Energies 2012, 5, 2381-2403; doi:10.3390/en5072381 energies ISSN 1996-1073 www.mdpi.com/journal/energies Article Parametric Study of Thermodynamics in the Mediterranean Courtyard as a Tool for the Design of Eco-Efficient Buildings Juan M. Rojas 1, Carmen Galán-Marín 1,* and Enrique D. Fernández-Nieto 2 1 Department of Building Construction. E.T.S. Arquitectura, University of Seville, Seville 41012, Spain; E-Mail:
[email protected] 2 Department of Applied Mathematics E.T.S. Arquitectura, University of Seville, Seville 41012, Spain; E-Mail: [email protected] * Author to whom correspondence should be addressed; E-Mail: [email protected]; Tel.: +34-954-556-591; Fax: +34-954-557-018. Received: 19 March 2012; in revised form: 29 May 2012 / Accepted: 26 June 2012 / Published: 10 July 2012 Abstract: Traditionally, people in the Mediterranean region knew that the temperatures in their courtyards were cooler in summer than outside temperature. This paper provides a quantitative study on the usefulness of Mediterranean courtyards as passive energy saving systems. This work is based on the creation of a Computational Fluid Dynamics (CFD) numerical model developed using the open source Freefem++ language. In this work, first the numerical model is tested using simplified-shape courtyards which have been previously studied both physically under controlled parameters, and mathematically through numerical simulations. We also study the most appropriate depth ratio for a courtyard, based on these simplified shapes, depending on the climate. Secondly, we apply the numerical model in a real geometry, the Monte Málaga hotel. We compare the numerical results with the monitored data of the temperature in the courtyard of the hotel. The numerical model takes into account precomputed solar radiation in the walls of the courtyard, the predominant wind and buoyancy effects. Keywords: courtyard; patio; microclimate; CFD; finite elements; sustainable architecture OPEN ACCESS
Energies 2012, 5 2382 1. Introduction It is possible to describe the courtyard concept using the definition outlined by Feijó Muñoz: “Courtyards can be defined as unbuilt spaces which are delineated by the interior facades of the buildings, or those spaces which are situated within the interior alignments of a plot” [1]. It may be possible to improve our understanding of Mediterranean courtyard’s concept if we examine the previous definition in conjunction with that of Perez-De-Lama and Cabeza: “A space that is open to the sky, typically centralized and with a geometrical shape, frequently surrounded by porticoes, which constitutes the organizing nucleus of the spaces that lay around it, and symbolically represents the community associated to it” [2]. The thermodynamic behaviour, and the related temperature distribution, in a Mediterranean courtyard is defined by the interaction of different causes, such as thermo-mechanical interactions between the walls, elements in the courtyard (fountains, vegetation, etc.) and the air circulating around them [3]. These ones generate a complex structure in the temperature distribution. Three main physical causes that explain this distribution are: stratification, convection and flow patterns. (A) Stratification: If the walls have a lower temperature than the air temperature, then the air in contact with the walls is cooled. Consequently the density of this air increases and passes to a lower layer so displacing warmer air to the upper stratum until a stable state has evolved [see Figure 1(a)]. (B) Convection: If the walls have a warmer temperature than the air (by the effect of radiation for example), the air in contact with them is warmed. A convective flow is created when the air in contact with the warmer walls rises and cooled air goes down the centre of the courtyard [see Figure 1(b)]. (C) Flow Patterns: The existence of air currents in the courtyard (for example induced by the wind) is another key factor in understanding its thermodynamic behaviour. Depending on the shape of the courtyard, different flow patterns are produced. The structure of the streamlines and therefore the distribution of temperature depends on the depth ratio D that is the proportion between the characteristic height (h) and the characteristic length (w) of the courtyard: that is to say D = h/w [see Figure 1(c)]. Figure 1. Courtyard’s vertical section. In grey colour: building section. In others colours: air at different temperatures. (a) Stratification; (b) Convection; (c) Flow patterns (Images from the CFD model). (a) (b) (c)
Energies 2012, 5 2383 The physical behaviour of air at low speeds is described by the Navier-Stokes equations. These partial differential equations are nonlinear and describe the motion of a Newtonian fluid. They are obtained by applying the principles of mass conservation, angular momentum and energy. Due to the complexity of these equations, it is not possible to obtain an analytical solution. In this work we have considered that the fluid is in a laminar regime. There are a lot of commercial CFD programs that allow an approximation of the solution of these equations to be obtained [4]. One characteristic of such commercial program’s codes is that usually it is not possible to get access to the source code. It is also difficult to introduce some modifications in the model if they are not part of the commercial code. Freefem++ is a high level open source computational language written in C++ aligned to the implementation of finite element methods. In this work we develop a code written in Freefem++ to approximate the solution of Navier-Stokes with variable density with the Boussinesq approximation. The numerical code can takes into account pre-calculated radiations over the walls of the courtyard, which is variable in space and time. Before using this mathematical model to study real courtyards, in a first step we test the model using courtyards with elementary shapes. These tests have been previously studied both physically under controlled parameters in a wind tunnel [5], and mathematically through numerical simulations [6]. Data provided by the simulations correctly reproduce the physical reality and are equivalent to those supplied by the numerical simulations performed in [6] with the software “fluent”. After, we apply the model in a real geometry, the courtyard of the Monte Málaga hotel. For this test first we compute the radiation in a partition of the walls of the courtyard. This information is taking into account by the code in order to define the boundary conditions during the numerical simulation. The predominant wind and buoyancy effects are include in the numerical simulation. We compare the numerical results with the monitored temperature in the courtyard of the hotel. This paper is organized as follows: Section 2 presents the model used for the simulations carried out in this research. Section 3 presents flow patterns that can be found in simplified-shape courtyards with a function of the proportion between the width and the height of the courtyard. This proportion will be named depth ratio (D). In Section 4 the depth ratio of the courtyard and air stratification phenomena are related based on climate conditions. The typical Mediterranean courtyards are specifically detailed, describing the different usual shapes and a checking with the results obtained from the mathematical model is given. Section 5 presents an application of the tool: the study of the evolution of the temperatures in the Monte Málaga hotel (located in Malaga, southern Spain). Conclusions of this research are shown in Section 6. 2. Numerical Model The proposed numerical model includes thermodynamic equations and Navier-Stokes equations appropriate to simulate the natural stratification and convection processes on a local scale and to simulate streamlines or flow patterns. The proposed model is especially appropriate for deep Mediterranean courtyards where these phenomena are especially important. It is considered a numerical discretization of the Navier-Stokes equations with variable density depending on the temperature. The unknowns of the equations are the velocity field (u) and the
Energies 2012, 5 2384 temperature (T). Taking into account the mass conservation equation, the momentum conservation equation and the Boussinesq hypothesis, the following equations are obtained: u tuu( u)pf u0 T tuT( T)0 where: f 0 g 0 and ρ/ρ0 is the relative density. Using the perfect gas law we can approximate the relative density by the relative temperature T/T0 (for more details see [7]). By we denote the kinematic viscosity and p is the pressure. As a boundary condition we consider the temperature of the walls of the buildings. To compute this temperature we consider radiation effects. In this way, in Section 5 we present an application of the model to simulate the temperature evolution in the courtyard of the Monte Málaga hotel. The radiation is computed using the software Autodesk Ecotect Analysis. With this software we have calculated the radiation at each hour in different parts of the external walls of the hotel. With this information we approximate Tw, the temperature of the wall, by assuming a constant temperature at each hour at each partition of the wall. We compute this temperature as the stationary solution of the partial differential equation, used to solve the following equation: Ul w(Tref Tw) (Tref 4 Tw 4) I 0 where U is the transmittance, lw is the length of the wall, σ is the Stephan-Boltzman constant, ε is the emissivity of the wall, α is the absorbance of the wall, Tref is a reference temperature and I is the radiation reaching the wall. By using this form to compute the temperature of the wall we assume that the mean temperature of the wall is almost independent of the temperature in the interior of the building. Although we consider a constant value for the transmittance, the absorbance and the emissivity, it can be considered different values of these constant at each of the walls of the courtyard, depending on the material. Let us remark that this boundary condition can be improved by taking into account the reflections of the solar radiation on the walls of the courtyard. The reference temperature is a parameter of the model which can be defined in terms of the air temperature and measure data. 3. Streamlines in Simplified Shape Courtyards There are many studies about thermodynamic behaviour in interior spaces like large halls or atria [8,9]. But there are few studies on the behaviour of exterior spaces, such as courtyards. Between these ones, it has been very important in this work the research of Hall, who has carried out several experiments in a wind tunnel in Cardington (UK) to understand the structure of streamlines inside courtyards under different wind conditions [5]. The speed of these air currents was measured at
Energies 2012, 5 2385 different heights inside and outside the courtyards and the ability of the courtyards, depending on their geometry, to disperse or concentrate a pollutant agent. Hall first described this geometry as a function of the proportion between the height and the width of the courtyard, naming it aspect ratio (h/w). In our research this proportion will be named in a more descriptive and architectural way depth ratio D = h/w. To obtain (experimentally) the degree of pollutant concentration, a uniform quantity of methane was deposited on the floor in the centre of the model courtyards in the wind tunnel. This quantity was very small so as not to interfere with the flow patterns. Concentrations of methane at different heights of the courtyard were measured. Hall demonstrated that for the same initial conditions (wind and quantity of pollutant), the concentration of the pollutant depends solely on the courtyard shape. This relationship is not a direct proportion one but it is described with an irregular curve (see Figure 2). If these non-dimensional concentrations in the base of the courtyard are represented as a function of the depth ratio D = h/w, it can be observed that for low depth ratio, low concentrations are obtained. This concentration increases in value when the depth ratio is increased up to a maximum value when D = 0.3. From this point, concentration decreases as depth ratio increases up to a minimum level when D = 1.5. From that point, if D is increased, the concentration in the base of the courtyard increases proportionally. Figure 2. Figure of the work presented by Hall et al. [5]. (a) Pollutant concentration measures in the base of the courtyard related to the proportion between the height and the width of the courtyard; (b) Non dimensional pollutant concentration formula by Hall et al. [5]. (a) (b) This behaviour is explained by Hall et al. [5] based on the presence of different current structures or flow patterns depending on the courtyard shape. Different shapes give rise to different flow speeds and different air renewals per hour in different type of courtyards. The results obtained for the streamlines in laboratory tests obtained by Hall were checked using numerical simulation by Sánchez [6]. The first application included in this work was to obtain the streamlines for simple shape courtyards. Results obtained by the proposed tool were similar to the above and fit in with the facts obtained in Hall’s wind tunnel experiments [5]. The results of the simulations and the conclusions were as follows. 2 ref CU W KQ where: K non dimensional concentration of gas C concentration in a point Uref wind speed in Hmax W width of the courtyard Q pollutant's quantity
Energies 2012, 5 2386 (a) For those courtyards with very open proportions, where D < 0.3 (see Figure 3), streamlines are fully apparent in the inner space of the courtyard with no recirculation structures such as eddies or vortexes. In courtyards where D reaches 0.3, oval eddies appear, but they produce very few air renewals. This oval eddies are more defined as D is increasing, such as the air renewal rises. Figure 3. Streamlines for D < 0.3. (b) For those courtyards where D = 1 (see Figure 4), structures and thermal distribution inside the courtyard was notably different than outside. The square shape of the courtyard allows the creation of a circular eddy which produces many more air renewals than oval eddies. In courtyards where D = 1 this whirlwind is centered in the middle of the courtyard filling the whole inner space and obtaining the best air renewal for all the inner space. Figure 4. Streamlines for D = 1. (c) For those very deep courtyards where D > 1, the outer air inflow is drastically reduced in the lower parts of the courtyard (see Figure 5). The vortex previously located in the central area filling the whole inner space of the courtyard now moves up to the upper part of the section, filling just a small part of the space inside the courtyard and becoming an obstacle that obstructs streamlines penetrating deeper inside the courtyard.
Energies 2012, 5 2387 Figure 5. Streamlines for D > 1. Although it is important to understand the mechanical behaviour of the air temperature in a courtyard by characterizing the streamlines inside the courtyard, it is even more important to determine what this means for the evolution of the temperature inside the courtyard depending on whether the courtyard behaves as a thermal source or thermal drain. The courtyard will work as a thermal source or drain according to its depth ratio and the amount of solar radiation it receives. The next section presents a study that attempts to characterize simple shape courtyards related to the type of climate. 4. Temperature Evolution in Simplified Shape Courtyards Earlier research [6] related previous concentration of pollutant experiments [5] with the ability of courtyards to disperse or concentrate heat within them. The K concentration due to flow patterns indicate the ability of air in different courtyard shapes to mix with the outer environment. The mixture of courtyard air with outside air is one of the factors that determine the temperature inside a courtyard. Depending on the depth ratio, it will be easier to balance or imbalance its temperature with the outside. The effect of conduction between volumes of air is negligible comported to convection, heat transport by mass. The heat in these conditions may be treated as if it were a “pollutant” in the air. Therefore, when temperature differences are not very large and wind is present, it is the structures of currents of air (flow patterns) rather than the processes derived from air floating (stratification, natural convection) that will condition the temperatures inside the courtyard. These flow patterns govern the mixture of the different volumes of outside and inside air at different temperatures. These patterns, in turn, depend on the shape of courtyard itself (depth ratio D). In specific cases, the geometrical shape of the courtyard affects the temperature within it in the same way it did it with pollutants. Sánchez [6] defined the relationship between concentration of contaminants and thermodynamic properties in the equation given below (Figure 6). The non-dimensional concentration of a contaminant could be replaced by a “non-dimensional concentration of heat”, (from now on, non-dimensional temperature, θ) and apply the equations developed for that. In fact, rather than measuring the concentrations of a gas, Sánchez simulated in a CFD model, the various resulting temperatures after releasing a heat flux Q in the courtyard, obtaining the curve of non-dimensional temperature shown in Figure 6(a) very similar to the concentration of pollutant curve
Energies 2012, 5 2388 in Figure 2(a). Sanchez replaced the concentration of pollutant K in the previous equation Figure 2(b), with the heat flow, obtaining the non-dimensional temperature θ according to formula in Figure 6(b). Figure 6. (a) Non dimensional temperature in the courtyard base; (b) Non dimensional temperature formula from Sánchez [6]. (a) (b) When the courtyard acts as a thermal source (for example when its walls are warmed by solar radiation), the behaviour according to Sánchez is as follows: for wide open courtyards with low depth ratios (D < 0.3) the non-dimensional temperature is low, increasing up to a maximum when D = 0.3. If the depth ratio continues increasing, the non-dimensional temperature decreases to a minimum when D = 1. For D > 0.3 an eddy is formed and reaches its maximum power of renewal when D = 1. In order to avoid overheating in the lower part of the courtyard, the greater ventilation is achieved in square section courtyards, where D = 1 (h = w). If depth ratio increases (D > 1), the altitude of the courtyard where the temperature is measured becomes a very important factor (see Figure 7). In fact while at the bottom of the courtyard the non-dimensional temperature increases proportionally with depth ratio, in the upper third, the non-dimensional temperature continues to decline. This is so because in deep courtyards, the small whirlpool is formed at the top, renewing the air there in a very intense way (see Figure 5). Let us remark that it is possible to extract other results from Hall’s experiment in addition to the previous ones. The walls of deep and well shaded courtyards are often at a lower temperature than the outside air temperature. In this case heat is not provided but absorbed and they act not as thermal sources but heat drains. This is very common in the deep courtyards of Mediterranean climates [10]. Therefore, according to our data, the following equation is proposed to determine the non dimensional temperature when the courtyard acts as a heat drain (see Figure 8). Formula in Figure 8(b) is a contribution of this paper. It complements the previous formula (see Figure 7) that was described in previous research that could only be applied to those courtyards that acted as heat sources. 2 p CTTUW Q where: θ Non dimensional temperature ρ Air Density (kg/m3) Cp Specific heat (J/kg K) T Temperature (°C) T∞ Reference temperature (°C) U∞ Wind speed in Hmax (m/s) W Width of the courtyard (m) Q Heat Pattern (W)
Energies 2012, 5 2389 Figure 7. (a) Graphic of the non dimensional temperature related to the depth ratio of the courtyard as a heat source at three different heights. Three different flow patterns are shown for D = 0.1, D = 1, D = 5 which correspond with changes of non dimensional temperature. The four lines represent θ at three different heights in the courtyard and the average temperature of the whole courtyard; (b) Non dimensional temperature formula when the courtyard acts as a thermal source [6]. (a) (b) The verification for this should be based on a wind tunnel experiment such as in the one developed by Hall [5], but in reverse on contaminant fluxes. This experiment has not been carried out yet in a physical setting (i.e., in wind tunnel). However, if the buoyancy effects (as in Hall’s experiment) are not significant, it is possible within this experiment, to consider only the mechanical effects as similar to a problem of mechanics. This class of problems is both reversible and symmetrical and therefore we can deduce the formula in Figure 8(b) in a logical manner given that the results reflect those obtained by Hall. Models of courtyards could be placed in a wind tunnel as in Hall’s experiments. But the inside space of the tunnel should be filled current of air with a pollutant (for instance heat), so that its concentration (non-dimensional temperature) at a height of reference Hmax is θref = 25. At the base of the courtyard fresh air without pollutants is provided (as a heat drain). Re-circulation and mixtures should respond to the previously proposed equation, exchanging a stream of pollutant by a heat stream. This expression presumes a reasonable symmetric behavioural pattern for these natural phenomena mechanics, on the scale studied. The graph of non-dimensional temperature in a courtyard as a heat drain (see Figure 8) shows that when the depth ratio increases, the temperature for low and medium altitudes of courtyard decreases. This is consistent with the known flow patterns for different depth ratios of courtyards (see Figure 8). The greater the depth ratio from D = 1, the less renewal in low and middle parts of the courtyard due to the formation of a small vortex plug. In other words, additional isolation. So a source, or in this case a heat drain, manages to considerably affect the isolated space in contact with it. 2 p CTTUW Q where: θ Non dimensional temperature ρ Air Density (kg/m3) Cp Specific heat (J/kg K) T Temperature (°C) T∞ Reference temperature (°C) U∞ Wind speed in Hmax (m/s) W Width of the courtyard (m) Q Heat Pattern (W)
Energies 2012, 5 2396 5. Temperature Evolution in the Courtyard of the Monte Málaga Hotel Once the model had been contrasted with previous simulations for simple shapes, we apply it to study the thermodynamic behavior of a real courtyard. In this case, the courtyard of the Monte Málaga Hotel, in the city of Málaga, Spain. The building that houses the Monte Málaga Hotel is a paradigmatic example using the thermodynamic strategy for improving the Mediterranean courtyard energy efficiency. Passive strategies complement the active ones. The common areas of the building are air-conditioned taking the air from a deep courtyard, D2 = 2.9. This courtyard is connected to another larger one, D1 = 0.77 (see Figure 14). Figure 14. (a) Image of the Monte Málaga Hotel; (b) the deep courtyard, and (c) section with air circulation diagram. (a) (b) (c) Continuous monitoring of temperatures and the outdoor patio has given valuable data to compare with the numerical model. This study shows the thermodynamic performance of both courtyards. The overheating or rarefied air of the deepest courtyard is avoided by forcing the renewal of the air. As a result, the air that is taken from this courtyard is always more temperate than the outside air, being as much as 9 °C cooler in summer as shown in the monitoring data. This means that the building annually consumes 100 kW h/m2 per year of electricity (year 2010). This is below the average consumed by hotels with similar characteristics, 165–200 kW h/m2 per year according to the IDAE (Institute for Energy Diversification and Saving of Energy, Ministry of Science and Technology, Government of Spain) [12].
Energies 2012, 5 2397 It is interesting to compare the behavior with different temperatures a few days apart. In Figure 15 the evolution of the monitored temperatures are represented. They correspond to the 27th April and the 5th May 2010. Spring days are considered to have temperatures representative of the Mediterranean climate. The days are warm but the nights are much cooler. This allows the walls of the courtyard lose heat at night. Therefore, the following day the courtyard is a cool space that can become a heat drain. However, for these two days the temperature evolution is different. The 5th May was a cooler day with a maximum of 26.05 °C at 18:00 and a minimum of 15.95 °C at 7:00 am. The courtyard shows its tempering properties, with a pleasant range of temperatures (18 °C minimum and maximum of 23 °C). It was a hot day on the 27th April with a maximum of 31.32 °C at 19:00 and a minimum of 20.13 °C at 8:00. But temperatures in the courtyard remain in a range between 19 °C and 23 °C. Figure 15. Red: Outside monitored temperature. Blue: Monitored temperature in the courtyard (a) Monitored temperatures on the 27th April 2010; (b) Monitored temperatures on the 5th May 2010. The courtyard acts as a heat drain on the morning and on the 27th as a heat source on the night. Monte Málaga Hotel, Málaga, Spain (Design work was completed in 2002 and the construction completed in 2005 by J. M. Rojas and J. R. Montoya, architects). 27th April 2010 5th May 2010 (a) (b) In Test 2 we simulate the temperature evolution with the data of 27th April 2010. We compare the monitored temperature in the courtyard with the results of the numerical simulation. The temperature evolution was simulated with the real courtyard complex geometry (see Figure 16). In this model, the definition of the boundary of the domain was defined by segments. In order to take into account the solar radiation, its average value over each segment is computed at different times. The value of Tref is set taking into account the measured temperature at 7:00 a.m. Various physical phenomena were examined in relation to the courtyards: stratification, natural convection induced by solar radiation, and wind-induced extraction. In the first test (Test 1) the buoyancy effects alone were examined in order to simulate the stratification of the air given by the difference of temperature in the courtyards of the hotel. In the final test (Test 2) the temperature evolution in the courtyard was studied when linked to solar radiation, forced air extraction and wind.
Energies 2012, 5 2398 5.1. Test 1—Stratification Effect: The Courtyard as a Heat Drain In this test the buoyancy effect of the air was studied, that is, the stratification of the air at different temperatures. This phenomenon is significant in deeper courtyards, where air speeds are lower, close to zero in some areas. To simulate the effect of stratification on the courtyard of the Monte Málaga Hotel (Figures 15 and 16), the following conditions were assumed in our model: there was no wind and the outside temperature always keep constant at 27 °C (hence the background color in Figure 17 is permanently dark red). Figure 16. (a) The geometry of the courtyard’s section [Figure 14(c)] has been divided into segments of lines to find the equations that describe them and introduce them into the numerical model; (b) Definition of the courtyard domain with coordinates of the segments in meters (code for Freefem++). (a) (b)
Energies 2012, 5 2399 Figure 17. Test 1. Stratification of the air in the courtyard by buoyancy effects. Temperature: °C; T: hours. The surface temperature of the walls in contact with the courtyards remains constant at 22 °C. Under these conditions, the air in contact with the surface of these walls is cooled, increasing its density. This cooler air then falls to the bottom of both courtyards. This process creates convective eddies, especially in the deepest courtyard (see Figure 17). These air structures disappeared when the courtyard is full of fresh air with stratification by temperature gradient (see Figures 17, bottom two). This behaviour is an example of the courtyard as a heat drain, that leads it to become, if there is no wind, a container that is filled with cooler air. 5.2. Test 2—Linking Solar Radiation, Forced Extraction and Wind In this test we simulate the temperature evolution in the Monte Málaga hotel, with data corresponding to April 27, 2010. The wind air extraction in the deeper courtyard of the Monte Málaga Hotel has been considered, in order to study their influence over the temperature. The monitoring data of external temperature and wind were also introduced within the model. In Figure 18, the evolution of temperature at several times of the day is presented. A horizontal wind of 0.01 m/s was presumed at the left external boundary (see Figure 19). Analogously a vertical extraction was presumed at the bottom of the deeper courtyard. In this simulation it was observed that the shape of the courtyard and the induced extraction allowed the generation of a vortex in the bigger courtyard. The air of the deeper courtyard was influenced by the temperature of the external air, the cooler air of the bigger courtyard, and the fact that this deeper courtyard gets less solar radiation.
Energies 2012, 5 2400 Figure 18. Test 2. Air temperatures. Forced extraction and wind. Solar radiation is imposed as boundary conditions. Temperature: °C; T: hours. In the following image using the previous model, the modules and directions of the vector speed are represented. For the biggest courtyard (D1), the formation of the wide eddy studied in the courtyards (as in Figure 4 above) can be identified, but the existence of other eddies can also be detected. In practice, structures more complex than in the simplified courtyard are observed. In the square courtyard (D1), the formation of two eddies can be detected as a result of the interaction of two courtyards of different depths and the extraction current. Mechanical causes (pressure, speeds) represented in Figure 19 and thermodynamic causes (buoyancy by different temperatures) represented in Figure 18, interact in a complex form. This determines the definition in detail of these air structures. Only a numerical model that correctly simulates the interaction between both, such as the one developed within this study is useful to us to calculate the temperature inside these courtyards.
Energies 2012, 5 2401 Figure 19. Test 2. Air velocities. Forced extraction and wind. Solar radiation is imposed as boundary conditions. Velocities: m/s. T: hours. In Figure 20 we present the comparison between the monitored temperature and the result of the numerical simulation. We can observe that the numerical results obtained with the model taking into account all the described phenomena is able to capture the averaged behaviour of the courtyard. Figure 20. Red: Outside monitored temperature on the 27th April 2010. Blue: Monitored temperature in the courtyard on the 27th April 2010. Orange: numerical results. 6. Conclusions This work is the first part of a project with an interdisciplinary team of architects, mathematicians, and engineering experts in the field of thermodynamic processes. The final objective of the project is the design of a tool that allows for the calculation of the inside air temperature within a courtyard, during the project phase. Using the information of the courtyard’s geometry (architecture) and the local climate where it is placed (microclimate), to calculate this temperature. The aim of this research is to allow thermodynamically controlled design. This will be achieved by quantifying the energy, and therefore economic savings achieved by the design of a specific courtyard. In this paper we develop of a Computational Fluid Dynamics (CFD) numerical model that uses the open source Freefem++ language. Firstly the numerical model has been tested using simplified-shape
Energies 2012, 5 2402 courtyards which have been previously studied both physically under controlled parameters, and mathematically through numerical simulations. We also present a study about the most appropriate depth ratio for a courtyard, based on these simplified shapes, depending on the climate. The numerical model is applied to study the temperature evolution in the courtyard of the Monte Málaga hotel. When we compare the numerical results with the monitored data of the temperature in the courtyard of the hotel we observe that the numerical results predict with a good precision the average behaviour of its evolution. The developed numerical code takes into account precomputed solar radiation in the walls of the courtyard, the predominant wind and buoyancy effects. The main purpose of the model is to face complex situations such those in real buildings. The described behaviours (stratification, convection, airflow patterns and shape-depth ratio) overlap and it is not easy to foresee the result of the addition of each partial phenomenon. Results obtained have so far have proven that the model is useful to reproduce the thermodynamic behaviour of real buildings, showing that air temperatures inside deep narrow courtyards (like those so common in the Mediterranean area) are substantially warmer than the outside temperatures. The use of the model as a calculation tool to quantify the thermal benefits of this space, gives rise to new possibilities for designing more eco-efficient buildings within budget, updated and parametrical version of the traditional courtyard, a design which has been in use for the past four thousand years [13]. Acknowledgements This work has been partially supported by the Andalusian Government Research project TEP-7985. References 1. Feijó Muñoz, J.; Meiss, A. El espacio exterior del CTE-DB-HS3: metodología para el estudio de soluciones alternativas. In City and Landscape; Spanish Government: Madrid, Spain, 2011; pp. 71–79. 2. Pérez-de-Lama, J.; Cabeza, J.M. A holistic approach to the Mediterranean patio. Extending the new method of configuration factors to semi-open spaces. In Environmentally Friendly Cities, Proceedings of the 15th Passive and Low Energy Architecture (PLEA’98), Lisbon, Portugal, June 1998; pp. 167–170. 3. Guerra, J.; Álvarez Domínguez, S.; Rodriguez, E.A.R. Velazquez. Comfort Issues in the Outdoor at Expo’92. In Proceeding of Passive and Low Energy Architecture (PLEA’91), Seville, Spain, September 1991; pp. 179–187. 4. Chen, Q.Y. Using computational tools to factor wind into architectural environment design. Energy Build. 2004; 36, 1197–1209. 5. Hall, D.J.; Walker, S.; Spanton, A.M. Dispersion from Courtyard and Other Spaces. Atmos. Environ. 1999, 33, 1187–1203. 6. Sánchez de la Flor, F.J. Modificaciones microclimáticas inducidas por el entorno del edificio y su influencia sobre las demandas energéticas de acondicionamiento. Ph.D. Thesis, University of Seville, Seville, Spain, 1 July 2003.
Energies 2012, 5 2403 7. Dobrzynski, C. Adaptation de maillage anisotrope 3d et application à l'aéro-thermique des bâtiments. Ph.D. Thesis, Pierre et Marie Curie University, Paris, France, 2005. 8. Tanasic, N.; Jankesa, G.; Skistad, H. CFD analysis and airflow measurements to approach large industrial halls energy efficiency: A case study of a cardboard mill hall. Energy Build. 2011, 43, 1200–1206. 9. Pan, Y.; Li, Y.; Huang, Z.; Wu, G. Study on simulation methods of atrium building cooling load in hot and humid regions. Energy Build. 2010, 42, 1654–1660. 10. Capitel, A. La Arquitectura del Patio, 1st ed.; Editorial Gustavo Gili: Barcelona, Spain, 2005; pp. 20–155. 11. Sierra Delgado, J.R. La casa en Sevilla 1976–1996; El Monte Foundation & Electa: Sevilla, Spain, 1996; pp. 213–318. 12. IDAE. Ahorro de Energía en el Sector Hotelero. Recomendaciones y Soluciones de Bajo Riesgo; IDAE, Institute for Energy saving and diversification, Ministry of Science and Technology, Spanish Government: Madrid, Spain, 2001; pp. 11–30. 13. Giedion, S. El Presente Eterno2: Los Comienzos de la Arquitectura; Alianza Editors: Madrid, Spain, 1981; pp. 197–198. © 2012 by the authors; licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution license (http://creativecommons.org/licenses/by/3.0/).