Testing of high current transformer by non-uniform equivalent magnetomotive force method
Full text
19TH IMEKO TC-4 Measurements of Electrical Quantities 38 A real-time compensation method for MV voltage transducer for power quality analysis Gabriella Crotti96, Daniele Gallo97, Domenico Giordano96, Carmine Landi97, Mario Luiso97 The growing need of power quality analysis in medium voltage grids leads to the employment of transducers with wider and wider bandwidth. This requirement is in contrast with the need of adopting a low cost hardware for capillary monitoring. Therefore, in this paper a technique for the extension of the frequency bandwidth of a MV voltage divider is presented. The performance of the compensated divider is comparable with that of dividers of better accuracy class, but the cost is kept low. Ratio error and phase displacement of the Compensated Divider 11PE149 Testing of High Current Transformer by Non-uniform Equivalent Magnetomotive Force Method Kaifeng Qu98, Wei Zhao98, Bo Jiang99, Songling Huang98, Junjie Chen98 In the testing of high current transformer performance under interference from external current, it is very difficult to reproduce the high current from adjacent bus-bar or eccentric primary bus-bar. To overcome the difficulty, this manuscript presents an effective and original method called Non-uniform Equivalent Magnetomotive Force (NEMMF) Method, which uses a single non-uniformly distributed testing winding to reproduce the adjacent and concentric primary bus-bar simultaneously. The principle of the NEMMF method is verified by Finite Element Method (FEM). Magnetic circuit model in hypothetical equivalently homogeneous medium 11PE153