scieee AI-readable full text Open interactive document viewer

Thermal comfort of older people during summer in the continental Mediterranean climate

Baquero Larriva, María Teresa,Forcada Matheu, Núria

Abstract

Globally, the population is ageing and extreme weather scenarios are expected, especially in southern European countries. In this context, the study assessed the thermal comfort of older people in five nursing homes in a continental Mediterranean climate in Spain during summer, through environmental measurements and surveys on site. A total of 1412 people were interviewed, including residents (older people) and non-residents (adults). The results showed that under the same environmental conditions, adults felt that the environment was warmer and they were less tolerant than older people. There was a 2.4¿°C difference between the neutral temperature of older people (25.6¿°C) and adults (23.2¿°C). Older people were less sensitive to thermal changes and their comfort zone was wider than that of adults. The comparison with similar studies from other climatic zones concluded that the neutral temperature for elderly in different climatic zones is similar but the thermal comfort zones are different. Older people were less sensitive to temperature changes than the predicted mean vote (PMV) model predicted. Therefore, this model would not be suitable for older people in cooling conditions in the Mediterranean continental climate. These results could be a starting point for the development of more accurate, healthy indoor spaces that meet the needs of older people as a vulnerable group, while improving energy efficiency and reducing emissions.

Full text

Journal Pre-proof Thermal comfort of older people during summer in the continental Mediterranean climate María Teresa Baquero Larriva, Nuria Forcada PII: S2352-7102(22)00693-3 DOI: https://doi.org/10.1016/j.jobe.2022.104680 Reference: JOBE 104680 To appear in: Journal of Building Engineering Received Date: 15 March 2022 Revised Date: 14 May 2022 Accepted Date: 17 May 2022 Please cite this article as: Marí.Teresa. Baquero Larriva, N. Forcada, Thermal comfort of older people during summer in the continental Mediterranean climate, Journal of Building Engineering (2022), doi: https://doi.org/10.1016/j.jobe.2022.104680. This is a PDF file of an article that has undergone enhancements after acceptance, such as the addition of a cover page and metadata, and formatting for readability, but it is not yet the definitive version of record. This version will undergo additional copyediting, typesetting and review before it is published in its final form, but we are providing this version to give early visibility of the article. Please note that, during the production process, errors may be discovered which could affect the content, and all legal disclaimers that apply to the journal pertain. © 2022 Published by Elsevier Ltd. Author statement María Teresa Baquero: Formal analysis, Investigation, Data Curation, Writing - Original Draft, Visualization Núria Forcada: Conceptualization, Methodology, Resources, Writing - Review & Editing, Supervision, Project administration, Funding acquisition Journal Pre-proof Thermal comfort of older people during summer in the continental Mediterranean climate Abstract Globally, the population is ageing and extreme weather scenarios are expected, especially in southern European countries. In this context, the study assessed the thermal comfort of older people in five nursing homes in a continental Mediterranean climate in Spain during summer, through environmental measurements and surveys on site. A total of 1,412 people were interviewed, including residents (older people) and non-residents (adults). The results showed that under the same environmental conditions, adults felt that the environment was warmer and they were less tolerant than older people. There was a 2.4ºC difference between the neutral temperature of older people (25.6ºC) and adults (23.2ºC). Older people were less sensitive to thermal changes and their comfort zone was wider than that of adults. The comparison with similar studies from other climatic zones concluded that the neutral temperature for elderly in different climatic zones is similar but the thermal comfort zones are different. Older people were less sensitive to temperature changes than the predicted mean vote (PMV) model predicted. Therefore, this model would not be suitable for older people in cooling conditions in the Mediterranean continental climate. These results could be a starting point for the development of more accurate, healthy indoor spaces that meet the needs of older people as a vulnerable group, while improving energy efficiency and reducing emissions. Keywords: thermal comfort; older people; thermal sensation; nursing homes; cooling season 1 1 Abbreviations: Csa, Mediterranean climate; Csa-c, Mediterranean continental climate; Csa-m, typical Mediterranean climate; Csb, oceanic Mediterranean climate; Cwa, humid subtropical climate; Dwa, humid continental climate; Cfb, oceanic humid subtropical; Dfb, Eastern humid continental climate, Dfc, Subarctic climate; Ta, dry air temperature; RH, relative humidity; Tr, mean radiant temperature; Va, air velocity; Tout; outdoor dry temperature; RHout, outdoor relative humidity; Top, operative temperature; Trm, running mean of outdoor temperature; Tg, globe temperature; ASHRAE, American Society of Heating, Refrigerating and Air-Conditioning Engineers; R, residents (older adults); NR, non-residents (caregivers, therapist, etc.); N, sample size; Tn, neutral temperature; TSV, thermal sensation vote; MTSV, mean thermal sensation vote; P, thermal preference; A, thermal acceptability; PMV, predicted mean vote; Clo, Journal Pre-proof 1. Introduction The growth of the ageing population is considered a major challenge for European countries. International policies have focused on improving the building environment for ageing societies, to gain more years of health and wellbeing [1]. In Spain, 20% and 6% of the population correspond to people over 65 and 80 years old respectively. These figures are forecast to increase in the next few years [2]. As a result, demand for assisted living and residential homes is increasing and the indoor environmental quality and energy efficiency implications may need to be considered [3,4]. As older people spend most of their time indoors [5], focusing on protecting the health of older people and improving energy efficiency would also bring economic benefits for society [6]. Extreme weather events are predicted to increase due to climate change. More frequent hightemperature events such as heatwaves are expected and will mainly affect southern European countries [7]. The most vulnerable groups like older people would be most affected [8]. This has been evidenced in past events like the 2003 heatwave in England, where the excess mortality of people over 75 rose 33%, compared to a 13.5% rise among younger people [9]. Similarly, around 600 people, three-quarters of whom were over the age of 65, died in Chicago’s 1995 heat wave[10]. Increasing global temperatures in the context of an ageing population is a public health concern [11]. With age, some physiological aspects decrease like muscle strength, sweating rate, the ability to transport heat to the skin, hydration levels, vascular reactivity and cardiovascular stability [12,13]. In other words, older people have reduced thermoregulation capacity, combined with a decrease in the ability to detect changes in their body temperature. This makes them more vulnerable to extreme climate scenarios [13,14]. clothing insulation level; Met, metabolic activity; Mclo, mean clothing insulation; Mmet, mean metabolic activity rate; NH, nursing home; VRV, variable refrigerant flow cooling system; mamsl, meters above sea level Journal Pre-proof Figure 1 represents the main climatic zones in Europe. Most southern countries correspond to a Mediterranean climate according to the greatest widely used climate classification, the Köppen- Geiger [15,16]. There are four prevailing climatic zones in Europe: Csa (Mediterranean climate, temperate with dry and hot summer); Cfb (Oceanic climate, mild cool winters and humid mild summers); Dfb (Eastern humid continental climate, warm summer) and Dfc (Subarctic climate, long and cold winters and cold summer). These are divided into other sub climates. Most southern European countries, including Spain, correspond to the Csa climate. Figure 1. Main European climatic zones by Köppen-Geiger classification International commitments, like the Paris Climate Conference from 2015 to 2030, have been made to reduce greenhouse gas emissions [17]. Buildings are responsible for 36% of greenhouse gas emissions and one of the European Union’s objectives is to reduce these emissions by 90% Journal Pre-proof by 2050 [18]. Heating, ventilation and air conditioning (HVAC) systems are one of the main elements responsible for building consumption and emissions, and thermal comfort is directly implicated in this [19,20]. Thermal comfort is one of the most important factors for indoor environmental quality. It affects human health and energy efficiency [6,20–22]. Approximately 75% of heating and cooling is generated by fossil fuels, according to Eurostat [23]. Therefore, decreasing energy demand for HVAC is important for the European decarbonization policy. The European Cooling Index (ECI) has been developed to analyze the geographical distribution of cooling demands in Europe [24]. It is based on the cooling degree days (CDD) concept, which refers to the assumed point from which consumers need to use the cooling system in a space. It depends on the number of degrees per day that the daily temperature is above a normal temperature (22ºC) [25]. The need for cooling buildings in 2020 was double that of 1979 and Spain ranks fifth among the countries with the highest cooling degree days after Malta, Cyprus, Portugal and Greece [26],most of which are southern countries (Figure 2). Journal Pre-proof Figure 2. Cooling degree days in Europe. Source: Eurostat 2021 [26]. The most commonly used HVAC design standards, such as ASHRAE 55 [27] and ISO 7730 [28], are mainly focused on the characteristics of average young people (male, 35 years old, 1.70 m tall, weight 75 kg, normal level of clothing and standard metabolic rate) and may not fit the physiological needs of older people [4,29–34]. Thermal perception is a complex issue. Many factors, including physiological, physical (behaviour) and psychological factors, influence each person’s perception and adaptation apart from environmental conditions [35,36]. Most of these factors differ between older and younger people [37]. Past studies have assessed physiological changes in thermal environments. Novieto and Zhang [13] found that heart rate, metabolic rate and weight in older subjects differed between 10 and 19.2% from younger ones. They stated that metabolic rate had the greatest influence on thermal comfort. Schellen et al. [34] found that the skin and body temperature of older adults was lower than that of younger people and that this had a significant effect on thermal comfort. In the last few years, there have been many studies on thermal comfort in older people, and some have assessed thermal comfort in nursing homes [30,38–43] and older peoples’ homes [44–48]. However, there is still a gap in knowledge on thermal comfort temperature for specific climatic zones, type of building and user. Some authors have found differences in thermal perception between older adults and younger ones [49]. This is mainly because thermal sensitivity decreases with age as a consequence of some physiological changes such as a reduction in muscle strength, sweating, heat transport capacity to the skin, hydration levels, vascular reactivity and cardiovascular stability [4,12,13,49,50]. A study by Krüger et al. [51,52] found that younger adults were more sensitive than older ones in Curitiba Brazil. Studies by Hwang et al. [44] and Wong et al. [39] in Korea Journal Pre-proof determined that older people perceived the environment as colder. Tartarini et al. [38] in Australia found that residents had a higher thermal sensation than non-residents in nursing homes. However, only a few studies about indoor thermal comfort in summer in the Mediterranean climate (Csa) consider older people [11,53–55]. Hansen et al. [11] reported higher morbidity in older women and people with chronic health conditions during heatwaves in Australia and stated that older people are adapted to heat extremes and undertake appropriate adaptive behaviours. Giamalaki and Kolokotsa [55] focused on older people’s thermal comfort in their own homes in Greece and found that they prefer a warmer thermal environment in winter and cooler in summer. Bills et al. [53,54,56] studied older people’s homes in Australia and found more of a preference for cooler conditions than that considered by ASHRAE and they determined that older people were more sensitive to heat. No studies have been reported on older people’s thermal comfort in the continental Mediterranean climate. Cities need to adapt their buildings to an ageing population and to climate change. However, it remains unclear to what extent air conditioning standards and regulations are applicable to buildings occupied by elderly people in each climatic zone. The effectiveness of these standards needs to be investigated so that a more energy efficient setpoint temperature can be applied if possible, for the well-being of all occupants. Existing studies recognize the need to develop thermal comfort standards for each climatic zone and different users. Most of those studies found that the PMV model was unsuitable for older people in different climatic zones. This study compares its results with past research findings in different climatic zones to identify differences in thermal perception that could be related to climate adaptation, cultural and social factors in each study context. Given the above, the objectives of this study were to: a) evaluate the thermal comfort of the elderly by identifying their neutral temperature and thermal comfort zone in the continental Mediterranean Journal Pre-proof climate in the cooling season; b) compare the thermal comfort of elderly people (residents of nursing homes) and adults (non-residents); c) compare the thermal comfort of elderly people from the continental Mediterranean climate in the cooling season and other climates; d) check whether the PMV model is suitable for older people in the continental Mediterranean climate. 2. Methodology 2.1. Continental Mediterranean climate description Continental Mediterranean is a temperate climate with a dry and hot summer (Csa-c). It is characterized by low average relative humidity of 37%, an average temperature of 25–32.8ºC and maximums that exceed 35ºC in summer, in contrast with moderate-high humidity in winter that reaches maximums of 71%, average temperatures of 2–11ºC and minimums below -2ºC. The daily thermal oscillation presents amplitudes of up to 16ºC in summer and around 6.9ºC in winter [57,58]. 2.2. Experimental campaign: fieldwork An experimental campaign was conducted in five nursing homes in the Madrid Region, in Las Rozas, Alcobendas, Colmenar Viejo and Madrid in Spain. Figure 3 presents the location of each nursing home. Field measurements were made over three days in each centre during the months of June, July, and August 2021 (Table 1 presents the exact dates of the measurements in each nursing home). Environmental measurements and surveys were performed simultaneously in common areas (living room, therapy room, dining room and gym-physiotherapy room). After 10 minutes of equipment stabilization, measurements were recorded every 15 seconds for periods between 15 and 60 minutes, depending on the activity and number of people in each room, and between 10 Journal Pre-proof 2.3. Statistical analysis The statistical analysis was carried out using Spearman’s and Pearson’s correlation test. Linear regressions and the chi-square test were performed using IBM SPSS 22 software at a significance level of 0.05, to assess the relationships between thermal perception and environmental and personal variables. 3. Results and discussion 3.1. Outdoor and indoor environmental conditions During the experimental campaign, the outdoor temperature ranged from 15.2ºC to 29.3ºC with an average of 23.4ºC. Relative humidity ranged from 16.9% to 83.7% with an average of 44.6%. The experimental campaign was carried out under conditions that are characteristic of a continental-Mediterranean climate. The average indoor environmental conditions during the experimental campaign were Ta = 25ºC, Tg = 25ºC, RH = 44%, va = 0.1 m/s. Table 6 presents the outdoor and indoor environmental conditions during the study. Table 6. Indoor and outdoor conditions of the experimental campaign Environmental Variable Mean Max Min SD Tg (ºC) 24.95 27.65 22.42 1.11 Ta (ºC) 24.95 28.02 22.22 1.20 RH (%) 44.02 56.98 29.90 7.10 Va (m/s) .06 .28 .00 .07 Tr (ºC) 24.95 27.49 22.41 1.08 Top (ºC) 24.95 27.76 22.36 1.12 Tout (ºC) 23.42 29.30 15.20 4.51 Trm (ºC) 23.45 27.31 17.96 2.53 RHout (%) 44.59 83.73 16.85 19.05 Journal Pre-proof 3.2. Sample description Five nursing homes in Las Rozas, Alcobendas, Colmenar Viejo and Madrid in the Community of Madrid, Spain, were selected. A total of 1,412 surveys were collected during the experimental campaign in the summer, 87.3% were older people (residents, most of them over 65 years old), 12.7% were younger adults (non-residents, nursing home staff). Regarding the gender of participants, 78% of the general sample were women. Women represented 75.5% of residents and 93.3% of non-residents. Nursing homes staff helped to select participants with good cognitive function for inclusion in the study. 3.3. Thermal sensation residents and non-residents Chi-square tests revealed statistically significant differences (p<0.05) between thermal sensation votes (TSV) of residents and non-residents in cooling conditions in nursing homes (Table 7). No significant differences were found according to the gender of the participant (p>0.05). Even though there was a big difference between the groups, the comparison between groups may not be representative but just indicative. Table 7. Chi-square test between TSV and the type of user in summer (cooling). Residents/non-residents Women/men Pearson Chi- Square Value df Asymp. sig. (2- sided) Value df Asymp. sig. (2- sided) 169.147* 6 0.00 9.893** 6 0.129 Likelihood ratio 124.451 6 0.00 11.954 6 0.063 Linear-by-linear association 92.575 1 0.00 2.547 1 0.11 No. of valid cases 1412 1412 *2 cells (14.3%) have an expected count less than 5. The minimum expected count is 4.21. **0 cells (0.0%) have an expected count less than 5. The minimum expected count is 7.34. Journal Pre-proof Regarding older people’s thermal sensation, 78% perceived the environment as neutral (TSV=0); 77.2% stated they would not change it and 90% thought it was acceptable. Under the same conditions, 58% of non-residents had a neutral thermal sensation, 61.7% would not change it and 86.7% felt it was acceptable. Adults considered that the environment was warmer than the older people: 19.44% felt the environment was slightly warm (TSV=1), 7.78% warm (TSV=2) and 10.56% hot (TSV=3). This coincides with the figure of 35.6% of adults who would prefer the environment to be cooler, in contrast with 12.3% of residents who would prefer it to be warmer. Figure 6 presents these results by type of user. Figure 6. Thermal sensation, preference and acceptability of older people and adults. Schellen et al. [34] found that the thermal sensation of older adults was in general 0.5 scale units lower than that of younger adults. Similar results were found by the Forcada et al. [30] in their study in nursing homes in the Mediterranean climate on the eastern coast of Spain, where residents were more tolerant than non-residents. Nevertheless, in that context, only 13.3% of nonresidents had a neutral thermal sensation while 67% felt the environment was hot (TSV=+1; +2 and +3). Spearman´s correlation test was performed to assess the correlation between thermal sensation vote (TSV) (ordinal variable) and the environmental parameters (as numerical variables). The 0 10 20 30 40 50 60 70 80 90 Acceptable Unaccepatble % of votes Thermal acceptability (A) Adults Older people 0 10 20 30 40 50 60 70 80 Cooler No change Warmer % of votes Thermal preference (P) 0 10 20 30 40 50 60 70 80 -3 -2 -1 0 1 2 3 % of votes Thermal sensation vote (TSV) a) b) c) Journal Pre-proof results revealed that thermal sensation was strongly correlated (p<0.01) with indoor environmental variables like Top and Tr for older people and adults. 3.3.1. Neutral temperature and comfort zone Through linear regression, the neutral temperature (Tn) was calculated for older people and adults as a function of their mean thermal sensation votes (MTSV) and the operative temperature (Top) with weighted 0.5°C binned data [63–67] (Equations 3–4). Figure 7 represents these linear regressions. The neutral temperature was found to be 25.6°C for older people and 23.2°C for adults, with a very high difference of 2.4°C between them. The slope of the TSV of older people is lower. This means that they are less sensitive to thermal changes and thermal changes may affect adults more, as some other studies have found [30,38,68,69]. Some authors attributed this to the influence of the reduction in their thermal sensitivity and regulation [3,47]. However, other factors such as origin, expectation, previous experience and exposure time to a thermal environment may influence each person’s subjective perception [49,70]. This could be related to thermal adaptation, as residents spend most of their day indoors, while non-residents enter and leave the residence every day [71]. Older people MTSV= 0.15569Top-4.0227 (R2=0.6) (3) Adults MTSV= 0.356 Top-8.2524 (R2=0.5) (4) Journal Pre-proof Figure 7. TSV of older people and adults in the function of Top ºC. The thermal comfort zone is defined by ASHRAE [27]as the range of temperature where at least 80% of users are satisfied with the thermal environment. ASHRAE suggests a special category of 90% for older people [27,60]. As in the present study, 90% of older people and 86.7% of adults found the environment acceptable (Figure 6). The thermal comfort zone will be considered within the interval of TSV= -1 to 1, as in other studies [39,44,53,72–74]. Based on linear regression models (Equations 3–4), the comfort zone for older people was found to be from 19.4ºC to 32.3ºC, while for adults it was from 20.4ºC to 26ºC. The comfort zone for adults was narrower than that of older people. The results reported that temperatures up to 32.3ºC may still be comfortable for most older adults. However, some authors suggested that these high temperatures may be risky for health [6,75]. A bibliographic review by Tham et al. [75] found that indoor temperatures higher than 26ºC were associated with increased respiratory distress emergencies, and symptoms of dementia were significantly exacerbated. This means that even if older people feel that the environment is pleasant, their health may be at risk without them noticing [6]. Journal Pre-proof Both the neutral temperatures and the comfort zone vary in studies in other climatic regions. Although the methodology used to define these limits differs in all the referenced studies, in the present study the range has been extrapolated from the linear regression between TSV and Top, considering TSV (-1 to +1) as satisfied. This method is the most common in most thermal comfort studies [39,44,53,72–74]. Some studies [30,44] define this range by a second order polynomial best fit regression to estimate the percentage of dissatisfied people (PPD) in response to the change in Top, and others use psychrometric charts [76] or other statistical models [41]. Some authors have reported that there is no consensus on these charts and models. This could lead to misconceptions, since there are no guidelines on how levels and ranges should be defined and determined, and significant variations in methods and terms exist in the literature [44,77]. For the sake of comparison, we obtained the temperature ranges according to the methodology in the present study, using the logistic regression of each study and interpolating TSV values between -1 and 1. Table 8 presents this comparison between the present study and others from different climatic zones for the summer or cooling season. Table 8. Comparison of thermal comfort estimated for other climatic zones in the cooling season for older and young adults. Reference Climate Location Type of building N Older people MTSV model Tn ºC Comfort zone* Present study Csa-c Madrid region, Central Spain Nursing homes 1412 1232 MTSV= 0.15569Top- 4.0227 (R2=0.6) 25.6 19.4-32.3 Bills 2018 [46] Csa Adelaide, Australia Dwelling 2667 267 MTSV=0.135Top- 2.971 22 14.6-29.4 Forcada et al. 2020 [30] Csa-m East coast, Spain Nursing homes 623 476 MTSV=0.28 Top- 7.17 (R2=0.59) 25.3 22-29.2 Hwang et al. 2010 [44] Cwa Taiwan, China Dwelling 670 352 MTSV=0.39 Top- 9.84 (R2=0.91) 25.2 22.6-27.8 Journal Pre-proof Wong et al. 2009 [39] Cwa Hong Kong, China Nursing homes 384 25.8 Loughnan et al. 2015 [45] Cfb Victorian, Australia Dwelling 55 55 26.6 Tartarini et al. 2018 [38] Cfb Southeastern New South Wales, Australia Nursing homes 258 166 MTSV=0.165 Top-3.79** 22.9 16.9-29 Yang et al. 2016 [41] Dwa Korea Nursing homes 114 114 TSV=0.57 Top-13.63 23.9 22.15-25.6 Kainaga et al. 2022[68] Cfa Nagano, Japan Nursing homes 4535 4535 MTSV=0.03Top- 0.7 (R2=0.3) 25.9 Tao et al. 2020 [76] Cwa Hong Kong, China Nursing homes 181 181 26- 29 Abbreviations: N = sample; Tn = neutral temperature; Cwa = humid subtropical climate; Csa-c = Mediterranean continental climate; Csa-m = Mediterranean climate; Cfb = Oceanic climate; Dwa = humid continental climate; Cfa = humid subtropical; Top = operative indoor temperature; Ta = indoor air temperature *Obtained using the logistic regression of each study and interpolating TSV values between -1 and 1. ** Calculated based on the figure of linear regression presented in the referenced study Neutral temperature results from the present study were similar to those of the study performed in nursing homes in the Mediterranean climate (Csa-m) in the coastal region of Spain, under cooling conditions [30], where Tn was found to be 25.3ºC for residents and 23.9ºC for nonresidents but within a narrower thermal comfort zone for residents from 22ºC to 29.2ºC. However, these results are very different to those of a study in Australia, which corresponds to a Csa climate [46]. In a Cwa climate (humid subtropical climate), Hwang & Chen [44] found neutral temperature to range from 22.6ºC to 27.8ºC for older people in summer in private dwellings. In a Cfb climate (oceanic climate), Tartarini et al. [38] found a wider comfort zone range from 16.9ºC to 29ºC in nursing homes. Nevertheless, Loughnan et al. [45] found that most older people stated that they were thermally comfortable at a temperature of 26.6ºC in dwellings. In Dwa (humid continental Journal Pre-proof climate) in Korea, Yang et al. [41] analysed thermal comfort by clusters. By linear regression, they found a neutral temperature of 23.9ºC and a thermal comfort zone range from 22.15 to 25.6ºC for older people. Considering that the thermal comfort zone is calculated by the regression between MTSV and Top, the differences among thermal comfort zones in different climatic regions might be attributed to different sensitivity to temperature changes due to adaptation to climate and tolerance [78,79], cultural variables [22,70,78,80], origin or health level within different climatic regions. For the present study the comfort zone is broader than for the other studies indicating that elderly people from the continental Mediterranean climate have a low sensitivity to temperature changes and allow broader temperatures. However, the neutral temperature was found to be similar for all elderly people in different regions. This result allows determining a common setpoint temperature for all nursing homes but defining different margin of acceptability by climatic region. 3.4. Influence of personal variables on thermal sensation Metabolic rate varies according to the activity performed (met), and this, together with the level of clothing, are considered personal factors that affect the perception of thermal comfort and adaptation to the environment [81]. Statistical differences were found between older people and adults for met and clo (T-student test) (p<0.01). Table 9 presents the level of activity (met) and clothing insulation. The results showed that met was higher for adults, as most of the time older people performed passive activities, some were restricted by their health status [11], and many had mobility difficulties. Older people wore higher levels of clothing than adults, which could also be attributed to thermal sensitivity loss. These results are consistent with those of other studies that found older people wear higher levels of clothing insulation in general [51,56]. Some authors have found that older people tend to adjust their clothing levels as their main adaptative behaviour to the thermal Journal Pre-proof environment in residential environments [44,82]. This might be the only possible adaptive behaviour in environments like nursing homes where residents cannot control the air conditioning or windows [83,84]. Table 9. Activity and level of clothing during the experimental campaign User Type Met Clo Mean SD Max Min Mean SD Max Min Older people 1.04 0.11 1.60 0.80 0.65 0.23 1.60 0.10 Adults 1.57 0.12 1.60 1.00 0.46 0.14 0.96 0.19 Spearman’s correlation test was performed to assess the correlation between thermal sensation vote (TSV) (ordinal variable) and personal variables (clo and met, as numerical variables). The results revealed that thermal sensation was only correlated to activity and to the level of clothing in older people (p<0.01). Thermal sensation was negatively correlated with the level of clothing in older people (r = -0127). In other words, when older people wore higher levels of clothing, they felt warmer. This coincided with the results of Forcada et al. [30]. Some authors stated that most TSV differences between age groups are related to a lower activity level that implies lower metabolic heat production in the elderly [34,85]. Clearly, it is important to find other adaptative behavioural solutions for older people to improve their thermal comfort and overall health in environments like nursing homes where they do not have control of air conditioning or windows. For example, they could use small handheld fans, cooling pads, blankets, etc. The level of clothing was significantly correlated to indoor environmental variables like RH and Va, and to the outdoor temperature (Tout) for older people. For adults, neither clothing nor activity was related to environmental variables. Similarly, the level of activity of older people was found Journal Pre-proof to be correlated to indoor environmental variables like Top and outdoor variables like the RHext. For adults, there was no correlation. Linear regression was calculated to find the relation between level of clothing with indoor operative temperature (Top) for both groups (Equations 5 and 6). Older people Mclo = 0.0131Top+1.0117 (5) Adults Mclo = -0.0105Top+0.7191 (6) Figure 8 presents these regression models. The results indicate that both older people and adults adjust their clothing levels related to Top more than Trm. When Top increased, the Clo level decreased, even though this influence was low compared to other studies [30,38,44]. Figure 8. a) Mean Clo vs. Trm; b) Mean Clo vs. Top Additionally, through the Pearson correlation test, the level of clothing (clo) was not correlated with activity (met) for older people or for adults (p>0.05). All of them maintained their level of clothing independently from the activity. In contrast, in the study of Forcada et al. [30], only younger adults adapted their clothing to the activity that was performed. Other authors found that older people’s most popular strategy of thermal adaptation is clothing adjustment [44,82]. 0.3 0.4 0.5 0.6 0.7 0.8 0.9 21 23 25 27 29 Clo Top ºC Older people Clo Adults Clo Lineal (Older people Clo) Lineal (Adults Clo) 0.3 0.4 0.5 0.6 0.7 0.8 0.9 21 23 25 27 29 Clo Trm ºC a) b) Journal Pre-proof In the context of the ageing population trend, more research is needed to determine mitigation and adaptation strategies for the extreme climate scenarios to come, including the correct design of buildings such as nursing homes. These results could be a starting point for the development of more accurate, healthy indoor spaces that meet the needs of older people as a vulnerable group, while improving energy efficiency and reducing emissions. 5. Acknowledgements This research was supported by the Spanish Ministry of Economy, Industry and Competitiveness under the R&D project Thecoelen, reference no. PID2019-106777RB-C21. Additionally, thanks to Sanitas Mayores and especially Marc Vallet and Albert Ayala for providing their nursing homes and helping to collect the required data. The authors would like to extend our appreciation to all the caregivers, maintenance staff and elderly people who participated in this project. 6. References [1] World Health Organization, Global Age-friendly Cities: A Guide, France, 2007. [2] A. Abellán, P. Aceituno, J. Pérez, D. Ramiro, A. Ayala, R. Pujol, Un perfil de las personas mayores en España 2019. Indicadores estadísticos básicos, Inf. Envejec. En Red. (2019) 38. http://envejecimiento.csic.es/documentos/documentos/enredindicadoresbasicos2019.pdf. [3] G. Havenith, Temperature regulation and technology, Gerontechnology. 1 (2001) 41–49. https://doi.org/10.4017/gt.2001.01.01.004.00. [4] F. Salata, I. Golasi, W. Verrusio, E. de Lieto Vollaro, M. Cacciafesta, A. de Lieto Vollaro, On the necessities to analyse the thermohygrometric perception in aged people. A review about indoor thermal comfort, health and energetic aspects and a perspective for future studies, Sustain. Cities Soc. 41 (2018) 469–480. https://doi.org/10.1016/j.scs.2018.06.003. [5] EC-European Commission, Indoor air pollution: New EU research reveals higher risks than previously thought, 2003. [6] D. Ormandy, V. Ezratty, Health and thermal comfort : From WHO guidance to housing strategies, Energy Policy. 49 (2012) 116–121. https://doi.org/10.1016/j.enpol.2011.09.003. [7] IPCC, Climate Change 2014 . Synthesis report, 2014. https://doi.org/10.1017/CBO9781107415324. [8] European Commission, Adaptation to climate change, How Will We Be Affect. (2022). Journal Pre-proof https://ec.europa.eu/clima/eu-action/adaptation-climate-change/how-will-we-be- affected_en (accessed March 9, 2022). [9] R.S. Kovats, Heat waves and health protection: Focus on Public Health, Social Care, and Building Regulations., BMJ Br. Med. J. 333 (2006) 314–315. [10] E. Klinenberg, Heatwave: A Social Autopsy of Disaster in Chicago., University of Chicago Press., Chicago, 2002. [11] A. Hansen, P. Bi, D. Pisaniello, M. Nitschke, G. Tucker, J. Newbury, A. Kitson, E. Dal Grande, J. Avery, Y. Zhang, L. Kelsall, Heat-health behaviours of older people in two Australian states, Australas. J. Ageing. 34 (2015) E19–E25. https://doi.org/10.1111/ajag.12134. [12] J. Van Hoof, J.L.M. Hensen, Thermal comfort and older adults, Gerontechnology. 4 (2006) 223–228. https://doi.org/10.4017/gt.2006.04.04.006.00. [13] D.T. Novieto, Y. Zhang, Thermal comfort implications of the aging effect on metabolism , cardiac output and body weight, in: Adapt. to Chang. New Think. Comf., 2010. [14] N.R.I. Ryti, Y. Guo, J.J.K. Jaakkola, Global association of cold spells and adverse health effects: A systematic review and meta-analysis, Environ. Health Perspect. 124 (2016) 12–22. https://doi.org/10.1289/ehp.1408104. [15] M. Kottek, J. Grieser, C. Beck, B. Rudolf, F. Rubel, World map of the Köppen-Geiger climate classification updated, Meteorol. Zeitschrift. 15 (2006) 259–263. https://doi.org/10.1127/0941-2948/2006/0130. [16] PVSITES, European climate zones and bio-climatic design requirements, 2016. [17] World Metereological Organization, United In Science, 2019. [18] European Comission, A Roadmap for Moving to a Competitive Low Carbon Economy in 2050: Communication from the Commission to the European Parliament, the Council, the European Economic and Social Committee and the Committee of the Regions., 2011. [19] L. Yang, H. Yan, J.C. Lam, Thermal comfort and building energy consumption implications – A review, Appl. Acoust. 115 (2014) 164–173. [20] M. Jos, D. Bienvenido-huertas, C. Rubio-bellido, J.L. P, Evaluating the potential of adaptive comfort approach using historic data to reduce energy consumption in buildings in southern Spain, Build. Environ. 185 (2020). https://doi.org/10.1016/j.buildenv.2020.107313. [21] W. Miller, D. Vine, Z. Amin, Energy efficiency of housing for older citizens: Does it matter?, Energy Policy. 101 (2017) 216–224. https://doi.org/10.1016/j.enpol.2016.11.050. [22] M. Frontczak, P. Wargocki, Literature survey on how different factors in fl uence human comfort in indoor environments, Build. Environ. 46 (2011) 922–937. https://doi.org/10.1016/j.buildenv.2010.10.021. [23] European Comission, Energy Efficiency, Heat. Cool. (2022). https://energy.ec.europa.eu/topics/energy-efficiency/heating-and-cooling_en (accessed March 9, 2022). Journal Pre-proof [24] D. Paer, J. Nilsson, R. Anders, ECOHEATCOOL Work Package 2. The European cold market. Final Report, Sweden, 2005. https://www.osti.gov/etdeweb/biblio/20758196. [25] P.G. Nicolas, V. Konstaninos, K.-R. Anna, M.R.J. Antonio, P.L. Alicia, Heat and Cooling Demand and Market Perspective, Pettern, The Netherlands, 2012. https://doi.org/10.2790/56532. [26] EUROSTAT, Heating and cooling degree days-statistics, Heat. Cool. Degree Days EU-27 Lev. (2021). https://ec.europa.eu/eurostat/statisticsexplained/index.php?title=Heating_and_cooling_degree_days_- _statistics#Heating_and_cooling_degree_days_at_EU-27_level (accessed March 9, 2022). [27] ASHRAE, STANDARD 55 – Thermal Enviornmental Conditions for Human Occupancy, 2020. https://www.ashrae.org/technical-resources/bookstore/standard-55-thermal- environmental-conditions-for-human-occupancy. [28] International Organization for Standardization, ISO 7730. Ergonomics of the thermal environment. Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria, 2005. [29] M.T. Baquero Larriva, E. Higueras, Health risk for older adults in Madrid, by outdoor thermal and acoustic comfort, Urban Clim. 34 (2020) 100724. https://doi.org/10.1016/j.uclim.2020.100724. [30] N. Forcada, M. Gangolells, M. Casals, B. Tejedor, M. Macarulla, K. Gaspar, Summer thermal comfort in nursing homes in the Mediterranean climate, Energy Build. 229 (2020) 110442. https://doi.org/10.1016/j.enbuild.2020.110442. [31] G. Havenith, I. Holmér, K. Parsons, Personal factors in thermal comfort assessment: Clothing properties and metabolic heat production, Energy Build. 34 (2002) 581–591. https://doi.org/10.1016/S0378-7788(02)00008-7. [32] F. Kalmár, An indoor environment evaluation by gender and age using an advanced personalized ventilation system, Build. Serv. Eng. Res. Technol. 38 (2017) 505–521. https://doi.org/10.1177/0143624417701985. [33] Y. Jin, F. Wang, S.R. Payne, R.B. Weller, A comparison of the effect of indoor thermal and humidity condition on young and older adults’ comfort and skin condition in winter, Indoor Built Environ. 0 (2021) 1–18. https://doi.org/10.1177/1420326X211030998. [34] L. Schellen, W.. van Marken Lochtenbelt, M.G.L.. Loomans, J. Toftum, M.. de Wit, Differences between young adults and elderly in thermal comfort, productivity , and thermal physiology in response to a moderate temperature drift and a steady-state condition, Indoor Air. 20 (2010) 273–283. https://doi.org/10.1111/j.1600- 0668.2010.00657.x. [35] P. Höppe, Different aspects of assessing indoor and outdoor thermal comfort, Energy Build. 34 (2002) 661–665. https://doi.org/10.1016/S0378-7788(02)00017-8. [36] F. Salata, I. Golasi, E. de L. Vollaro, F. Bisegna, F. Nardecchia, M. Coppi, F. Gugliermetti, A. de L. Vollaro, Evaluation of different urban microclimate mitigation strategies through a PMV analysis, Sustain. 7 (2015) 9012–9030. Journal Pre-proof https://doi.org/10.3390/su7079012. [37] M.T. Baquero Larriva, E. Higueras García, Thermal comfort for the elderly: A systematic review of the scientific literature, Rev. Esp. Geriatr. Gerontol. 54 (2019) 280–295. https://doi.org/10.1016/j.regg.2019.01.006. [38] F. Tartarini, P. Cooper, R. Fleming, Thermal perceptions, preferences and adaptive behaviours of occupants of nursing homes, Build. Environ. 132 (2018) 57–69. https://doi.org/10.1016/j.buildenv.2018.01.018. [39] L.T. Wong, K.N.K. Fong, K.W. Mui, W.W.Y. Wong, L.W. Lee, A field survey of the expected desirable thermal environment for older people, Indoor Built Environ. 18 (2009) 336–345. https://doi.org/10.1177/1420326X09337044. [40] Y. Jiao, H. Yu, T. Wang, Y. An, Y. Yu, Thermal comfort and adaptation of the elderly in free-running environments in Shanghai, China, Build. Environ. 118 (2017) 259–272. https://doi.org/10.1016/j.buildenv.2017.03.038. [41] J. Yang, I. Nam, J.R. Sohn, The influence of seasonal characteristics in elderly thermal comfort in Korea, Energy Build. 128 (2016) 583–591. https://doi.org/10.1016/j.enbuild.2016.07.037. [42] Y. Wu, H. Liu, B. Li, R. Kosonen, D. Kong, S. Zhou, R. Yao, Thermal adaptation of the elderly during summer in a hot humid area: Psychological, behavioral, and physiological responses, Energy Build. 203 (2019) 109450. https://doi.org/10.1016/j.enbuild.2019.109450. [43] A. Mendes, A.L. Papoila, P. Carreiro-Martins, L. Aguiar, S. Bonassi, I. Caires, T. Palmeiro, Á.S. Ribeiro, P. Neves, C. Pereira, A. Botelho, N. Neuparth, J.P. Teixeira, The Influence of Thermal Comfort on the Quality of Life of Nursing Home Residents, J. Toxicol. Environ. Heal. - Part A Curr. Issues. 80 (2017) 729–739. https://doi.org/10.1080/15287394.2017.1286929. [44] R.. Hwang, C.. Chen, Field study on behaviors and adaptation of elderly people and their thermal comfort requirements in residential environments, Indoor Air. 20 (2010) 235–245. https://doi.org/10.1111/j.1600-0668.2010.00649.x. [45] M. Loughnan, M. Carroll, N.J. Tapper, The relationship between housing and heat wave resilience in older people, Int. J. Biometeorol. (2015) 1291–1298. https://doi.org/10.1007/s00484-014-0939-9. [46] R. Bills, Creating Comfort and Cultivating Good Health: The Links Between Indoor Temperature, in: Therm. Comf. Heal. 10th Wind. Conf. Rethink. Comf. NCEUB 2018, Windsor, UK, 2018: pp. 886–900. [47] G. Fan, J. Xie, H. Yoshino, U. Yanagi, K. Hasegawa, C. Wang, X. Zhang, J. Liu, Investigation of indoor thermal environment in the homes with elderly people during heating season in Beijing, China, Build. Environ. 126 (2017) 288–303. https://doi.org/10.1016/j.buildenv.2017.09.031. [48] C. Hughes, S. Natarajan, Summer thermal comfort and overheating in the elderly, Build. Serv. Eng. Res. Technol. 40 (2019) 426–445. https://doi.org/10.1177/0143624419844518. Journal Pre-proof [49] M.T. Baquero Larriva, E. Higueras García, Thermal Comfort for older adults: a systematic review of scientific literature, Rev. Esp. Geriatr. Gerontol. (n.d.). [50] J. Van Hoof, L. Schellen, V. Soebarto, J.K.W. Wong, J.K. Kazak, Ten questions concerning thermal comfort and ageing, Build. Environ. J. 120 (2017) 123–133. https://doi.org/10.1016/j.buildenv.2017.05.008. [51] E. Krüger, B. Givoni, F.A. Rossi, Outdoor Comfort study in Curitiba, Barzil. Effects of gender, body weight and age on the thermal preference, in: Adapt. to Chang. New Think. Comf. Cumberl. Lodg. Wind. UK, 9-11 April 2010. London Netw. Comf. Energy Use Build., 2015. [52] E.L. Krüger, F.A. Rossi, Effect of personal and microclimatic variables on observed thermal sensation from a field study in southern Brazil, Build. Environ. 46 (2011) 690– 697. https://doi.org/10.1016/j.buildenv.2010.09.013. [53] R. Bills, V. Soebarto, T. Williamson, Thermal experiences of older people during hot conditions in Adelaide, in: Revisiting Role Archit. Sci. Des. Pract. 50th Int. Conf. Archit. Sci. Assoc. Proceedings, 2016 / Zuo, J., Daniel, L., Soebarto, V. (Ed./S), 2016: pp. 657– 664. [54] R. Bills, V. Soebarto, Understanding the changing thermal comfort requirements and preferences of older Australians, in: Living Learn. Res. a Better Built Environ. 49th Int. Conf. Archit. Sci. Assoc., 2015: pp. 1203–1212. http://anzasca.net/category/conferencepapers/2015-conference-papers. [55] M. Giamalaki, D. Kolokotsa, Understanding the thermal experience of elderly people in their residences: Study on thermal comfort and adaptive behaviors of senior citizens in Crete, Greece, Energy Build. 185 (2019) 76–87. https://doi.org/10.1016/j.enbuild.2018.12.025. [56] R. Bills, Cold Comfort : Thermal sensation in people over 65 and the consequences for an ageing population, in: Proc. 9th Wind. Conf. Mak. Comf. Relev., Cumberland Lodge, Windsor, UK, 2016. [57] Departamento de Producción de la Agencia Estatal de Meteorología de España y Departamento de Meteorología e clima de Portugal, Atlas Climático Ibérico. Temperatura del Aire y Precipitación (1971-2000), Closas-Orc, 2011. http://www.aemet.es/documentos/es/conocermas/publicaciones/Atlasclimatologico/Atlas.pdf. [58] AEMET, Temperaturas medias y su comparación con las de los últimos 30 años. (Observatorio de Retiro), Banco Datos. Ayunt. Madrid Territ. y Medio Ambient. (2019). http://www-2.munimadrid.es/CSE6/control/seleccionDatos?numSerie=14020000020 (accessed March 22, 2019). [59] International Standard Organization, ISO 7726: Ergonomics of the thermal environment. Instruments and methods for measuring physical quantities, 1998. [60] Comite’Europe’en de Normalisation, Indoor environmental input parameters for design and assessment of energy performance of buildingsaddressing indoor air quality, thermal environment, lighting and acoustics. EN 15251, 2007. Journal Pre-proof [61] E. Envejecimiento en Red, Una estimación de la población que vive en residencias de mayores, Estadísticas Sobre Resid. (2020). https://envejecimientoenred.es/unaestimacion-de-la-poblacion-que-vive-en-residencias-de-mayores/#:~:text=En 2019%2C nuestra estimación indica,lo establecemos en el 86%25. (accessed April 25, 2021). [62] W.G. Cochran, Sampling Techniques, 2nd ed., New York, 1963. [63] M. Khoshbakht, Z. Gou, F. Zhang, A pilot study of thermal comfort in subtropical mixedmode higher education office buildings with different change-over control strategies, Energy Build. 196 (2019) 194–205. https://doi.org/10.1016/j.enbuild.2019.05.030. [64] N. Forcada, M. Gangolells, M. Casals, B. Tejedor, M. Macarulla, K. Gaspar, Field study on adaptive thermal comfort models for nursing homes in the Mediterranean climate, Energy Build. 252 (2021) 111475. https://doi.org/10.1016/j.enbuild.2021.111475. [65] M. Jowkar, H. Bahadur, A. Montazami, J. Brusey, The influence of acclimatization , age and gender-related differences on thermal perception in university buildings: Case studies in Scotland and England, Build. Environ. 179 (2020) 106933. https://doi.org/10.1016/j.buildenv.2020.106933. [66] R.J. de Dear, G.S. Brager, Developing an adaptive model of thermal comfort and preference, ASHRAE Trans. 104 (1998) 145–167. [67] Z. Wang, R. De Dear, M. Luo, B. Lin, Y. He, A. Ghahramani, Individual Difference in Thermal Comfort: A Literature Review, Build. Environ. 138 (2018) 181–193. https://doi.org/10.1016/j.buildenv.2018.04.040. [68] T. Kainaga, K. Sagiaska, R. Yamada, T. Nayaka, A Case Study of a Nursing Home in Nagano, Japan:Field Survey on Thermal Comfort and Building Energy Simulation for Future Climate Change, Energies. 15 (2022). https://doi.org/10.3390/en15030936. [69] Y. Wu, H. Liu, B. Li, R. Kosonen, D. Kong, S. Zhou, Thermal adaptation of the elderly during summer in a hot humid area : Psychological , behavioral , and physiological responses, Energy Build. 203 (2019) 109450. https://doi.org/10.1016/j.enbuild.2019.109450. [70] I. Knez, S. Thorsson, Thermal, emotional and perceptual evaluations of a park: Crosscultural and environmental attitude comparisons, Build. Environ. 43 (2008) 1483–1490. https://doi.org/10.1016/j.buildenv.2007.08.002. [71] N. Forcada, M. Gangolells, M. Casals, B. Tejedor, M. Macarulla, K. Gaspar, Field study on thermal comfort in nursing homes in heated environments, Energy Build. 244 (2021) 111032. https://doi.org/10.1016/j.enbuild.2021.111032. [72] X.L. Ji, W.Z. Lou, Z.Z. Dai, B.G. Wang, S.Y. Liu, Predicting thermal comfort in Shanghai’s non-air-conditioned buildings, Build. Res. Inf. 34 (2006) 507–514. https://doi.org/10.1080/09613210600722511. [73] H. Feriadi, N.H. Wong, S. Chandra, K.W. Cheong, Adaptive behaviour and thermal comfort in Singapore’s naturally ventilated housing, Build. Res. Inf. (2010) 37–41. https://doi.org/10.1080/0961321021000013830. [74] R. De Dear, G.S. Brager, The adaptive model of thermal comfort and energy Journal Pre-proof conservation in the built environment, Int. J. Biometeorol. 45 (2001) 100–108. https://doi.org/10.1007/s004840100093. [75] S. Tham, R. Thompson, O. Landeg, K.A. Murray, T. Waite, Indoor temperature and health: a global systematic review, Public Health. 179 (2020) 9–17. https://doi.org/10.1016/j.puhe.2019.09.005. [76] Y. Tao, Z. Gou, Z. Yu, J. Fu, X. Chen, The challenge of creating age-friendly indoor environments in a high-density city: Case study of Hong Kong’s care and attention homes, J. Build. Eng. 30 (2020) 101280. https://doi.org/10.1016/j.jobe.2020.101280. [77] P.K. Cheung, C.Y. Jim, Determination and application of outdoor thermal benchmarks, Build. Environ. 123 (2017) 333–350. https://doi.org/10.1016/j.buildenv.2017.07.008. [78] S. Manu, Y. Shukla, R. Rawal, L.E. Thomas, R. de Dear, Field studies of thermal comfort across multiple climate zones for the subcontinent: India Model for Adaptive Comfort (IMAC), Build. Environ. 98 (2016) 55–70. https://doi.org/10.1016/j.buildenv.2015.12.019. [79] M. Frontczak, P. Wargocki, Literature survey on how different factors influence human comfort in indoor environments, Build. Environ. 46 (2011) 922–937. https://doi.org/10.1016/j.buildenv.2010.10.021. [80] M.T. Baquero Larriva, A.S. Mendes, N. Forcada, The effect of climatic conditions on occupants ’ thermal comfort in naturally ventilated nursing homes, Build. Environ. 214 (2022) 108930. https://doi.org/10.1016/j.buildenv.2022.108930. [81] P.. Fanger, Assessment of thermal comfort practice, Br. J. Ind. Med. 30 (1973) 313–324. https://doi.org/http://dx.doi.org/10.1136/oem.30.4.313. [82] Y. Jiao, H. Yu, T. Wang, Y. An, Y. Yu, The relationship between thermal environments and clothing insulation for elderly individuals in Shanghai, China, J. Therm. Biol. 70 (2017) 28–36. https://doi.org/10.1016/j.jtherbio.2017.07.002. [83] H. Feriadi, N.H. Wong, Thermal comfort for naturally ventilated houses in Indonesia, Energy Build. 36 (2004) 614–626. https://doi.org/10.1016/j.enbuild.2004.01.011. [84] G. Schiller Brager, R. de Dear, A Standard for Natural Ventilation, ASHRAE J. 15 (2000) 250–260. https://doi.org/10.11436/mssj.15.250. [85] D.W. DeGroot, G. Havenith, W.L. Kenney, Responses to mild cold stress are predicted by different individual characteristics in young and older subjects., J. Appl. Physiol. 101 (2006) 1607–15. https://doi.org/10.1152/japplphysiol.00717.2006. [86] R. Yao, B. Li, J. Liu, A theoretical adaptive model of thermal comfort - Adaptive Predicted Mean Vote (aPMV), Build. Environ. 44 (2009) 2089–2096. https://doi.org/10.1016/j.buildenv.2009.02.014. [87] J. Van Hoof, Forty years of Fanger’s model of thermal comfort: Comfort for all?, Indoor Air. 18 (2008) 182–201. https://doi.org/10.1111/j.1600-0668.2007.00516.x. [88] I. Golasi, F. Salata, E. de Lieto Vollaro, M. Coppi, Complying with the demand of standardization in outdoor thermal comfort: a first approach to the Global Outdoor Comfort Index (GOCI), Elsevier Ltd, 2018. https://doi.org/10.1016/j.buildenv.2017.12.021. Journal Pre-proof [89] R. De Dear, Revisiting an old hypothesis of human thermal perception: Alliesthesia, Build. Res. Inf. 39 (2011) 108–117. https://doi.org/10.1080/09613218.2011.552269. Journal Pre-proof Highlights • Younger adults feel environment warmer and are less tolerant • There are 2.4ºC of difference between neutral temperature for older and younger adults. • Comfort zone for older people was wider than for adults. • Elderly from the different climates has different thermal perception • The real elderly thermal sensitivity was lower than PMV prediction model Journal Pre-proof Declaration of interests ☒ The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper. ☐The authors declare the following financial interests/personal relationships which may be considered as potential competing interests: Journal Pre-proof