper limit of 1.05 is not exceeded. Moreover, the resulting few number of capacitors regards to the size of the system is emphasized, achieving the main proposed goal, that is, all the voltage magnitudes are in limits. New Capacitors Allocation Injected Reactive Power (Mvar) 4629 54.40 5126 22.57 5156 25.97 5183 43.05 5190 12.93 14030 214.45 Tabla 5: Solution for the actual 128-bus test system 5 Conclusion In this paper, a procedure to solve the capacitor placement problem is considered. A linear programming method is employed which minimizes the bus voltage deviations from voltage limits. This linear methodology has been guaranteed to reach realistic solutions not only to solve the optimization problem but also to deduce the final voltage magnitudes, even for very overloaded systems. The implemented algorithm is simple and fast, so its use on real time would be of interest in order to determine the best way to operate on all the switched capacitors being on the system to improve all voltages in a global way. 6 Acknowledgments Authors acknowledge the financial support provided by the Spanish Minister of Science and Technology under grant ENE 2004-03342. Referencias [1] J. J. Grainger and S. H. Lee, ”Optimum size and location of shunt capacitors for reduction of losses on distribution feeders”, IEEE Trans. Power App. Syst., vol. PAS-100, pp. 11051116, Mar. 1981. [2] M. E. Baran and F. F. Wu,”Optimal sizing of capacitors placed on a radial distribution system”, IEEE Trans. Power Delivery, vol. 4, pp. 735743, Jan. 1989. [3] H. D. Chiang, J. C. Wang, O. Cockings, and H. D. Shin,”Optimal capacitor placement in distribution systems; Part 1: A new formulation of overall problem”, IEEE Trans. Power Delivery, vol. 5, pp. 634642, Apr. 1990. 15th PSCC, Liege, 22-26 August 2005 Session 16, Paper 4, Page 5
Figura 2: Voltage profiles for the 128-bus system [4] H. D. Chiang, J. C. Wang, O. Cockings, and H. D. Shin, ”Optimal capacitor placement in distribution systems; Part 2: Solution algorithms and numerical results”, IEEE Trans. Power Delivery, vol. 5, pp. 643649, Apr. 1990. [5] Y. C. Huang, H. T. Yang, and C. L. Huang, ”Solving the capacitor placement problem in a radial distribution system using tabu search approach”, IEEE Trans. Power Syst., vol. 11, pp. 18681873, Nov. 1996. [6] S. Sundhararajan and A. Pahwa, Optimal selection of capacitors for radial distribution systems using a genetic algorithm, IEEE Trans. Power Syst., vol. 9, pp. 14991506, Aug. 1994. [7] K. N. Miu, H. S. Chiang, and G. Darling, Capacitor placement, replacement and control in largescale distribution systems by a GA-based two-stage algorithms, IEEE Trans. Power Syst., vol. 12, pp. 11601166, Aug. 1997. [8] A. Kalyuzhny, G. Levitin, D. Elmakis, and H. B. Haim, System approach to shunt capacitor allocation in radial distribution systems, Electric Power Syst. Res., vol. 56, pp. 5160, 2000. [9] P.Kundur, ”Power System Stability and Control”, EPRI Power System Engineering Series, McGraw Hill Inc., 1994, p.992. [10] B.Gao, G.K.Monison, P.Kundur, ”Voltage Stability Evaluation Using Modal Analysis”, IEEE Trans. Power Systems, Vo1.7, No.4, November 1992, pp. 1529 - 1542. [11] ”IEEE Special Tutorial Course - Voltage Stability”. Proceedings of the 1998 Power Engineering Society Summer meeting. San Diego CA p p (4).6. 15th PSCC, Liege, 22-26 August 2005 Session 16, Paper 4, Page 6 View publication statsView publication stats