HVDC grids stability enhancement through the integration of battery energy storage systems

Azizi, Neda; Moradi, Hassan; Rouzbehi, Kumars; Mohammadi, Fazel

Abstract

In high voltage direct current (HVDC) grids, the reference values of power controllers are normally adjusted based on the DC-link voltage as the DC voltage is regulated by the droop controllers. As a matter of fact, except for the DC slack bus, there is a trade-off between power-sharing and voltage regulation of all the remaining HVDC buses. The main issue with this control strategy is that in case of contingencies, significant voltage and power oscillations throughout HVDC grids can be expected. To address such issues, the integration of a battery energy storage system into HVDC grids through a multi-port DC/DC power converter is investigated in this paper. The DC/DC converter used in this paper consists of three ports: (1) two ports are connected in cascade with the intended DC transmission line, formerly named cascaded power flow controller, and (2) the third port is for the integration of the battery energy storage system to form a multi-functional device. Therefore, the proposed framework can potentially achieve small-signal stability enhancement and regulate/adjust the power throughout the HVDC grids.

Full text

Received: 6 January 2023 Revised: 24 May 2023 Accepted: 19 June 2023 IET Renewable Power Generation DOI: 10.1049/rpg2.12788 ORIGINAL RESEARCH HVDC grids stability enhancement through the integration of battery energy storage systems Neda Azizi1Hassan Moradi1Kumars Rouzbehi2Fazel Mohammadi3,4 1Department of Electrical Engineering, Razi University, Kermanshah, Iran 2Department of System Engineering and Automatic Control, University of Seville, Seville, Spain 3Department of Electrical and Computer Engineering, University of Windsor, Windsor, Ontario, Canada 4Electrical and Computer Engineering and Computer Science Department, University of New Haven, West Haven, Connecticut, USA Correspondence Hassan Moradi, Department of Electrical Engineering, Razi University, Kermanshah, Iran. Email: [email protected].ir Abstract In high voltage direct current (HVDC) grids, the reference values of power controllers are normally adjusted based on the DC-link voltage as the DC voltage is regulated by the droop controllers. As a matter of fact, except for the DC slack bus, there is a trade-off between power-sharing and voltage regulation of all the remaining HVDC buses. The main issue with this control strategy is that in case of contingencies, significant voltage and power oscillations throughout HVDC grids can be expected. To address such issues, the integration of a battery energy storage system into HVDC grids through a multi-port DC/DC power converter is investigated in this paper. The DC/DC converter used in this paper consists of three ports: (1) two ports are connected in cascade with the intended DC transmission line, formerly named cascaded power flow controller, and (2) the third port is for the integration of the battery energy storage system to form a multi-functional device. Therefore, the proposed framework can potentially achieve small-signal stability enhancement and regulate/adjust the power throughout the HVDC grids. 1 INTRODUCTION Nowadays, due to the growth in using renewable energy sources, especially offshore wind power, and the need for coordinating and integrating them into power systems, the tendency to use high voltage direct current (HVDC) grids is increasing [1]. In conventional AC power systems, reactive power regulations can be used to minimize power transmission losses. However, in all hybrid AC/DC grids, power transmission losses can be optimized by regulating the active power exchange among AC and DC sides [2]. In addition, in HVDC grids, there is a trade-off between DC voltage and power, which leads to the fact that the DC voltage deviations after any disturbances also affect the operation of hybrid AC/DC grids [2]. Therefore, one of the key challenges for the safe and secure operation of large-scale hybrid AC/DC power systems is DC voltage oscillations [3, 4]. In ref. [2], an optimization algorithm is proposed to minimize power losses and reduce DC voltage deviation when the operating condition change in hybrid AC/DC modular multilevel converters (MMCs)-based system. In the proposed method in ref. [2], the total number of iterations has been This is an open access article under the terms of the Creative Commons Attribution-NonCommercial-NoDerivs License, which permits use and distribution in any medium, provided the original work is properly cited, the use is non-commercial and no modifications or adaptations are made. © 2023 The Authors. IET Renewable Power Generation published by John Wiley & Sons Ltd on behalf of The Institution of Engineering and Technology. reduced and the power flow of AC grids has been excluded from the iterative solution. In ref. [5], a method to estimate the average voltage of power converter stations is proposed. This method is based on a distributed observer, and the need for global information in the centralized secondary control methods is eliminated. Moreover, a combined control structure that contains two control schemes, i.e. autonomous control and hierarchical control, to deal with contingencies in HVDC grids is proposed in ref. [6]. Since using a power system stabilizer (PSS) is a common method for enhancing oscillation damping in AC power systems, employing the DC power system stabilizer (DC-PSS) leads to voltage oscillations damping in HVDC grids [7]. However, DC-PSS cannot solve the issues related to inertia and all lowfrequency oscillations. It is also worth noting that DC-PSS uses power signal oscillation to improve voltage fluctuations damping. Also, due to the presence of the droop controller in the HVDC grids, the use of the power signal fluctuations to improve the damping of the voltage signal fluctuations, in turn, causes increased power signal fluctuations [8]. Apart from DC- PSSs, active power modulation is used in ref. [9] to provide IET Renew. Power Gener. 2023;1–16. wileyonlinelibrary.com/iet-rpg 1 2AZIZI ET AL. a solution for inter-area oscillations damping of an idealized two-machine HVDC system. A synchronized method in HVDC combined with offshore wind farms that can deliver more artificial inertia is presented in ref. [10]. Implementation of inertia emulation for HVDC systems using the stored energy in the capacitors of DC-link of HVDC networks is presented in ref. [11]. It has been shown in ref. [12] that HVDC systems can improve power transmission capacity and provide greater security in low wind conditions. Distributed dynamic controllers are introduced in ref. [13] for both frequency containment and restoration reserves of asynchronous AC systems connected by a multi-terminal HVDC system. In addition, in this control strategy, by minimizing the quadratic cost functions of voltage deviation and power generation, the performance of HVDC systems is optimized. The concept of a flexible DC transmission system (FACTS) that provides voltage regulation, load flow control, and power control is introduced in refs. [14]and[15]. To identify and control the voltage of DC/DC power converters, a data-driven-based voltage control strategy is developed [16]. The advantage of the strategy presented in ref. [16]isthat this method only requires the data of power converters, including the duty cycles and the output voltage, to find a dynamic model and does not need a predefined standard model of power converters. Having thoroughly checked the presented methods in the literature, it is evident that such methods can rarely simultaneously damp the DC voltage and power oscillations. Therefore, this paper proposes a method inspired by the use of energy storage systems (ESSs) in AC systems to control the DC voltage, DC power, and damping oscillations. The proposed method assists in reducing such fluctuations by injecting additional power via an ESS connected by a triple active bridge (TAB) DC/DC power converter. Furthermore, using this converter in the cascade connection of the DC transmission line, it is also possible to control the power flow to form a multi-functional device [17]. The proposed control strategy is capable of improving the overall stability of the DC voltage and DC power in HVDC grids, especially in the presence of faults and disturbances, which have major impacts on the operation of power systems in the stable condition and lead to the damping of low-frequency oscillations. There are various types of storage systems, among which batteries are of great interest due to their advantages, such as controllability, and geographical independence [18]. The major characteristics of a battery energy storage system (BESS), such as its flexibility and expected cost reduction, have led this type of ESS to be widely developed in electric power systems [19, 20]. In addition to addressing issues, such as power quality, batteries are also used to solve energy management problems [21]. A review of research studies shows that until 2018, a total of 125,000 home energy storage systems with a battery power of about 415 MW and a capacity of 930 MWh have been installed [22]. It should be noted that BESS can also be used together with supercapacitors as a hybrid energy storage system (HESS). In such systems, the control strategy shares the current between the battery and the capacitor [23]. Also, different topologies for power converters have been presented in the literature [24, 25], and some of them are based on multi-port topologies for connecting to any number of DC transmission lines [26–28]. In ref. [24], a control method is presented in which DC/DC power converters have been used to reach the flexible power flow control in multi-terminal HVDC grids. The power flow management through a different connection structure of a power converter is investigated in ref. [25]. This structure is named a serial-parallel DC power flow controller. The input signal of this structure is the DC transmission line voltage, and the output signal of the configuration is DC transmission line current [25]. A multi-port power converter technology as a solution for connecting different sources, such as wind turbines, fuel cells, photovoltaic, and energy storage, at different voltage levels with bidirectional power flow capability and centralized control has been investigated [29]. Due to advantages, such as isolation, bidirectional power flow control, a wider soft-switching range, and higher resource utilization, one of the most common choices among topologies available for isolated multi-port power converters is dual active bridge (DAB) [30]. In addition, the TAB-based power converter topology has been of interest for multi-port power converters [31]. However, in this paper, the topology of the TAB multi-port DC/DC power converter is used. It should be noted that the proposed method in this paper is a multi-functional device for the integration of the BESS, and it can enhance the small-signal stability and regulate/adjust the power of DC grids. Considering the power flow throughout the system, the power of the battery in this paper is considered in such a way that the BESS is capable of providing the required power when necessary and according to the power flow and the supervisory control command. Therefore, it is not possible to consume all this power to improve transient stability. Time-domain simulations and system analysis show that the proposed method provides a decent damping improvement as well as power flow control functionality to the system. All analytical studies and simulations have been conducted on the CIGRÉ HVDC test system in MATLAB/Simulink environment. In summary, the main contributions of this paper are as follows: ∙This paper presents a method for damping DC voltage and power oscillations and provides the required power throughout HVDC grids by considering a trade-off between DC voltage and power of all the remaining DC buses. ∙In this paper, a multi-functional device for the integration of the BESS is proposed. ∙Integration of a BESS into HVDC grids through a multi-port DC/DC power converter is investigated. ∙The proposed method simultaneously improves the smallsignal stability and regulates/adjusts the power of the intended HVDC line. The rest of this paper is structured as follows. The proposed configuration is presented in Section 2. The understudy HVDC grid is given in Section 3. Analysis and results are reported in Section 4. The conclusions are discussed in Section 5. 17521424, 0, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/rpg2.12788 by Universidad De Sevilla, Wiley Online Library on [25/08/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License AZIZI ET AL.3 FIGURE 1 Multi-port DC/DC connection configuration 2PROPOSED CONFIGURATION As it is shown in Figure 1, the multi-port DC/DC power converter should be installed on the associated DC transmission line. The existence of this device as a compensating BESS has the potential to take over power regulation in the corresponding line. 2.1 State-space model The proposed TAB multi-port converter is a nonlinear multiinput and multi-output system [32]. The state-space model of such a system is written by considering the average switching cycle of battery current (ib), grid current il,and the voltage of clamp capacitors vc1,vc2,andvc0 as state variables. The equations are given in terms of state variables listed in Equations (1)to(5). L1 2 d dt ib=Lbd dtib=vb−(1 −db)vc1 (1) L2 2 d dtil=Lld dtil=v1−(1 −dl)vc2 (2) C1vc1 d dt vc1 =2(1 −db)vc1il1 −p1(3) C2vc2 d dtvc2 =2(1 −dl)vc2il2 −p2(4) C0vc0 d dtvc0 =p0−v2 c0 R0(5) That here: ib=2il1,il=2il2,Lb=L1 2,Ll=L2 2(6) where iband ilare the total currents of the battery and grid. Also, il1 and il2 represent the average value of the switching cycle of the inductor currents of port-1 and port-2. Furthermore, the average switching cycle powers output from the two input ports to the output are denoted by p1,p2,andp0. It should be noted that the duty ratio of the battery is shown by dband the duty ratio of the grid is shown by dl. In the next step, the equations become linear around a point value, as follows: pi|(i=0,1,2) =pi+Δpi(7) Δpi|(i=0,1,2) =𝜕 𝜕db Δdb+𝜕 𝜕dl Δdl+𝜕 𝜕d1 Δd1 +𝜕 𝜕d2 Δd2+ 2 ∑ j=0 𝜕 𝜕vcj Δvcj(8) where, ib,il,vc0,vc1,andvc2 are the system state variables, db,dl, d1,andd2are the control variables, and v1and vbare the internal variables. Finally, if the DC and nonlinear terms not be considered, the small-signal equations for the converter are written as follows: L1 2 d dtΔib=Δib−(1 −Db)Δvc1 +vc1Δdb(9) L2 2 d dtΔil=Δv1−(1 −Dl)Δil+vc2Δdl(10) C1d dtΔvc1 =(1 −Db)Δib−ΔdbIb−Δic1 (11) C2d dtΔvc2 =(1 −Dl)Δil−ΔdlIl−Δic2 (12) Also, Δic1|(j=0,1,2) =Δpi vci (13) Generally, there are two control objectives for the proposed multi-port converter. ∙DC-link voltage control (vc0) under all operating conditions ∙Matching the transformer voltage to the duty ratio of the input bridges control According to the proposed control objectives, the proposed display of state space is written as Equations (14)and(15). Δ X=AΔX+BΔUc+EΔU0(14) ΔY=CΔX+DΔUc+FΔUD(15) where ΔX=[ΔibΔvc1 Δvc2 Δvc0 ]T(16) ΔY=[Δvc0] (17) ΔUc=[ΔdbΔd1Δd2]T(18) ΔUD=[Δvb] (19) A=⎡⎢⎢⎢⎢⎢⎣ 2∕L12∕L1(1 −Db)0 0 01∕C1(1 −Db)0 0 001∕C2(1 −Dl)0 00 01∕(C0R0) ⎤⎥⎥⎥⎥⎥⎦ (20) 17521424, 0, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/rpg2.12788 by Universidad De Sevilla, Wiley Online Library on [25/08/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License 4AZIZI ET AL. FIGURE 2 Small-signal modelling for (a) port-1, (b) secondary referred of port-1, (c) port-0 (d) small signal modelling for all three ports B=⎡⎢⎢⎢⎣ (2∕L1)VC100 0(−1∕C1)Ib0 00(1∕C2)Il ⎤⎥⎥⎥⎦ (21) E=⎡⎢⎢⎢⎢⎢⎣ 0 −1∕C1 −1∕C2 1∕C0P0 ⎤⎥⎥⎥⎥⎥⎦ (22) C=[0001 ](23) D=[0](24) F=[0](25) where, state vector, output vector input vector, and disturbance input vector are shown by ΔX,ΔY,ΔUc,andΔUD, respectively. According to Equations (1)–(25), the state-space small-signal average equivalent model of the proposed multi-port power converter is shown in Figure 2. Since both grid input ports are the same, only port-1 modelling is described in detail in Figure 2. 2.2 Proposed topology The topology of the TAB multi-port DC/DC power converter, as the proposed structure in single-phase, has been illustrated in Figure 3. The structure of the DC/DC power converter has three ports. The first and the third port are connected in cascade with the intended DC transmission line, and the second port is used to integrate the BESS into the HVDC grid. In order to connect the BESS through conventional DC/DC converters, it is necessary to consider a high conversion ratio for power converters. Using such a converter requires high capital costs. However, by using a multi-port power converter, problems related to the high conversion ratio can be addressed. This can be done by setting different ports for the integration of the BESS; thus, enhancing the small-signal stability, and regulating/adjusting the power of the intended HVDC line. The main core in this structure is a TAB DC/DC power converter with magnetic insulation between the voltage sides [25]. 17521424, 0, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/rpg2.12788 by Universidad De Sevilla, Wiley Online Library on [25/08/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License AZIZI ET AL.5 FIGURE 3 Proposed structure for the power converter The TAB DC/DC power converter consists of HVDC cascaded-connected series formed multi-modular power converters. In this structure, high-frequency transformers form a galvanic isolation stage to couple the low-voltage/high-current energy sources and high-voltage DC links. There is also an additional port for the BESS in the proposed structure. This configuration is formed based on the MMC with a half-bridge structure with nmodules connected in series and an inductor. The isolation stage in Figure 3consists of several full bridges. Some of the full bridges are used to share a common DC-link, which is connected in series to the positive terminal of the HVDC link, and the other full bridge is used in the same way for the negative terminal. However, MMCs can have other topologies to improve controllability under fault conditions. The number of sub-modules is calculated based on the HVDC line voltage, and the number of full bridges is calculated based on the current level. 2.3 An average model for TAB DC/DC power converter As mentioned earlier, one of the most critical factors for static and dynamic analyses of the system is the proper modelling of the converter. In this regard, an average model for the TAB multi-port DC/DC power converter is developed in this paper, and it is shown in Figure 4[24]. FIGURE 4 Average equivalent model of TAB multi-port DC/DC power converter 2.4 Local controller of the designed configuration The local controller of the proposed structure is demonstrated in Figure 4. In this configuration, the output signal of the voltage droop controller is added to the Pref to provide the reference power Prbased on the changes in the voltage measured among both sides of the power converter. In the control structure, vector control provides the correct reference signals for the internal controllers [33]. The secondary control layer is designed in such a way as to act as a supervisory controller and sends proper control signals to the local controllers based on the power flow of the system. However, the BESS controller is designed in such a way that the change in nb, and then, the amount of injected power by BESS, can be controlled by the power flow. 2.5 Cascade power flow controller As shown in Figure 4, the average model of the TAB DC/DC converter on the DC line side consists of a current source controlled by the equation Ip=ncIk, which is modelled in parallel with the DC-link capacitor (Cp). In addition, there is a controlled voltage source with the equation Vk=ncVibefore an inductor (Ls). This model mainly is known as a cascaded power flow controller (CPFC) [24]. To improve the transient state, the outer loop of the TAB DC/DC converter is also used to determine the local reference power values. The conversion ratio nc is expressed as: nc=Vk Vi(26) where, the steady-state DC voltage are shown by Vkand Vi, respectively. In the design process of the TAB DC/DC converter local controller, it is also considered that by choosing the appropriate conversion ratio (nc), the desired power flow can be achieved in the DC transmission line. 17521424, 0, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/rpg2.12788 by Universidad De Sevilla, Wiley Online Library on [25/08/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License 6AZIZI ET AL. The structure of the TAB DC/DC converter shows that if the transmission ratio is considered equal to unity, the multiport DC/DC converter does not involve in the power flow control process, but if this ratio is considered to be a numerical value other than unity, the proposed power converter can also act as a power flow controller. Each of these control modes can be selected by sending the smsignal. In the structure shown in Figure 4,PCPFC,r is the reference power defined by the differential voltage droop controller, and mis the droop coefficient. In this structure, the droop coefficient is mCPFC and its input signal is Vik =Vi−Vk. In the TAB DC/DC converter control structure, there are two inner and outer control loops. The reference current of the internal control loop is provided through the PI power controller. Furthermore, nc,ff is used as the feedforward ratio to increase the control dynamic response of the TAB DC/DC converter, and the switching delay is indicated by e−sTsw . 2.6 Battery energy storage system A “controlled current source” (Ip=nbIk) connected to the BESS, as a second port, is demonstrated in Figure 4.The conversion ratio nbof the energy storage port is defined as: nb=Vk Vb(27) where Vbis the voltage of the BESS. As shown in Equation (27), by changing the conversion ratio, the DC/DC converter can change the battery charge condition. Also, as shown in Figure 4and Equation (27), by changing Vk,nbchanges, and then, the battery controller comes into action and uses the battery power to perform network oscillation damping. If a fault within the grid occurs, BESS has the role of a stabilizer, but when power flow control is required, it acts as a series voltage source in the DC transmission line and controls the power flow. In fact, the parameter “nb” is a conversion ratio by which a proper signal can be sent to the controller of the port, including the BESS. This conversion ratio shows that if Vkis less than Vb, the excess power flows from the BESS to the main HVDC grid, and if Vkis greater than Vb, the excess power can be used to charge the BESS. However, due to the existing trade-off between DC voltage and power in HVDC grids, which is controlled by the droop controllers, injecting power into the main HVDC grid or transferring power from the main HVDC grid can lead to disruption of power-sharing in the network. Therefore, the power injected into the main HVDC grid or the power transferred from the main HVDC grid is adjusted according to the power-sharing program in the steady-state conditions by setting the nbff. That is, when the goal is to improve small-signal stability, without any change in power flow, nc=1 and nbis changing. However, when the objective is to control power flow, nband nccan change. Considering that in steady-state analysis, the impact of the capacitor and inductor can be ignored, the previous equation is FIGURE 5 SoC controller shown as follows: ⎡⎢⎢⎢⎣ Vk Ii Ib ⎤⎥⎥⎥⎦ =⎡⎢⎢⎢⎣ nc−Rs 0nc 0nb ⎤⎥⎥⎥⎦[Vi Ik](28) In dynamic studies, it is possible to use the frequency domain representation: ⎡⎢⎢⎢⎣ Vk Ii Ib ⎤⎥⎥⎥⎦ =⎡⎢⎢⎢⎣ nc−(Rs+sLs sCpnc 0nb ⎤⎥⎥⎥⎦[Vi(s) Ik(s)](29) The first block of the charge controller is the state of charge (SoC) controller, which defines the conditions for charging/discharging of the battery, as shown in Figure 5. In Figure 5 structure Ibis the current of the battery, Vb,ref is the reference voltage of the battery, and KSoC is the gain for energy integration. It is worth mentioning that in this control structure for the battery SoC, the reference of the voltage of the battery Vb,ref is determined using the supervisory control, and then, Vb,in is compared with the measured voltage Vi,meas in the next control loop. Moreover, as it is shown in Figure 4, under various conditions, the control signal sncan be used to select each mode using the supervisory control. If sn=0, the BESS only is used for damping the existing oscillations and if sn=1, the BESS can help to control the power flow. Also, if the SoC is greater than or equal to the minimum SoC level, the battery can inject active power to match the safe depth- of-discharge of the battery, and if the SoC of the battery is less than the maximum SoC limit, the battery can be charged. In this regard, the maximum and minimum values of SoC have been chosen as 100% and 20%, respectively [34]. SoC limits the contribution of the battery to power flow regulation. As a result, the voltage reference is executed according to the specified conditions as follows [35, 36]: Vb,in ={Vb,ref,SoCmin ≤SoC ≤SoCmax 0 Otherwise (30) Usually, the battery voltage is kept within its safety limits using protection devices. However, the use of a bidirectional charge controller provides the charging conditions in such a way that the overcharging of the battery is prevented by adjusting the current flow [37]. The charge controller is shown in Figure 6. In a transient state, by comparing the DC voltage (Vi,meas) with a reference voltage (Vb,in), the error signal can be 17521424, 0, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/rpg2.12788 by Universidad De Sevilla, Wiley Online Library on [25/08/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License AZIZI ET AL.7 FIGURE 6 The charge controller calculated. Then, by using a PI controller, the value for the charge/discharge current (Ib) can be determined. In this regard, if Ib>0, the battery can be charged, and when Ib<0, the battery can be discharged. As it is presented in Figure 6,the input signal has been used to control the difference between the DC voltage and the reference DC voltage. Placing the washout filter in the controller structure ensures that the battery power does not interfere with power-sharing. A classic washout filter consists of two high-pass and low-pass filters for linear and rotational motions. The parameters of these filters are fixed, and in this paper, Twhas been determined using the genetic algorithm (GA), particle swarm optimization (PSO) algorithm, and the Ziegler—Nichols method. Due to the trade-off between the DC voltage and power, in the transient condition, the power required by the main HVDC grid for damping fluctuations is provided using BESS. However, the injection of this power into the main HVDC grid in steady-state conditions leads to the disruption of the power balance. The existence of the washout filter in the control scheme makes it possible to eliminate the impact of excess power of the BESS in the steady-state and only use the battery power in the transient state. Without using the washout filter, the excess power of the battery can affect the balance of the power and power-sharing. Thus, the balance of the voltage of different buses can be destroyed. In this technique, additional power is provided by a BESS to improve the system stability and eliminate oscillations in the voltage and power of HVDC grids. Also, if it is necessary, a control signal (nb,ff) through the supervisory control can change the nb. The parameters of controllers are tuned using the Ziegler— Nichols method [38]. Also, the GA and the PSO algorithm are used for tuning the parameters [39] and they are compared with the Ziegler—Nichols method. The PSO algorithm and the GA algorithm first start by selecting a random population, and then, search for the global optimal solution by continuously updating the population. The purpose of the optimization of parameters is to minimize the objective function in Equation (31)[39]. The optimization process is such that after selecting parameters in the population, then the simulation file of the under-study test HVDC grid can be run following a three-phase fault at the Ba- A0 location with a duration of 150 ms. In each iteration, the objective function in Equation (31) is calculated. This step is executed with 120 iterations. Finally, the optimal parameters can be calculated using Equation (31)[39]. Error = n ∑ b=1(∫t 0 t(|ΔVdcb|+|ΔPb|)dt)(31) The tuned parameters of controllers are shown in Table 1. The linearized closed-loop small-signal model of this system is shown in Figure 7for investigation of the proposed control method. In Figure 7, the dynamic behaviour of the BESS is shown by the low-pass filter [40], where Tb, as the time constant of the BESS, is 0.25 s. In this model, mis the voltage droop coefficient. Additionally, a second-order Pade approximation of the switching delay has been used to show the modelling of the delay due to the pulse width modulation. It should be noted that the current PI controller coefficients are shown by ki,p,andki,i,andLsand Rs are the inductance and resistance behind the power converter model, respectively. The Bode diagrams of the closed-loop model according to Figure 7with BESS and without BESS are plotted in Figure 8. Figure 8is obtained according to the data provided in ref. [24]. As is shown in Figure 8, the controller can operate in a wide frequency range. Figure 8shows, the system at frequencies below 2 Hz has an equal gain margin in the cases with and without BESS. It can also be seen that the system at frequencies below 6 Hz has an equal phase margin in the cases with and without BESS. However, in higher frequencies (>10 Hz up to 1000 Hz), the BESS can add about 87 dB of gain margin and 160 degrees of phase margin to the system. The Bode diagram of the closed-loop model using various parameters of the controller (kp1 =0.25 to 0.45, ki1 =5to7, TW=0.25 to 0.26) is shown in Figure 9.Asitisshownin Figure 9by increasing the system’s parameters, the frequencies 2 and 6 Hz are increased. The delay impact is shown in Figure 10.Asitisshownin Figure 10, a delay of 10 ms has been applied to thesystem, which does not have much impact on the Bode diagram of the system. 3UNDERSTUDY TEST HVDC GRID Figure 11 shows the general configuration of the understudy HVDC grid. This HVDC grid is inspired by CIGRÉ DCS3 in this paper. The CIGRÉ test network, which was developed and introduced by the CIGRÉ B4 working group as a benchmark test grid, is usually utilized to study and analyze DC grids [41]. The introduced CIGRÉ B4 DC test network consists of four offshore AC systems, two DC nodes without connection to any AC system, two onshore systems, and three DC systems named DCS1, DCS2, and DCS3. In this paper, DCS3 is considered as the grid consisting of 4 AC areas that are related through a 5-terminal bipolar power converter station [41]. Also, it is assumed that the rated power is 1000 MW and the rated voltage of each power converter is ±400 kV. In the test grid, as illustrated in Figure 11, “Ba”s are onshore AC busses, “B0”s are offshore AC busses, DC busses, AC/DC converter stations, and DC/DC converter stations are shown by “Bb”, “Cb”, and “Cd”, respectively. Also, the AC system, which is named Ba comprises two busses, Ba-B1 and Ba-B2. Ba-B1 is connected to the Cb-B1 as the AC/DC converter and Ba-B2 is connected to the Cb-B2 as the AC/DC converter. Also, AC systems D and C are offshore wind power plants. In Figure 11 two VSCs are connected to B0-C2 and B0-D1 as offshore AC buses, while 17521424, 0, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/rpg2.12788 by Universidad De Sevilla, Wiley Online Library on [25/08/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License 8AZIZI ET AL. FIGURE 7 Small-signal modelling of the proposed method FIGURE 8 The Bode diagram of the close-loop model FIGURE 9 Bode diagram of the close-loop model following various parameters FIGURE 10 The Bode diagram of the closed-loop model with and without delay FIGURE 11 The under-study HVDC grids the other three VSCs are operated as interfaces among DC grids and onshore AC buses consisting of Ba-B1, Ba-A1, and Ba-B2. It means that these power converters are connected to the grid. In DCS3, offshore systems are considered constant power resources. Ba-B1 and Ba-B2, which are stiff AC buses, 17521424, 0, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/rpg2.12788 by Universidad De Sevilla, Wiley Online Library on [25/08/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License AZIZI ET AL.15 5CONCLUSIONS In this paper, the use of a multi-port DC/DC power converterbased BESS, as a multi-functional device, in improving the transient stability and enhancing the power transmission capacity of HVDC grids is proposed. The proposed control structure in this paper is an effective control framework that deals with multi-port DC/DC power converters to achieve DC voltage control and eliminate voltage and power oscillations. Also, the control scheme of the DC/DC converter can control the power flow in the intended transmission line. Analysis and time-domain simulations of the system demonstrate that the proposed method has given the system an appropriate and acceptable damping improvement. The presented method in this paper simultaneously improves the transient stability of DC voltage and control power oscillation damping within HVDC grids using BESS. CONFLICT OF INTEREST The authors declare no conflict of interest. DATA AVAILABILITY STATEMENT Data sharing not applicable to this article as no datasets were generated or analysed during the current study ORCID Hassan Moradi https://orcid.org/0000-0002-4802-6117 Kumars Rouzbehi https://orcid.org/0000-0002-3623-4840 Fazel Mohammadi https://orcid.org/0000-0002-9811-350X REFERENCES 1. Raza, A., et al.: Power dispatch and voltage control in multiterminal HVDC systems: a flexible approach. IEEE Access 5, 24608–24616 (2017) 2. Zhang, Y., Meng, X., Shotorbani, A.M., Wang, L.: Minimization of ACDC grid transmission loss and DC voltage deviation using adaptive droop control and improved AC-DC power flow algorithm. IEEE Trans. Power Syst. 36(1), 744–756 (2020) 3. Rodriguez, P., Rouzbehi, K.: Multi-terminal DC grids: challenges and prospects. J. Mod. Power Syst. Clean Energy 5(4), 515–523 (2017) 4. Mohammadi, F.: Network expansion planning of multi-carrier energy systems. In: Planning and Operation of Multi-Carrier Energy Networks, pp. 339–360. Springer, Cham (2021) 5. Zhang, Y., Shotorbani, A.M., Wang, L., Li, W.: Distributed voltage regulation and automatic power sharing in multi-terminal HVDC grids. IEEE Trans. Power Syst. 35(5), 3739–3752 (2020) 6. Zhang, Y., Shotorbani, A.M., Wang, L., Li, W.: A combined hierarchical and autonomous DC grid control for proportional power sharing with minimized voltage variation and transmission loss. IEEE Trans. Power Delivery 37(4), 3213–3224 (2021) 7. Azizi, N., Moradi Cheshmeh Beigi, H., Rouzbehi, K.: HVDC grids stability improvement by direct current power system stabilizer. IET Gener. Transm. Distrib. (2021) 8. Zafari, A., Mehrasa, M., Rouzbehi, K., Sadabadi, M.S., Bacha, S., Hably, A.: DC-link voltage stability-based control strategy for grid-connected hybrid AC/DC microgrid. In: 2020 2nd Global Power, Energy and Communication Conference (GPECOM), pp. 268–273. IEEE, Piscataway, NJ (2020) 9. Harnefors, L., Johansson, N., Zhang, L., Berggren, B.: Interarea oscillation damping using active-power modulation of multiterminal HVDC transmissions. IEEE Trans. Power Syst. 29(5), 2529–2538 (2014) 10. Liu, X., Lindemann, A.: Coordinated control of VSC-HVDC connected offshore windfarms for enhanced ability of providing synthetic inertia. In: 2015 IEEE 6th International Symposium on Power Electronics for Distributed Generation Systems (PEDG), pp. 1–6. IEEE, Piscataway, NJ (2015) 11. Chamorro, H.R., Sevilla, F.R.S., Gonzalez-Longatt, F., Rouzbehi, K., Chavez, H., Sood, V.K.: Innovative primary frequency control in lowinertia power systems based on wide-area RoCoF sharing. IET Energy Syst. Integration 2(2), 151–160 (2020) 12. Rakhshani, E., Mehrjerdi, H., Al-Emadi, N.A., Rouzbehi, K.: On sizing the required energy of HVDC based inertia emulation for frequency control. In: 2017 IEEE Power & Energy Society General Meeting, pp. 1–5. IEEE, Piscataway, NJ (2017) 13. Andreasson, M., Wiget, R., Dimarogonas, D.V., Johansson, K.H., Andersson, G.: Distributed frequency control through MTDC transmission systems. IEEE Trans. Power Syst. 32(1), 250–260 (2016) 14. Rouzbehi, K., Miranian, A., Luna, A., Rodriguez, P.: Towards fully controllable multi-terminal DC grids using flexible DC transmission systems. In: 2014 IEEE Energy Conversion Congress and Exposition (ECCE),pp. 5312–5316. IEEE, Piscataway, NJ (2014) 15. Rouzbehi, K., Miranian, A., Candela, J.I., Luna, A., Rodriguez, P.: Proposals for flexible operation of multi-terminal DC grids: Introducing flexible DC transmission system (FDCTS). In: 2014 International Conference on Renewable Energy Research and Application (ICRERA), pp. 180–184. IEEE, Piscataway, NJ (2014) 16. Rouzbehi, K., Miranian, A., Escaño, J.M., Rakhshani, E., Shariati, N., Pouresmaeil, E.: A data-driven based voltage control strategy for DC-DC converters: application to DC microgrid. Electronics 8(5), 493 (2019) 17. Mohammadi, F., Nazri, G.-A., Saif, M.: An improved mixed AC/DC power flow algorithm in hybrid AC/DC grids with MT-HVDC systems. Appl. Sci. 10(1), 297 (2019) 18. Yang, Y., Bremner, S., Menictas, C., Kay, M.: Battery energy storage system size determination in renewable energy systems: a review. Renewable Sustainable Energy Rev. 91, 109–125 (2018) 19. Shahnazian, F., et al.: Control of MMC-based STATCOM as an effective interface between energy sources and the power grid. Electronics 8(11), 1264 (2019) 20. Zubi, G., Dufo-López, R., Carvalho, M., Pasaoglu, G.: The lithium-ion battery: State of the art and future perspectives. Renewable Sustainable Energy Rev. 89, 292–308 (2018) 21. Divya, K., Østergaard, J.: Battery energy storage technology for power systems—an overview. Electr. Power Syst. Res. 79(4), 511–520 (2009) 22. Figgener, J., et al.: The development of stationary battery storage systems in Germany–a market review. J. Energy Storage 29, 101153 (2020) 23. Shen, J., Khaligh, A.: Design and real-time controller implementation for a battery-ultracapacitor hybrid energy storage system. IEEE Trans. Ind. Inf. 12(5), 1910–1918 (2016) 24. Rouzbehi, K., Candela, J.I., Luna, A., Gharehpetian, G.B., Rodriguez, P.: Flexible control of power flow in multiterminal DC grids using DC–DC converter. IEEE J. Emerg. Sel. Top. Power Electron. 4(3), 1135–1144 (2016) 25. Rouzbehi, K., Yazdi, S.S.H., Moghadam, N.S.: Power flow control in multiterminal HVDC grids using a serial-parallel DC power flow controller. IEEE Access 6, 56934–56944 (2018) 26. Yazdi, S.S.H., Rouzbehi, K., Carrizosa, M.J., Heidary, A., Bagheri, M.: Modeling, control, and operation of an M-DAB DC–DC converter for interconnection of HVDC grids. IEEE Syst. J. 17, 2652–2663 (2023) 27. Abbasipour, M., Milimonfared, J., Yazdi, S.S.H., Rouzbehi, K.: Static modeling of the IDC-PFC to solve DC power flow equations of MT-HVDC grids employing the Newton-Raphson method. In: 2019 10th International Power Electronics, Drive Systems and Technologies Conference (PEDSTC),pp. 450–457. IEEE, Piscataway, NJ (2019) 28. Rouzbehi, K., Miranian, A., Candela, J.I., Luna, A., Rodriguez, P.: A hybrid power flow controller for flexible operation of multi-terminal DC grids. In: 2014 International Conference on Renewable Energy Research and Application (ICRERA), pp. 550–555. IEEE, Piscataway, NJ (2014) 29. Tao, H., Kotsopoulos, A., Duarte, J.L., Hendrix, M.A.: Family of multiport bidirectional DC–DC converters. IEE Proc. Electr. Power Appl. 153(3), 451–458 (2006) 17521424, 0, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/rpg2.12788 by Universidad De Sevilla, Wiley Online Library on [25/08/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License 16 AZIZI ET AL. 30. Sha, D., Wang, X., Chen, D.: High-efficiency current-fed dual active bridge DC–DC converter with ZVS achievement throughout full range of load using optimized switching patterns. IEEE Trans. Power Electron. 33(2), 1347–1357 (2017) 31. Zhang, N., Sutanto, D., Muttaqi, K.M.: A review of topologies of threeport DC–DC converters for the integration of renewable energy and energy storage system. Renewable Sustainable Energy Rev. 56, 388–401 (2016) 32. Biswas, I., Kastha, D., Bajpai, P.: Small signal modeling and decoupled controller design for a triple active bridge multiport DC–DC converter. IEEE Trans. Power Electron. 36(2), 1856–1869 (2020) 33. Mohammadi, F., et al.: Robust control strategies for microgrids: a review. IEEE Syst. J. 16(2), 2401–2412 (2022) 34. Datta, U., Kalam, A., Shi, J.: Battery energy storage system to stabilize transient voltage and frequency and enhance power export capability. IEEE Trans. Power Syst. 34(3), 1845–1857 (2018) 35. Mohammadi, F.: Lithium-ion battery state-of-charge estimation based on an improved Coulomb-counting algorithm and uncertainty evaluation. J. Energy Storage 48, 104061 (2022) 36. Mohammadi, F., Sanjari, M., Saif, M.: A real-time blockchain-based state estimation system for battery energy storage systems. In: 2022 IEEE Kansas Power and Energy Conference (KPEC),IEEEpp.1–4,Piscataway,NJ (2022) 37. Barote, L., Weissbach, R., Teodorescu, R., Marinescu, C., Cirstea, M.: Stand-alone wind system with vanadium redox battery energy storage. In: 2008 11th International Conference on Optimization of Electrical and Electronic Equipment, pp. 407–412. IEEE, Piscataway, NJ (2008) 38. Basilio, J.C., Matos, S.: Design of PI and PID controllers with transient performance specification. IEEE Trans. Educ. 45(4), 364–370 (2002) 39. Azizi, N., Moradi CheshmehBeigi, H., Rouzbehi, K.: Control strategy for direct voltage and frequency stability enhancement in HVAC/HVDC grids. IET Renewable Power Gener. 15(16), 3915–3926 (2021) 40. Kerdphol, T., Rahman, F.S., Mitani, Y., Watanabe, M., Küfeoˇ glu, S.K.: Robust virtual inertia control of an islanded microgrid considering high penetration of renewable energy. IEEE Access 6, 625–636 (2017) 41. Rouzbehi, K., Miranian, A., Luna, A., Rodriguez, P.: DC voltage control and power sharing in multiterminal DC grids based on optimal DC power flow and voltage-droop strategy. IEEE J. Emerg. Sel. Top. Power Electron. 2(4), 1171–1180 (2014) 42. Vrana, T.K., Yang, Y., Jovcic, D., Dennetière, S., Jardini, J., Saad, H.: The CIGRE B4 DC grid test system. Electra 270(1), 10–19 (2013) 43. Hemmati, R., Azizi, N.: Optimal control strategy on battery storage systems for decoupled active-reactive power control and damping oscillations. J. Energy Storage 13, 24–34 (2017) 44. Mohammadi, F., Nazri, G.-A., Saif, M.: A new topology of a fast proactive hybrid DC circuit breaker for MT-HVDC grids. Sustainability 11(16), 4493 (2019) 45. Wang, W., Barnes, M., Marjanovic, O., Cwikowski, O.: Impact of DC breaker systems on multiterminal VSC-HVDC stability. IEEE Trans. Power Delivery 31(2), 769–779 (2015) 46. Liu, Y., Green, T.C., Wu, J., Rouzbehi, K., Raza, A., Xu, D.: A new droop coefficient design method for accurate power-sharing in VSC-MTDC systems. IEEE Access 7, 47605–47614 (2019) 47. Peng, Q., Liu, T., Wang, S., Qiu, Y., Li, X., Li, B.: Determination of droop control coefficient of multi-terminal VSC-HVDC with system stability consideration. IET Renewable Power Gener. 12(13), 1508–1515 (2018) 48. Rouzbehi, K., Miranian, A., Candela, J.I., Luna, A., Rodriguez, P.: A generalized voltage droop strategy for control of multiterminal DC grids. IEEE Trans. Ind. Appl. 51(1), 607–618 (2014) 49. Chaudhuri, N.R., Majumder, R., Chaudhuri, B., Pan, J.: Stability analysis of VSC MTDC grids connected to multimachine AC systems. IEEE Trans. Power Delivery 26(4), 2774–2784 (2011) 50. D’Arco, S., Suul, J.A., Beerten, J.: Configuration and model order selection of frequency-dependent πmodels for representing DC cables in smallsignal eigenvalue analysis of HVDC transmission systems. IEEE J. Emerg. Sel. Top. Power Electron. 9(2), 2410–2426 (2020) 51. Shojaei, A.H., Ghadimi, A.A., Miveh, M.R., Mohammadi, F., Jurado, F.: Multi-objective optimal reactive power planning under load demand and wind power generation uncertainties using ε-constraint method. Appl. Sci. 10(8), 2859 (2020) How to cite this article: Azizi, N., Moradi, H., Rouzbehi, K., Mohammadi, F.: HVDC grids stability enhancement through the integration of battery energy storage systems. IET Renew. Power Gener. 1–16 (2023). https://doi.org/10.1049/rpg2.12788 17521424, 0, Downloaded from https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/rpg2.12788 by Universidad De Sevilla, Wiley Online Library on [25/08/2023]. See the Terms and Conditions (https://onlinelibrary.wiley.com/terms-and-conditions) on Wiley Online Library for rules of use; OA articles are governed by the applicable Creative Commons License