Characterizing the Steady-State Performance of AC Lines Through a Dimensionless Universal Model

Cruz-Romero, Pedro Luis; Gómez Expósito, Antonio; Del-Pino-López, Juan Carlos

Abstract

This paper revisits the AC power line model. Based solely on three dimensionless parameters, a universal electrical model is first developed, which is valid for any kind of power line (overhead, underground/submarine or gas insulated), irrespective of its rated voltage and length. Then, by neglecting the shunt losses, compact expressions are obtained in terms of the two remaining parameters for all electrical magnitudes characterizing the steady-state behavior of any line, such as real and reactive power flows at both ends, losses, charging current, transmission capability, etc. As a result, universal parameterized curves are also provided, including the well-known PV and P-δ curves. Moreover, numerical ranges of defining parameters are obtained for a diversity of present or future line arrangements, rated voltages and lengths, which are then represented as clusters of points on the universal curves. Beyond educational purposes, the proposed formulation and the associated characteristic curves can be useful, at the planning or design stages, when a certain degree of parameter uncertainty is still present, in order to compare different designs, or when selecting the most suitable simplified model for a particular case study, before fully defining the line features (type of conductor, phase-to-phase clearance, type of configuration, insulation, etc.).

Full text

Received March 22, 2022, accepted April 6, 2022, date of publication April 12, 2022, date of current version April 20, 2022. Digital Object Identifier 10.1109/ACCESS.2022.3166900 Characterizing the Steady-State Performance of AC Lines Through a Dimensionless Universal Model PEDRO CRUZ-ROMERO , (Member, IEEE), ANTONIO GÓMEZ-EXPÓSITO , (Fellow, IEEE), AND JUAN CARLOS DEL-PINO-LÓPEZ Departamento de Ingeniería Eléctrica, Universidad de Sevilla, 41004 Seville, Spain Corresponding author: Pedro Cruz-Romero ([email protected]) This work was supported in part by the Research Grant PID 2020-116433RB-I00 (AEI) and Grant ENE2017-89669-R (AEI), and in part by CERVERA under Grant CER-20191019. ABSTRACT This paper revisits the AC power line model. Based solely on three dimensionless parameters, a universal electrical model is first developed, which is valid for any kind of power line (overhead, underground/submarine or gas insulated), irrespective of its rated voltage and length. Then, by neglecting the shunt losses, compact expressions are obtained in terms of the two remaining parameters for all electrical magnitudes characterizing the steady-state behavior of any line, such as real and reactive power flows at both ends, losses, charging current, transmission capability, etc. As a result, universal parameterized curves are also provided, including the well-known PV and P-δcurves. Moreover, numerical ranges of defining parameters are obtained for a diversity of present or future line arrangements, rated voltages and lengths, which are then represented as clusters of points on the universal curves. Beyond educational purposes, the proposed formulation and the associated characteristic curves can be useful, at the planning or design stages, when a certain degree of parameter uncertainty is still present, in order to compare different designs, or when selecting the most suitable simplified model for a particular case study, before fully defining the line features (type of conductor, phase-to-phase clearance, type of configuration, insulation, etc.). INDEX TERMS Charging current, distributed-parameter model, gas insulated line, steady-state stability limit. LIST OF SYMBOLS (LINE-SPECIFIC PARAMETERS AND MAGNITUDES) bPer-unit-length shunt capacitive susceptance (S/km). BsSeries susceptance (S). (Bspu : per-unit magnitude). Bsh Shunt susceptance (S). (Bshpu : per-unit magnitude). cos ϕpower factor of the load connected to the receiving end. CPer-unit-length shunt capacitance (F/km). gPer-unit-length shunt conductance (S/km). GsSeries conductance (S). (Gspu : per-unit magnitude). Gsh Shunt conductance (S). (Gshpu : per-unit magnitude). The associate editor coordinating the review of this manuscript and approving it for publication was Fabio Mottola . InMaximum current (Thermally-limited or stabilitylimited) (A). IrRMS current phasor at the receiving end (A). isc Normalized sending-end charging current. ismax Normalized sending-end current corresponding to pr=prn. IsRMS current phasor at the sending end (A). lLength (km). lcCritical length (km). LPer-unit-length series inductance (H/km). plNormalized active losses. prNormalized magnitude of Prpu . Prpu Per-unit receiving-end active power (pu). pr0Normalized power at the receiving end when ql=0. prmax Value of prfor δ=δmax. prn Normalized magnitude of Prn. VOLUME 10, 2022 This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/ 40609 P. Cruz-Romero et al.: Characterizing Steady-State Performance of AC Lines Prn Maximum active power (thermally-limited or stability-limited) at the receiving end (MW). psNormalized magnitude of Pspu . psc Value of psfor pr=qr=0. Pspu Per-unit sending-end active power (pu). qlNormalized reactive balance. qrNormalized magnitude of Qrpu . qsc Value of qsfor pr=qr=0. Qrpu Per-unit receiving-end reactive power (pu). Qrn Reactive power at the receiving end when active power is Prn and Vr=0.95Vs(MW). qsNormalized magnitude of Qspu . Qspu Per-unit sending-end reactive power (pu). rPer-unit-length series resistance (/km). RsSeries resistance (). ssc Value of sending-end apparent power for pr= qr=0. SIL Surge impedance loading. xPer-unit-length series inductive reactance (/km). VrRMS voltage at the receiving end of the line. (Vrpu : per-unit magnitude). VsRMS voltage at the sending end of the line. (Vspu : per-unit magnitude). vrNormalized voltage at the receiving end of the line. vrc Value of vrfor pr=qr=0. XsSeries reactance (). yPer-unit-length complex shunt admittance (S/km). YsSeries admittance (S). zPer-unit-length complex series impedance (/km). Z0Characteristic impedance ()Complex series impedance (). αAttenuation constant (1/km). βPhase constant (1/km). δphase difference between sending and receiving voltages (rad). δmax steady-state stability limit angle (rad). γPropagation constant (1/km). κsCoefficient of series losses (also named κ). κsh Coefficient of shunt losses. τCoefficient of reactive balance. ωAngular frequency of electrical magnitudes (rad/s) I. INTRODUCTION Starting from the single-phase representation of two-port networks (customarily represented by the ABCD matrix), different distributed-parameter models of three-phase symmetrical lines have found widespread use, such as the π-equivalent, 0-equivalent or T-equivalent circuits [1]. For a given frequency (ω=2πf), the steady-state behavior of a power line can be represented through an equivalent circuit which depends ultimately on four electrical parameters, namely the series resistance and reactance (rand x=ωL), and the shunt conductance and susceptance (gand b=ωC), all per unit length, along with the line length l(which is worth retaining as an additional parameter to duly analyze its role). Parametric studies that aim to be as universal as possible should, therefore, analyze the impact of these 4+1 parameters on the electrical performance of any line. Historically, the presence of hyperbolic functions in the expressions of the ABCD matrix, and the lack of digital computers, led to the use of approximate expressions, obtained by retaining the first two or three terms of their series expansion. Alternatively, a long line can be divided into a finite number of short segments, each characterized by a lumped-parameter model, in which all parameters are proportional to the respective segment length. But none of those approximations can get rid of the five required parameters. Simplified models, which take advantage of the large differences in parameter values found in several particular cases of practical interest, are routinely used, such as the four-parameter model (shunt conductance neglected), which is acceptable for virtually any overhead line, the three-parameter model (shunt admittance neglected), for relatively short overhead lines, or the lossless model (series resistance and shunt conductance neglected), usually adopted for long overhead lines rated at ultra high voltages [1]. Those approximations have proven useful in explaining a variety of power line behaviors, preferably in a graphical form to more easily capture the impact of each parameter. Additional parameterizations are frequently found, by considering for instance the rated voltage or external parameters, such as the power factor (or reactive power) of the load served by the line. This paper develops an accurate positive-sequence analytical model, valid for any kind of AC line, which is based only on three dimensionless parameters. Such universal model leads to a rather simple algebraic formulation, from which the customary parameterized graphical analysis can be easily derived. Then, the performance of a generic line (voltage profile, transmission capability, reactive power internal balance, power losses, etc.), is fully characterized with the help of the proposed model. The paper is divided as follows: Section II briefly provides the background (the classical distributed-parameter π-circuit). Section III reviews previous parametric studies that have used this formulation in its different simplifying variants. Section IV presents the new parameters and the corresponding dimensionless formulation of the line power flows. Section V presents the main analytical and graphical results derived from the application of the model on all types of lines, assuming the shunt conductance to be negligible. Finally, Section VI presents the conclusions. II. DISTRIBUTED-PARAMETER π-CIRCUIT The single-phase equivalent π-circuit of a power line, obtained from the ABCD matrix [1], is depicted in Fig. 1, where the total series impedance (Zs) and half shunt admittance (Ysh) can be expressed as nonlinear functions of five parameters, including the four per-unit-length values 40610 VOLUME 10, 2022 P. Cruz-Romero et al.: Characterizing Steady-State Performance of AC Lines (r,x,gand b) and the line length, l, as follows: Zs=Rs+jXs=zl sinh γl γl=Z0sinh γl(1) Ysh =Gsh +jBsh =yl 2 tanh γl 2 γl 2=1 Z0 tanh γl 2(2) where z=r+jx,y=g+jb and γ=√zy =α+jβ, Z0=√z/yare known, respectively, as the propagation constant and the characteristic impedance. In the lossless case (r=g=0), γis purely imaginary (α=0) and Z0reduces to a resistance (R0). When the line is loaded with a pure resistance equal to R0, the operating point is known as Surge Impedance Loading (SIL), which is frequently used as a reference. It can be shown that any lossless line serving the SIL is perfectly balanced in terms of reactive power, and features a flat voltage profile [1]. For the purposes of this paper, the series admittance rather than the series impedance will be used: Ys=1/Zs=Gs−jBs(3) Note the minus sign preceding Bs, intentionally used so that all line parameters are positive (this change of sign is not needed in (2) because Bsh >0). Accordingly, the current-voltage relationships for the single-phase circuit of Fig. 1are as follows, when voltages are represented in polar coordinates: Is= −(Gs−jBs)Vr+[(Gs+Gsh)−j(Bs−Bsh)]Vs6δ Ir=(Gs−jBs)Vs6δ−[(Gs+Gsh)−j(Bs−Bsh)]Vr Then, the real and reactive power flows can be readily obtained from their definition (P+jQ =V I∗). At this point, it is customary to adopt the per unit system, which has two main advantages: 1) all transformer ratios become 1:1 (i.e., all impedances/admittances are referred to a common framework); 2) single-phase and three-phase magnitudes are indistinguishable for balanced systems. When doing so, the power flows at the sending (input power) and receiving (output power) ends, in per-unit magnitudes, are given by: Pspu =Vrpu Vspu (Bspu sin δ−Gspu cos δ) +V2 spu (Gspu +Gshpu ) (4) Qspu = −Vrpu Vspu (Bspu cos δ+Gspu sin δ) +V2 spu (Bspu −Bshpu ) (5) Prpu =Vrpu Vspu (Bspu sin δ+Gspu cos δ) −V2 rpu (Gspu +Gshpu ) (6) Qrpu =Vrpu Vspu (Bspu cos δ−Gspu sin δ) −V2 rpu (Bspu −Bshpu ) (7) In addition to the four line parameters, each equation embeds four electrical variables (power, voltage magnitudes and phase difference) which, independently or combined, are to be considered in the parameterized curves. FIGURE 1. Equivalent π-circuit of a power line. III. BRIEF REVIEW OF PARAMETRIC STUDIES Since the beginnings of power engineering, the parametric analysis of lines has helped to better understand their electrical performance. Without claiming to be exhaustive, we summarize here some of those studies, focusing especially on aspects like parameters involved, simplifying assumptions and analytical and graphical results. In [2] the aim of the parametric analysis was the estimation of the loadability characteristic curve (steady-state load capability versus length) of HV overhead lines (34.5−330 kV), obtaining empirically derived curves that are based on a predefined steady-state stability margin. In [3], a more analytical approach is performed, obtaining similar curves under the assumptions of lossless line and constant γvalue for all line designs. This way, the load capability (in per-unit of SIL) is not dependent on per-unit-length parameters, being only a function of the line length and terminal voltages. Assuming a constant load power factor, it is possible to obtain simple curves of line loadability versus length, within voltage drop and stability limits. Moreover, the analysis of [2] is extended in [3] to EHV/UHV transmission lines, highlighting the fact that the simplifying assumptions are even more justified at those voltage levels. If the analysis is aimed at assessing the effect of the line design (single/double circuit, three/ four-conductor bundle, etc.) on its loadability characteristic, then a curve for each design should be considered [4]. Recently, a general formulation of the loadability characteristic regions (thermal limit, voltage drop limit and stability limit) has been proposed [5]. Regarding high voltage cables (66-220 kV), simple and approximate analytical expressions for the critical length (lc) are derived in [6] by neglecting the series impedance Zs. Graphical representations of Ir/Inversus l/lc, where In is the cable ampacity, are plotted for a particular 220 kV, 2000 MCM high pressure, oil-filled pipe-type cable. Application of the same curves to other cross sections yields an acceptable error at voltages equal to or higher than 132 kV. When dry-type cables with low dielectric losses are rather considered, Gsh can be neglected for l<150 km. In [7], the loadability and losses of compensated, three-core submarine cables with voltages between 132 and 400 kV are depicted versus the cable length, for a particular cross section of 1000 mm2. In [8], an in-depth analysis of the behavior of umbilical cables with rated voltages between 35 and 150 kV and cable cross sections between 95 and 400 mm2is performed. The receiving end voltage and power, as well as the sending end current, are depicted versus the cable length in VOLUME 10, 2022 40611 P. Cruz-Romero et al.: Characterizing Steady-State Performance of AC Lines order to highlight the limitation of power transfer due to the charging current. We can conclude that the previous parametric studies have usually been devoted to analyzing a particular aspect of a certain type of line (e.g. long overhead line, high voltage underground cable, etc.), generally applying some modeling assumptions and representing relevant magnitudes (e.g., receiving active power or sending charging current versus length) for a particular voltage range and configuration. This work is not intended to enhance those specific studies (well established in the literature), but rather to develop a comprehensive analytical and graphical framework, based on the distributed parameter model, which is accurate enough for all types of lines. The proposed unified framework uses three dimensionless parameters, which can be reduced for practical purposes to two parameters only. As the values of those parameters lie in a predefined interval for each major category of line, it is possible to assess the performance of a certain line, real or hypothetical, even if its parameters are not precisely known, by resorting to typical or expected values. IV. DIMENSIONLESS PARAMETERS AND POWER FLOWS To begin with, the following reference power, known as the Static Stability Limit (SSL), or static transmission capacity, is introduced: SSL =V2 spu Bspu .(8) Note that, as the sending voltage is normally very close to the rated voltage, the SSL is mainly determined by the series admittance (i.e., by the tower/conductor configuration and line length). The reader should be aware that, by neglecting the series resistance (only valid for UHV lines), the SSL is also defined in some classical textbooks as V2 spu /Xspu . While the reasons for the name of this reference power will be apparent later on, it is worth noting at this point that the SSL is generally much larger than the SIL, also used as an alternative reference power in the literature. Then, the power flow relationships (4)-(7) are normalized by dividing both members of the equations by the SSL, leading to: ps=vr(sin δ−κscos δ)+(κs+κsκsh) (9) qs= −vr(cos δ+κssin δ)+(1 −τ) (10) pr=vr(sin δ+κscos δ)−v2 r(κs+κsκsh) (11) qr=vr(cos δ−κssin δ)−v2 r(1 −τ) (12) where vr=Vrpu /Vspu denotes the receiving voltage normalized with the sending voltage. The above normalized power flows constitute the basis of the universal model developed in this work. They are nonlinear functions of the normalized receiving voltage (vr) and the phase angle difference between the two end buses (δ), along with three dimensionless parameters that will be introduced in the sequel. A. COEFFICIENT OF SERIES LOSSES This represents the relative size of the series conductance (resistance) with respect to the series susceptance (reactance): κs=Gs Bs=Rs Xs .(13) The value of κsranges, for any kind of realistic AC line, between 0.05 (UHV transmission level) and 1.5 (LV feeder). B. COEFFICIENT OF SHUNT LOSSES This is the ratio between the shunt and series conductance: κsh =Gsh Gs .(14) The value of κsh is generally negligible, except for UHV lines facing very special environmental conditions. If neglected, as is customarily done, then the active power line losses (pl) are proportional to κs: pl=ps−pr=κs(1 +v2 r−2vrcos δ).(15) C. COEFFICIENT OF REACTIVE POWER BALANCE This ratio represents the relative size of the shunt susceptance with respect to the series susceptance: τ=Bsh Bs .(16) A discussion follows, to better understand its range of values and role in the reactive power balance. From (16), taking into account (1) and (2), a very accurate approximation (less than 0.3 % error for any kind of power line), can be derived as follows: τ≈1 4bxl2sin βl βl3−sin βl βl(1 +κ2 s).(17) The ratio sin βl/βlis always close to 1, whereas κsranges between 0.05 and 1.5. Therefore, from (17), the following limits apply in practice: 0.5≤τ bxl2≤1.6.(18) By giving extreme values to b,xand lwe obtain the range of possible values for τ: 10−6≤τ≤0.25 ,(19) Note that the (quadratic) effect of the line length on the electrical behavior of the line is integrated in this parameter, which explains its unusually wide range of variation if it has to cover all power lines of practical interest. From (10) and (12) the reactive power balance of the line is given by ql=qs−qr=(1 +v2 r)(1 −τ)−2vrcos δ . (20) where a positive (negative) value means that the line has a deficit (surplus) of reactive power. Equation (20) compactly shows the important role of τ(and hence the line length) in the reactive power balance of the line, which justifies its name. 40612 VOLUME 10, 2022 P. Cruz-Romero et al.: Characterizing Steady-State Performance of AC Lines V. APPLICATIONS OF THE UNIVERSAL LINE MODEL In this section, the steady-state electrical behavior of any kind of line, including the line loadability, efficiency, reactive power requirements, charging current, Ferranti effect and PV/QV/PQ curves, will be fully characterized based on the coefficients κsand τ. For this purpose, it will be assumed that κsh =0 (i.e., Gsh Gs). Hence, for simplicity of notation, κswill be named just κin the sequel. A total of 20 power lines (see Table 1), covering the three major types (overhead, underground/submarine and gas insulated), as well as a wide range of rated voltages (from 400 V to 1200 kV), have been considered to illustrate the analysis and annotate the resulting curves. For each line, the length lis selected from the top range of typical present or future values. Along with the parameters, Table 1includes the values of the active power at the receiving end, Prn (stability-limited in cases O6, O7 and O8, thermally-limited for the rest), as well as the reactive power Qrn calculated so that Vr=0.95Vs for the given active power flow. Note that the reactive power is negative for overhead lines (i.e., it is also injected, rather than drawn, at the receiving end) and positive for cables, reflecting deficit and surplus, respectively. For the stabilitylimited lines, it is assumed that the maximum allowed phase angle difference is δmax/2, where δmax denotes the value of δcorresponding to the theoretical steady-state transmission capacity, as discussed below. The values of κand τ, corresponding to the lines of Table 1, are shown in Table 2, where a general trend for the evolution of those parameters with type of line and voltage can be observed. For the three line types, the behavior of κis similar, namely decreasing from higher voltages. This is explained from (13) and (1): κ=Rs Xs= Re[zl sinh γl γl] Im[zl sinh γl γl]≈Re[zl] Im[zl]=r x.(21) Typically, the ratio r/xdecreases for increasing voltages, regardless the type of line. Note that, despite this general trend, there are particular cases, such as U3, departing from this rule of thumb, owing to the influence of other factors, like different conductor clearances in the underground case. Regarding the evolution of τwith voltage and type of line, it is worth recalling from (18) that τis basically proportional to bxl2. For each type of line, the dependence with the square of length is the main reason behind the behavior of τ. For overhead lines, the increasing length with voltage of the cases of Table 1explains the evolution of τfrom O1 to O8. On the other hand, for the underground cables, the evolution of length against voltage is basically decreasing, so the behavior of τis the same. Eventually, for GILs of Table 1the length is again increasing with voltage, so τwill behave similarly. For the same reason, when comparing lines of similar length, even of different voltages, the difference in τwill be due basically to the product bx. A good example is O4 and G4, both with the same length (150 km). From Table 2, TABLE 1. Parameters of typical power lines (50 Hz, g=0). TABLE 2. Values of κand τfor the lines of Table 1. the values of τfor O4 and G4 are 134 and 125, respectively, which are roughly in the same proportion as their product bx. A. LINE LOADABILITY Regarding the behavior of lines in terms of active/reactive power flows, assuming that the sending voltage is equal to the rated voltage, it is customary to separately consider two idealized boundary constraints at the receiving bus, namely: 1) the voltage is specified (PV bus) and 2) the reactive power consumption is specified (PQ bus). In practice, the actual operating condition will lie somewhere between those extreme cases, depending on the type of line. For instance, a line belonging to a strongly meshed transmission system may be closer to the PV case, whereas a radial distribution line will be better characterized by the PQ-bus assumption. Both cases are considered below when analyzing the loadability from the steady-state stability viewpoint. 1) RECEIVING PV BUS The maximum active power that can reach the receiving end for a given voltage (PV bus) can be obtained from (11) as VOLUME 10, 2022 40613 P. Cruz-Romero et al.: Characterizing Steady-State Performance of AC Lines FIGURE 2. pr−δcurves for different values of κwith vr=1 pu (top) and for different values of vrwith κ=0.1 (bottom). follows: ∂pr/∂δ =0⇒δmax =arctan(1/κ) prmax =vrp1+κ2−κv2 r.(22) This limit depends to a greater extent on κand to a lesser extent on vr, as can be seen in Fig. 2, that shows the curves of pr(δ) for different values of κ, with vr=1 pu (top), and for different values of vrwith κ=0.1 (bottom). In the lossless case (κ=0), prmax =vr. Therefore, if the receiving voltage is maintained at the rated voltage (vr=1), then the maximum active power that can reach the receiving bus is exactly the SSL (prmax =1). But the same maximum power could be achieved in the lossy cases provided that vr>1. It is worth noting that for vr≤1 all the curves pr−δhave a common point at δ=arccos vr, regardless of the value of κ. Needless to say, angles larger than δmax correspond to infeasible steady-state operating points. In practice, a tighter limit than the SSL value is customarily imposed, in an attempt to address transient stability issues (e.g., sudden loss of a reactive power compensator near the receiving end). For instance, δ=δmax/2 is assumed in Table 1to determine the maximum active power of lines O6, O7 and O8 (δmax is 84◦for O6 and 88◦for O7 and O8), but more conservative values, such as δ=δmax/3, are frequently found in the literature. 2) RECEIVING PQ BUS The pr(δ) curves can also be obtained by imposing a given load power factor (cos ϕ) at the receiving bus (PQ bus). FIGURE 3. pr−δcurves for different values of κand τwith cosϕ=0.9. Eliminating vrby combining (11)-(12): vr=(1 −κtan ϕ) cos δ−(κ+tan ϕ) sin δ 1−τ−κtan ϕ,(23) leads to an expression of pr, not shown due to its complexity, which is depicted in Figure 3for representative values of κand τ. In this case, the maximum transmitted active power is roughly half the maximum value obtained for the PV-bus case. Note that the parameter τaffects the curves only slightly, whereas the influence of κis higher, much like in Figure 2(top). B. LINE EFFICIENCY From (9) and (11) the universal line efficiency expression is given by η=Pr Ps=pr ps=sin δ+κ(cos δ−vr) sin δ−κ(cos δ−1/vr).(24) Figure 4represents the efficiency versus κfor different values of δand two values of vr, namely vr=1 (solid line) and vr=0.9 (dashed line). As expected, the losses are null (η=1) for κ=0. For δ > 0, it can be shown that, for any vr<1, the respective ηcurve intersects with that for vr=1 exactly when η=vr. This can be observed in the figure, where the efficiency curves for vr=1 and vr=0.9 intersect, for a given δ > 0, at η=0.9. C. REACTIVE POWER BALANCE In this subsection, the line behavior regarding the generation/ consumption of reactive power is analyzed for the PV and PQ receiving end cases. 1) RECEIVING PV BUS In the PV-bus case, for a given vr, the reactive power balance of the line depends on the values of τand δ. For small values of τand δ, the first term of (20) is comparable to the second one, resulting in a narrow range of reactive power consumption/generation. On the contrary, for larger values of τand δthe first term of (20) is lower and the second term is higher, giving rise to a wider range of reactive power consumption/generation. 40614 VOLUME 10, 2022 P. Cruz-Romero et al.: Characterizing Steady-State Performance of AC Lines FIGURE 4. Line efficiency as a function of κand δfor two values of vr. FIGURE 5. Curves ql−δfor different values of τthrough the whole load range of the overhead lines in Table 1(vr=0.95 pu). This is better observed in Figures 5(overhead lines) and 6 (rest of lines), where qlis depicted versus δfor the values of τ corresponding to the whole set of lines in Table 1, when vr= 0.95 pu (qualitatively similar results are obtained for vr≈1). In Figure 5, the medium voltage overhead lines (O1, O2) consume/generate a small amount of reactive power in the whole loading range (for vr≈1) due to the small values of τ and δ. On the contrary, for high voltage overhead lines (O3 to O8) both terms of (20) may become quite different, leading to a much wider range of qlvalues. For the underground/submarine and GIL lines (Figure 6), typically shorter than overhead lines, the conclusion is similar to that of the medium voltage lines, O1 and O2. In these cases, τis small (it ranges from 2.8·10−6to 0.0265), so the first term of (20) is large, but the values of δare also low (second FIGURE 6. Curves ql−δfor different values of τthrough the whole load range of the underground/submarine and GIL lines in Table 1 (vr=0.95 pu). term of (20) non negligible), leading to relatively small reactive power imbalances. Accordingly, the range of variation between the loaded and unloaded cases is quite narrow, owing to the small range of variation of δ. As expected, as shown in Figure 6, the value of qlis mostly negative (surplus of reactive power). Be aware that, owing to the normalization of magnitudes, the scales of qlin figures 5(overhead lines) and 6 (GIL and underground lines) are quite different, so directly comparing the qlvalues from both figures can be misleading. 2) RECEIVING PQ BUS In the PQ-bus case, vrcan be eliminated from (20), by means of (23). This way, qlbecomes a function of δ, the power factor at the receiving end and the parameters κand τ. Assuming cos ϕ=0.9, the functions ql(δ) are represented in Figure 7 VOLUME 10, 2022 40615 P. Cruz-Romero et al.: Characterizing Steady-State Performance of AC Lines FIGURE 7. PQ bus: ql−δcurves for cosϕ=0.9 and different values of κ and τ. for the same values of κand τas in Figure 2. In contrast to Figure 2,τis more influential in this case than κin relation to the overall reactive power of the line. For light loads, there is an excess of reactive power, which intensifies for increasing values of τand alleviates for increasing line loadings. D. ACTIVE POWER FLOW THAT BALANCES THE REACTIVE POWER REQUIREMENTS OF THE LINE In Figures 5and 6the horizontal axis (ql=0) corresponds to the case in which the reactive power consumption of the series inductance is offset by the reactive power supplied by the shunt capacitance. Let pr0denote the real power delivered by the line when ql=0. In the lossless case, this operating point is termed the ‘‘surge impedance loading’’ (SIL), which is a reference or representative point worth characterizing. Figure 8represents pr0against τfor different values of κ and vr=0.95 (similar results are obtained for vr≈1). The cases O1, O2, U1 and U2 of Table 1are not shown, since ql=0 leads to an infeasible case, with no real solution for pr0. The normalized loadability limits (prn), provided in Table 1, are also shown in Figure 8. For the overhead lines considered, prn is always higher than pr0, which means that external reactive power support will be needed to deliver such levels of active power. Note, however, that for longer lengths than those assumed in Table 1(higher values of τ) the loadability limit might become lower than pr0, which is uneconomic. On the other hand, for underground/submarine and GIL lines it is generally verified that prn <pr0, meaning that a surplus of reactive power will always exist, regardless of the line loading. A notable exception is the line G1, that behaves much like an overhead line in this regard. This opens up the possibility of designing GIL lines at other voltages and lengths with a view to keeping the reactive unbalance at low levels. It is possible to obtain an approximate yet accurate enough analytic expression for pr0(vr) by equating (20) to zero, from which cos δ0=1+v2 r 2vr (1 −τ)≈1−τ , (25) sin δ0≈pτ(2 −τ),(26) The above approximations are acceptable as long as vr remains close to 1 (the practical case). For example, for vr= 0.95 the error in the approximation is 0.1%. Replacing (25) and (26) into (11) yields pr0(vr)≈vrpτ(2 −τ)+κ(1 −τ−vr).(27) Note that, for the particular value τ=1−vr, the second term in (27) vanishes and pr0is not a function of κ(as shown by the common point for all curves in Figure 8). In the lossless case (κ=0), pr0reduces to the well-known SIL concept, for which the following simplified expression is obtained in terms of normalized parameters: SIL ≈vrpτ(2 −τ)≈vr√2τ . (28) E. CHARGING CURRENT The charging current isc of a line is the current at the sending end with no load at the receiving end (pr=qr=0). In some cases (typically in long cables) this unavoidable current can be so large that the remaining ampacity gets drastically reduced. By equating (11) and (12) to zero, the expressions for the no-load voltage at the receiving end and the real, reactive and apparent powers at the sending end are obtained. A further simplification is made by taking into account that τ2, leading to: psc ≈κτ2 1+κ2−2τ>0,(29) qsc ≈ −τ2+2κ2−3τ 1+κ2−2τ,(30) isc =ssc ≈2τ√1+κ2−τ √1+κ2−2τ,(31) where psc and qsc denote the active and reactive power at the sending end when pr=qr=0. The maximum error of the above approximations for the heterogeneous set of lines included in Table 1is less than 1.5 %, except for the UHV long line O8, which is 4 %. Figure 9shows the curves of isc versus τfor different values of κ. The isc values for the lines of Table 1are shown as filled circles. In the same figure, the values of the current ismax, corresponding to the maximum load prn for each line in Table 1, are also depicted as empty circles. The figure clearly shows a higher dependency of isc on τthan on κ(the curves are quite close to each other). In fact, all the points corresponding to the lines of Table 1lie virtually on the curve for κ=0. The figure is also interesting to ascertain at a glance the relative importance of the no-load current over the maximum current, by comparing each filled circle with the empty one located right above. For the cases of Table 1, some lines like U3 or O8 have a significant no-load current that must be assessed and ultimately compensated, as it is well known. 40616 VOLUME 10, 2022 P. Cruz-Romero et al.: Characterizing Steady-State Performance of AC Lines FIGURE 8. Curves pr0versus τfor vr=0.95 pu and different values of κ, along with values of pr0and prn for the cases of Table 1(whenever pr0exists). FIGURE 9. Curves of charging current isc versus τfor different values of κ. For underground and GIL cases, the expression for isc can be further simplified by noting that τ≈0: isc ≈2τ√1+κ2−τ √1+κ2−2τ≈2τ , (32) The validity of this approximation can be checked in Figure 9, where the linear function isc =2τis also represented. F. FERRANTI EFFECT Under the same no-load conditions of the previous section (pr=qr=0), taking into account that τ2, the voltage at the receiving end can be obtained from vrc =√1+κ2 √1+κ2−2τ+τ2>1,(33) FIGURE 10. Voltage at the open receiving end for different values of κ. The circles correspond to the values of Table 1. which reflects the well-known Ferranti effect (open-circuit receiving end voltage always higher than the sending end VOLUME 10, 2022 40617