Energy management strategies based on fuzzy logic control for grid-tied domestic electro-thermal microgrid

Arcos Avilés, Diego Gustavo

Abstract

The environmental and economic benefits related to the reduction of both carbon dioxide emission and transmission losses have made distributed renewable generation systems became a competitive solution for future power systems. In this context, Microgrids (MG) are considered as the key building blocks of smart grids and have aroused great attention in the last decade for their potential and the impact they may have in the coming future. The MG concept has captured great attention in the last years since it can be considered one of the most suitable alternatives for integration of distributed generation units in the utility grid. However, this integration involves some challenges to deal with especially when penetration of Renewable Energy Sources (RES) into the distribution network is increased. Therefore, an effective Energy Management System (EMS) is required to ensure optimal energy utilization within the MG, consequently, facilitating both the grid integration and operator control. In this regard, the EMS strategy design depends on the application, MG power architecture, and the power management capability of the MG elements. This dissertation research focuses on the design of different EMS strategies based on Fuzzy Logic Control (FLC) for a residential grid-connected electro-thermal MG including renewable power generation (i.e. photovoltaic and wind turbine generators) and storage capability (i.e. battery bank and water storage tank). The main goal of the FLC-based EMS strategies is to minimize the grid power fluctuations while keeping the battery State-of-Charge (SOC) within secure limits. In order to accomplish this goal, the controller design parameters, such as membership functions and rule-base, of the FLC-based EMS strategies, are adjusted to optimize a pre-defined set of quality criteria of the MG behavior. The analysis and design of the FLC-based EMS strategies for electrical and electro-thermal MG power architectures are developed considering two different scenarios. A first scenario where the MG power forecasting is not provided and a second scenario where the forecast of generation power and load demand are considered. A comparison with the different EMS strategies is presented in simulation level, whereas the features of the enhanced FLC-based EMS strategies are experimentally tested on a real residential microgrid implemented at the Public University of Navarre (UPNa)

Full text

“ENERGY MANAGEMENT STRATEGIES BASED ON FUZZY LOGIC CONTROL FOR GRID-TIED DOMESTIC ELECTRO-THERMAL MICROGRID” PhD dissertation submitted for obtaining the Doctoral degree from the Universitat Politècnica de Catalunya, in the PhD program in Electronics Engineering Diego Gustavo Arcos Avilés Advisors: Francisco Juan Guinjoan Gispert (UPC) Luis María Marroyo Palomo (UPNa) June 2016 iii This work has been partially supported by the grant No. 2013-AR2Q4081, Secretaría Nacional de Educación Superior, Ciencia, Tecnología e Innovación SENESCYT and the Instituto de Fomento al Talento Humano of the Government of Ecuador. Part of this work has been carried out at the Laboratories of the Universidad Pública de Navarra v To Ale and Gabriel vii ACKNOWLEDGMENTS I would like to express my gratitude to my advisors Francesc Guinjoan and Luis Marroyo, for the motivation, enthusiasm, guidance, knowledge, support, and friendship throughout my time as a PhD. student. I would like to thank the Public University of Navarre and the INGEPER research group for hosting me during the experimental validation period. Especially thank to Julio Pascual for his patience and guidance. I would also like to thank my parents Caty and Chelo for their support and unconditional love during this difficult period of my life. Finally, I would like to thank the Secretaría Nacional de Educación Superior, Ciencia, Tecnología e Innovación (SENESCYT) and the Instituto de Fomento al Talento Humano of the Government of Ecuador by the scholarship No. 2013-AR2Q4081 from “Programa de becas para Docentes Universitarios”, which helped me for finishing my doctoral studies. ix ABSTRACT The environmental and economic benefits related to the reduction of both carbon dioxide emission and transmission losses have made distributed renewable generation systems became a competitive solution for future power systems. In this context, Microgrids (MG) are considered as the key building blocks of smart grids and have aroused great attention in the last decade for their potential and the impact they may have in the coming future. The MG concept has captured great attention in the last years since it can be considered one of the most suitable alternatives for integration of distributed generation units in the utility grid. However, this integration involves some challenges to deal with especially when penetration of Renewable Energy Sources (RES) into the distribution network is increased. Therefore, an effective Energy Management System (EMS) is required to ensure optimal energy utilization within the MG, consequently, facilitating both the grid integration and operator control. In this regard, the EMS strategy design depends on the application, MG power architecture, and the power management capability of the MG elements. This dissertation research focuses on the design of different EMS strategies based on Fuzzy Logic Control (FLC) for a residential grid-connected electro-thermal MG including renewable power generation (i.e. photovoltaic and wind turbine generators) and storage capability (i.e. battery bank and water storage tank). The main goal of the FLC-based EMS strategies is to minimize the grid power fluctuations while keeping the battery State-of-Charge (SOC) within secure limits. In order to accomplish this goal, the controller design parameters, such as membership functions and rule-base, of the FLC-based EMS strategies, are adjusted to optimize a pre-defined set of quality criteria of the MG behavior. The analysis and design of the FLC-based EMS strategies for electrical and electro-thermal MG power architectures are developed considering two different scenarios. A first scenario where the MG power forecasting is not provided and a second scenario where the forecast of generation power and load demand are considered. A comparison with the different EMS strategies is presented in simulation level, whereas the features of the enhanced FLC-based EMS strategies are experimentally tested on a real residential microgrid implemented at the Public University of Pamplona. xvi Contents 5.2.2. Controller design ................................................................................................... 101 5.2.3. Fuzzy logic controller design ................................................................................ 103 5.2.4. Simulation results and analysis ............................................................................. 104 CHAPTER 6 CONCLUSIONS AND FUTURE WORKS 109 6.1. Conclusions .................................................................................................................. 109 6.2. Future works ................................................................................................................ 111 6.3. Contributions ............................................................................................................... 112 REFERENCES 115 xvii FIGURE INDEX Fig. 1.1. World total primary energy supply from 1971 to 2013 by fuel (Mtoe), [1] © OECD/IEA, 2015 .......................................................................................................................... 1 Fig. 1.2. 1973 and 2013 fuel shares of TPES, [1] © OECD/IEA, 2015 ...................................... 1 Fig. 1.3. Annual growth rates of world renewable supply from 1990 to 2013, [4] © OECD/IEA, 2015 .......................................................................................................................... 2 Fig. 2.1. First topology, residential grid-connected microgrid .................................................. 10 Fig. 2.2. Second topology, residential grid-connected electro-thermal microgrid .................... 11 Fig. 2.3. UPNa microgrid configuration, component description and bus connections, © 2016, IEEE ............................................................................................................................................ 12 Fig. 2.4. Photovoltaic generator and wind turbine at UPNa ...................................................... 13 Fig. 2.5. Programmable load AMREL PLA7.5K-600-400 and simulation station ................... 13 Fig. 2.6. Lead-acid battery bank ................................................................................................ 14 Fig. 2.7. Hybrid power converter INGECON® HYBRID MS30 and switch cabinet which includes the control relays, power analyzers and digital indicators. ........................................... 14 Fig. 2.8. Components of the weather station (a) irradiance calibrated cell, (b) anemometer, and (c) Pt-100 temperature sensors. ................................................................................................... 15 Fig. 2.9. Supervisory and control station (a) NI-PXI frontal view, (b) monitoring and control station, (c) user interface, and (d) historic data acquired. ........................................................... 16 Fig. 2.10. Solar irradiance and solar irradiation ........................................................................ 17 Fig. 2.11. Solar cell, PV module, PV panel and PV array ......................................................... 17 Fig. 2.12. Battery SOC estimator block diagram ...................................................................... 20 Fig. 2.13. Photovoltaic power measured at UPNa microgrid .................................................... 23 Fig. 2.14. Wind turbine power measured at UPNa microgrid ................................................... 23 Fig. 2.15. Rate of energy collected from the solar thermal collectors ....................................... 24 Fig. 2.16. Electric load demand profile (a) excluding the EWH consumption, and (b) including the EWH consumption ................................................................................................................ 25 Fig. 2.17. Domestic hot water demand ...................................................................................... 25 Fig. 3.1. Net power profile (a) excluding the EWH consumption, and (b) including the EWH consumption ................................................................................................................................ 28 Fig. 3.2. Grid power profile ramp-rates for a MG with neither ESS nor energy management strategy (a) excluding the EWH consumption, and (b) including the EWH consumption ......... 32 Fig. 3.3. Simple moving average strategy block diagram ......................................................... 33 xviii Figure index Fig. 3.4. Simulation results of the SMA strategy excluding the EWH consumption (a) grid power profile, (b) battery SOC, and (c) grid power profile ramp-rates ...................................... 34 Fig. 3.5. Simulation results of the SMA strategy including the EWH consumption (a) grid power profile, (b) battery SOC, and (c) grid power profile ramp-rates. ..................................... 35 Fig. 3.6. Fuzzy energy management strategy based on MG NPT block diagram ..................... 36 Fig. 3.7. Membership functions for the FLC inputs of the fuzzy NPT strategy (a) MFs for the input PLG (n), (b) MFs for the input SOC (n), and (c) MFs for the input PAVG (n), © 2014, IEEE38 Fig. 3.8. MFs for the FLC output of the fuzzy NPT strategy, © 2014, IEEE ............................ 39 Fig. 3.9. Simulation results of the fuzzy NPT strategy excluding the EWH consumption (a) grid power profile, (b) battery SOC, (c) grid power profile ramp-rates comparison, and (d) maximum grid power profile ramp-rate. ..................................................................................... 41 Fig. 3.10. Simulation results of the fuzzy NPT strategy including the EWH consumption (a) grid power profile, (b) battery SOC, (c) grid power profile ramp-rates comparison, and (d) maximum grid power profile ramp-rate. ..................................................................................... 42 Fig. 3.11. Slopes by two consecutive samples (red solid line) of the average net power profile (blue solid line). © 2016, IEEE. .................................................................................................. 44 Fig. 3.12. Fuzzy ERoC strategy block diagram, © 2016, IEEE ................................................ 45 Fig. 3.13. Initial MFs for the FLC input variable ṖAVG.............................................................. 47 Fig. 3.14. Initial MFs for the FLC input variable battery SOC ................................................. 47 Fig. 3.15. Initial definition and distribution of the ZE fuzzy subset of the FLC output ............ 49 Fig. 3.16. Initial fuzzy rule-base and grid power variation with respect to the FLC inputs ...... 50 Fig. 3.17. Initial definition and distribution of the positive MFs for the FLC output ............... 51 Fig. 3.18. Initial definition and distribution of the MFs for the FLC output ............................. 52 Fig. 3.19. Triangular membership function parameters ............................................................ 53 Fig. 3.20. Mapping parameters for the MFs of the SOC input .................................................. 53 Fig. 3.21. Optimized MFs for the input variable ṖAVG, © 2016, IEEE ...................................... 54 Fig. 3.22. Optimized MFs for the input variable SOC, © 2016, IEEE ...................................... 54 Fig. 3.23. Optimized MFs for the FLC output PFLC, © 2016, IEEE .......................................... 55 Fig. 3.24. Optimization of the rules 7, 8 and 9 .......................................................................... 55 Fig. 3.25. Simulation results and comparison for the SMA strategy (top), the fuzzy NPT strategy (middle), and the fuzzy ERoC strategy (bottom), (a) grid power profile, and (b) battery SOC ............................................................................................................................................. 57 Fig. 3.26. Annual frequency of the battery SOC ranges established from the SMA, fuzzy NPT, and fuzzy ERoC strategies including the EWH consumption ..................................................... 57 Fig. 3.27. Improved behavior of the fuzzy ERoC strategy with respect to the SMA and fuzzy NPT strategies ............................................................................................................................. 58 Fig. 3.28. Influence of the derivative input in the grid power profile, © 2016, IEEE ............... 58 Figure index xix Fig. 3.29. Simulation results for the fuzzy ERoC strategy excluding the EWH consumption (a) grid power profile ramp-rates comparison, and (b) maximum grid power profile ramp-rate. .... 59 Fig. 3.30. Simulation results for the fuzzy ERoC strategy including the EWH consumption (a) grid power profile, (b) battery SOC, (c) annual frequency of the battery SOC ranges established from the defined EMS strategies, (d) grid power profile ramp-rates comparison, and (e) maximum grid power profile ramp-rate. ..................................................................................... 61 Fig. 3.31. Fuzzy logic controller design through LabVIEW® platform and the Fuzzy System Designer toolbox ......................................................................................................................... 62 Fig. 3.32. MFs number, type, name, mapping and variation range assignment (a) MFs for the input variable ṖAVG, (b) MFs for the input variable SOC, and (c) MFs for the output variable PFLC .............................................................................................................................................. 62 Fig. 3.33. Final FLC design (a) rule-base definition and, (b) FLC testing and surface ............. 62 Fig. 3.34. Experimental results obtained from UPNa MG (a) photovoltaic power, (b) wind turbine power, (c) renewable power generation, (d) load power, and (d) MG net power. .......... 63 Fig. 3.35. Simulated and experimental grid power profile comparison, © 2016, IEEE ............ 64 Fig. 3.36. Experimental validation of the fuzzy ERoC strategy, © 2016, IEEE ....................... 64 Fig. 3.37. Real power variables and battery SOC measured at UPNa MG on February 10th, 2015, © 2016, IEEE .................................................................................................................... 65 Fig. 4.1. Solar irradiance in the year under study (a) forecast of the incident solar irradiance on a horizontal surface provided by Meteogalicia, and (b) forecast of the incident solar irradiance on an inclined surface at UPNa, .................................................................................................. 68 Fig. 4.2. Comparison between the forecasted and measured data of the incident solar irradiance on an inclined surface at UPNa ................................................................................................... 68 Fig. 4.3. Forecast of photovoltaic power (a) during the year under study, and (b) comparison between forecasted and measured data ....................................................................................... 69 Fig. 4.4. Forecast of wind turbine power (a) during the year under study, and (b) comparison between forecasted and measured data ....................................................................................... 70 Fig. 4.5. Forecast of power generation (a) during the year under study, and (b) comparison between forecasted and measured data ....................................................................................... 71 Fig. 4.6. Comparison between the predicted load power demand and the load power demand measured at UPNa microgrid (a) winter season data, and (b) summer season data .................... 72 Fig. 4.7. Comparison between the prediction of the MG net power and the MG net power measured at UPNa microgrid ...................................................................................................... 73 Fig. 4.8. Fuzzy EMS based on MG power forecasting block diagram ...................................... 73 Fig. 4.9. Optimized MFs for the FLC inputs of the fuzzy EMS-FC strategy (a) MG forecast error, and (b) battery SOC ........................................................................................................... 76 xx Figure index Fig. 4.10. MFs for the FLC output of the fuzzy EMS-FC strategy ........................................... 77 Fig. 4.11. Grid power profile comparison for the SMA, the fuzzy NPT, the fuzzy ERoC and the fuzzy EMS-FC strategies....................................................................................................... 78 Fig. 4.12. Improved grid power profile evolution of the fuzzy EMS-FC strategy with respect to the fuzzy ERoC strategy .............................................................................................................. 79 Fig. 4.13. Battery SOC evolution during the year under study (a) SMA strategy, (b) fuzzy NPT strategy, (c) fuzzy ERoC strategy, and (d) fuzzy EMS-FC strategy ........................................... 80 Fig. 4.14. Daily average profile of the battery SOC during the year under study (a) SMA strategy, (b) fuzzy NPT strategy, (c) fuzzy ERoC strategy, and (d) fuzzy EMS-FC strategy ..... 81 Fig. 4.15. Annual frequency of the battery SOC ranges established from the SMA, fuzzy NPT, fuzzy ERoC, and fuzzy EMS-FC strategies including the EWH consumption .......................... 82 Fig. 4.16. Simulation results for the fuzzy EMS-FC strategy excluding the EWH consumption (a) grid power ramp-rates comparison, (b) grid power ramp-rates comparison with respect to the fuzzy ERoC strategy, and (c) maximum grid power profile ramp-rate ....................................... 83 Fig. 4.17. Simulation results accomplished through the defined EMS strategies including the EWH (a) grid power comparison, (b) battery SOC comparison, and (c) annual frequency of the battery SOC ranges ..................................................................................................................... 84 Fig. 4.18. Simulation results for the fuzzy EMS-FC strategy including the EWH consumption (a) grid power ramp-rates comparison with respect to the designed EMSs, (b) grid power ramprates comparison with respect to the fuzzy ERoC strategy, and (c) maximum grid power profile ramp-rate ..................................................................................................................................... 85 Fig. 4.19. Forecasted and measured data obtained at UPNa MG from Sep. 08th to Sep.14th, 2015. (a) Photovoltaic power, (b) wind turbine power, (c) load power, and (d) MG net power. 86 Fig. 4.20. Experimental results through the fuzzy EMS-FC strategy from Sep. 8th to Sep. 14, 2015 at UPNa MG ....................................................................................................................... 87 Fig. 4.21. Forecasted and measured data obtained at UPNa MG from Oct. 10th to Oct. 25th, 2015 (a) PV power generation, (b) WT power generation, (c) load demand, and (d) MG net power and resulting grid power profile ....................................................................................... 88 Fig. 4.22. Experimental results achieved through the fuzzy EMS based on MG power forecasting from Oct. 10th to Oct. 25th, 2015 at UPNa MG ......................................................... 88 Fig. 5.1. Residential grid-connected electro-thermal microgrid ................................................ 89 Fig. 5.2. Block diagram of the Fuzzy ERoC strategy applied to an electro-thermal microgrid 92 Fig. 5.3. MFs of the FLC for the fuzzy ERoC strategy applied to an electro-thermal MG (a) MFs for the input variable Ṗ*AVG, (b) MFs for the input variable SOC, and (c) MFs for the output variable PFLC ................................................................................................................................ 94 Figure index xxi Fig. 5.4. MG net power profile (a) comparison between the MG net power including the EWH consumption and the modified MG net power achieved through the fuzzy ERoC strategy applied to an electro-thermal MG, (b) reduction of the MG net power profile ........................... 95 Fig. 5.5. Battery power comparison between the fuzzy ERoC strategy including the EWH consumption and the fuzzy ERoC strategy applied to an electro-thermal MG ........................... 96 Fig. 5.6. Distribution of the energy required for the EWH in two different periods of the year under study .................................................................................................................................. 96 Fig. 5.7. Grid power profile and battery SOC comparison for the SMA, the fuzzy NPT, and the fuzzy ERoC strategies including the EWH consumption and the fuzzy ERoC strategy applied to an electro-thermal MG ................................................................................................................ 97 Fig. 5.8. Annual frequency of the battery SOC ranges established through the SMA, fuzzy NPT, fuzzy ERoC strategies including the EWH consumption and the fuzzy ERoC strategy applied to an electro-thermal MG ............................................................................................... 98 Fig. 5.9. Grid power profile and battery SOC comparison between the fuzzy ERoC strategy including the EWH consumption and the fuzzy ERoC strategy applied to an electro-thermal MG ..................................................................................................................................................... 98 Fig. 5.10. Grid power profile ramp-rates analysis (a) grid power ramp-rates comparison for the described EMS strategies, (b) grid power ramp-rates comparison with respect to the fuzzy ERoC strategy including the EWH consumption, and (c) maximum grid power profile ramp-rate achieved through the fuzzy ERoC ETH-MG strategy ............................................................... 100 Fig. 5.11. Block diagram of the Fuzzy EMS-FC strategy applied to an electro-thermal microgrid ................................................................................................................................... 101 Fig. 5.12. Net power forecasting block diagram ..................................................................... 102 Fig. 5.13. Fuzzy logic system: 2 inputs, 1 output, and 25-rules .............................................. 104 Fig. 5.14. Comparison between the initial and the modified variables of the MG (a) load demand comparison, (b) load demand forecast comparison, (c) MG net power comparison, and (d) forecast of the MG net power comparison .......................................................................... 105 Fig. 5.15. (a) Initial and modified average net power of the MG, (b) Grid power profile comparison between the fuzzy EMS-FC strategy including the EWH consumption and the fuzzy EMS-FC strategy applied to an electro-thermal MG ................................................................ 105 Fig. 5.16. Grid power profile and battery SOC comparison for the SMA, the fuzzy NPT, the fuzzy ERoC, and the fuzzy EMS-FC strategies including the EWH consumption and the fuzzy EMS-FC strategy applied to an electro-thermal MG ................................................................ 106 Fig. 5.17. (a) Contribution of the energy required by the EWH achieved through the fuzzy EMS-FC ETH-MG strategy, (b) Annual frequency of the battery SOC ranges achieved through xxii Figure index the SMA, fuzzy NPT, fuzzy ERoC, the fuzzy EMS-FC strategies including the EWH consumption and the fuzzy EMS-FC strategy applied to an electro-thermal MG .................... 107 Fig. 5.18. Grid power profile ramp-rates analysis (a) grid power ramp-rates comparison for the described EMS strategies, (b) grid power ramp-rates comparison for the fuzzy ERoC, the fuzzy EMS-FC strategies including the EWH consumption and the fuzzy EMS-FC ETH-MG strategy, (c) comparison of the grid power profile ramp-rates between the fuzzy EMS-FC including the EWH consumption and the fuzzy EMS-FC ETH-MG strategy, and (d) maximum grid power profile ramp-rate achieved through the fuzzy EMS-FC strategy applied to an electro-thermal MG ................................................................................................................... 108 xxiii TABLE INDEX Table 3-1 Evaluation quality criteria values (baseline values) .................................................. 31 Table 3-2 Quality criteria comparison between SMA strategy and baseline values excluding the EWH consumption ................................................................................................................ 34 Table 3-3 Quality criteria comparison between SMA strategy and the baseline values including the EWH consumption ................................................................................................................ 35 Table 3-4 FLC rule-base for the fuzzy NPT strategy ................................................................ 40 Table 3-5 Quality criteria comparison for the fuzzy NPT strategy, the SMA strategy and the baseline values excluding the EWH consumption ...................................................................... 41 Table 3-6 Quality criteria comparison for the fuzzy NPT strategy, the SMA strategy and the baseline values including the EWH consumption ....................................................................... 42 Table 3-7 Impact of the FLC output on the grid power profile, © 2016, IEEE ........................ 45 Table 3-8 Initial FLC rule-base of the fuzzy ERoC strategy, © 2015, IEEE ............................ 52 Table 3-9 Optimized rule-base for the FLC of the fuzzy ERoC strategy, © 2016, IEEE ......... 56 Table 3-10 Quality criteria comparison for the fuzzy ERoC strategy, the fuzzy NPT strategy, the SMA strategy and the baseline values excluding the EWH consumption ............................ 59 Table 3-11 Quality criteria comparison for the fuzzy ERoC strategy, the fuzzy NPT strategy, the SMA strategy and the baseline values including the EWH consumption ............................. 60 Table 4-1 Optimized rule-base for the fuzzy EMS based on MG power forecasting ............... 77 Table 4-2 Quality criteria comparison for the fuzzy EMS-FC strategy, the fuzzy ERoC strategy, the fuzzy NPT strategy, the SMA strategy and the baseline values excluding the EWH consumption ................................................................................................................................ 82 Table 4-3 Quality criteria comparison for the fuzzy EMS-FC strategy, the fuzzy ERoC strategy, the fuzzy NPT strategy, the SMA strategy and the baseline values including the EWH consumption ................................................................................................................................ 85 Table 5-1 Optimized fuzzy rule-base of the FLC for the fuzzy ERoC strategy applied to an electro-thermal microgrid ............................................................................................................ 95 Table 5-2 Quality criteria comparison for the fuzzy ERoC strategy applied to an electrothermal microgrid, the fuzzy ERoC, the fuzzy NPT strategy, the SMA strategy and the baseline values including the EWH consumption ..................................................................................... 99 Table 5-3 Optimized fuzzy rule-base for the FLC of the fuzzy EMS-FC strategy applied to an electro-thermal microgrid .......................................................................................................... 103 xxiv Table index Table 5-4 Quality criteria comparison for the fuzzy EMS-FC strategy applied to an electrothermal microgrid, the fuzzy EMS-FC strategy, the fuzzy ERoC strategy, the fuzzy NPT strategy, the SMA strategy and the baseline values including the EWH consumption ............. 107 xxv NOMENCLATURE Constants A WT rotor swept area DOD Maximum battery Depth of Discharge ∆T Integration period fi, ff Initial and final frequency limits for computing PPV criterion GSTC Incident irradiance under STC γ Power temperature coefficient k Maximum power assigned by the controller output of the fuzzy ERoC strategy kB Maximum power assigned by the controller output of the fuzzy NPT strategy ke Proportional gain of the battery control loop kT Thermal conductivity of the water storage tank L Length of the water storage tank M Number of samples in one day M3 Number of samples in 3-hours M12 Number of samples in 12-hours m Molar mass of the air N Number of samples in a year p Atmospheric pressure Pe Maximum forecast error PSTC Output power of PV array under STC R Universal gas constant R1 Inner radius of the water storage tank R2 Outer radius of the water storage tank ρ Air density SOCMIN Minimum battery SOC allowed SOCMAX Maximum battery SOC allowed SOCREF Battery SOC reference value SOCR1 Threshold which allows the power injection from storage state of charge TEXT Ambient temperature where the water storage tank is located Ts Sampling period TSTC Temperature under STC TW Timing window for one day Tweek Sampling period of one week 2 Chapter 1 carbon dioxide CO2). According to IEA the use of energy represents by far the largest source of GHG emissions [2]. Therefore, countries all over the world are implementing targets for GHG emission reduction, improved energy efficiency, and increased clean energy production [3]. As a result of these initiatives, the use of Renewable Energy Sources (RES) has increased in the last decades, being Photovoltaic (PV) and Wind power the kind of RES that has had the greatest growth with average annual rates of 46.6% and 24.8%, respectively, since the year 1990 [4], as shown in Fig. 1.3. In this regard, the IEA reports that the Organisation for Economic Cooperation and Development (OECD) countries account for most of the world production and growth of PV and wind energy [4]. Fig. 1.3. Annual growth rates of world renewable supply from 1990 to 2013, [4] © OECD/IEA, 2015 In this concern, the benefits that RES (e.g. photovoltaic, wind turbines…) have exhibited in the last years, such as reducing the fuel consumption and the GHG emissions [5], have contributed with the Distributed Generation (DG) systems to become a competitive solution for the future power systems (i.e. Smart Grids) [6], since they can produce electrical power with less environmental impacts, they are easy to install, and they are highly efficient with increased reliability [7], [8]. However, the adaptation of the utility grid to integrate them in a distributed, efficient and reliable manner without excessive investment still remains a challenge [9]. The Microgrid (MG) concept is a quite appealing alternative for overcoming the challenges of integrating Distributed Energy Resources (DER) units, including RES, into power systems [10], [11]. In this context, MGs are emerging as an integral feature of the upcoming power systems shaped by the various smart grid initiatives [12]. The concept of MG was first defined in the literature in [13] and [14] as the cluster of micro-sources, loads and storage systems operating as a single controllable system that can respond to central control signals. However, this concept has been discussed by several authors Introduction and objectives 3 [3], [11], [15]–[17]. At the present, the MG concept follows a similar philosophy that of smart grid one and their research will benefit the smart grid technology development [18]. In general, MGs are defined as low-voltage distribution network comprising loads, DG units and Energy Storage System (ESS) (e.g. batteries, flywheels, ultra-capacitors…), that are connected to the mains at a single Point of Common Coupling (PCC) [15], [19], and that include an Energy Management System (EMS) associated, which is responsible for the reliable, secure and economic operation of the MG [10], [20]. MGs are capable to operate in both gridconnected and stand-alone modes [14], [16]. According to [21], in grid-connected mode, the MG adjusts power balance of supply and demand by purchasing or selling power to the main grid in order to maximize operational benefits [22], [23]. Conversely, in stand-alone mode, where the MG is separated from the distribution network, the MG is in charge of keeping a reliable power supply to customers [24]. The EMS is in charge of controlling the power fluxes among the MG elements to reach a set of predefined objectives such as minimizing the MG operating costs [25], [26] or maximizing the revenues according to DG’ bids and electricity market price [21]. Additionally, the EMS design should take into account the MG power architecture and, in particular, the power management capability of the elements within the MG (i.e. which sources, loads and storage elements can be controlled). Once the power architecture and the predefined objectives are known, the EMS design can be undertaken by applying different methods [8], [10], [12], [20], [27]–[30]. In this regard, there is a wide variety of works handling different scenarios in terms of power architectures, objectives and methods. For instance in [31] an EMS strategy is designed by using local prediction and local forecasting as well as Stochastic Dynamic Programming (SDP) to control and extend the lifetime of an ESS included in a grid-connected MG with diesel an renewable generation. Moreover, in [32] the design of the EMS strategy focuses on controlling through a predictive control technique the ESS to compensate the hourly deviations of a forecasted energy plan in a grid-connected MG. Other studies consider scenarios with more degrees of freedom where the EMS drives different storage elements (e.g. batteries, fuel cells…), controllable loads (e.g. electrical load management, heat pumps…) or a combination of both as in [22], [33]–[37], to carry out Demand Side Management (DSM) and Demand Response (DR) strategies. The control methods used in this case are usually sophisticated as Model Predictive Control (MPC) and, include both generation and demand forecasting as in [38], [39]. In addition, Fuzzy Logic Control (FLC) has also been applied to the design of EMS for both stand-alone and grid-connected modes. For instance, [40]–[42] presents a fuzzy-based EMS 4 Chapter 1 applied to stand-alone MG, whereas [43] presents an EMS with fuzzy control for a DC MG, where the FLC is designed for both prioritizing selling additional electricity generated by Renewable Energy Sources (RES) and maintaining the battery State of Charge (SOC) above 50% to extend its life. Moreover, [44] presents an EMS where the FLC considers the evolution of the prices during one day, the energy demand, the production and the time of the day in order to ensure an affordable grid. It can be noticed form the literature that smoothing the power exchanged with the grid is generally not addressed as the main objective of the EMS strategy, since most of the studies focus on the economic achievement of the MG. However, new regulations for grid-connected systems with RES [45] require the control of the ramp-rates of the power generation and the quality support of the mains [46]. Thus, smoothing the grid power profile becomes an additional challenge for the EMS. This new challenge, i.e., smoothing the grid power profile, can be considered a suitable solution in a residential MG scenario facilitating the grid operators control and consequently the penetration of RES into the distribution network. In addition, the grid power profile control allows residential consumers generate their own energy causing the minimization of the amount of energy consumed from the utility grid, thus, reducing their electricity bill [47]. In this concern, the studies developed in [36], [37], [48]–[57] focus on minimizing the power peaks and fluctuations of the power exchanged with the grid. The first approach to smooth the power profile exchanged with the grid is performed by the Simple Moving Average (SMA) strategy [49]. This strategy uses a Low Pass Filter (LPF) to separate the low- and high-frequency components of the grid power profile via a simple moving average filter with a window size of one day [36]. Thus, the high-frequency component is handled by the ESS and the low-frequency component is exchanged with the grid. However, this strategy does not consider the state-of-Charge (SOC) of the ESS, causing the operation of the ESS outside secure limits compromising its lifetime. Alternatively, [50] suggests an EMS strategy design based on an heuristic knowledge of the desired behavior of the MG, where the amount of power assigned to the grid and to the storage system is computed by means of heuristically adjustable analytical expressions involving the power balance between consumption and generation as well as the battery SOC as main variables. This strategy reduces the fluctuations of the power exchange with the grid with respect the SMA strategy. However, it leads to a highly fluctuating grid power profile. This heuristic knowledge suggests the use of FLC for the design of the EMS strategy in a residential grid-connected scenario. In this regard, fuzzy logic provides a formal methodology Introduction and objectives 5 for representing, manipulating, computing, and implementing a human’s heuristic knowledge about how to control a system [58], [59]. In addition, it is a powerful control technique capable of dealing with the imprecisions and nonlinearity of complex systems, that can be based on experience of the user about the system behavior rather than the mathematical model of the system as in the traditional control theory [60], [61]. In this concern, considering the same inputs variables as in [50], the author presented in [51] an EMS strategy based on FLC, which includes the design of a two-input one-output FLC and 25-rules, which slightly improves the battery SOC and the grid power profile obtained in [50]. This study presented a detailed description for the design of the Membership Functions (MF) and rule-base, which parameters such as number of MFs per input, mapping, and dynamic range were adjusted to optimize a set of quality criteria of the MG behavior through an off-line learning-process simulation [54]. Furthermore, using the same design methodology, a new EMS based on FLC is presented in [52], this design improves the results obtained in [51] through the inclusion of supplementary information into the FLC. This new design was considering the MG Net Power Trend (NPT) as an additional input of the FLC, resulting in a 50-rules FLC. Even though the results evidence a low-frequency grid power profile with minimum fluctuations, the new input increases the controller complexity [54]. Therefore, with the aim of improving the aforementioned designs as well as simplifying the FLC complexity (i.e. to reduce the controller inputs number and its rule-base), an enhanced EMS strategy based on FLC of two inputs, one output and 25 rules is presented by the author in [53] and an extended version including experimental validation results is presented in [54]. The key factor of the improved design is to consider the MG Energy Rate-of-Change (ERoC) as a FLC input in order to anticipate the system behavior. This design allows quick reaction of the EMS against the MG energy changes in order to set the battery SOC close to the 75% of the rated battery capacity and smoothing the grid power profile. As aforementioned, the increase of both number of controllable elements within the MG and the information handled by the EMS strategy leads to the increase of the available degrees of freedom for the MG control, which facilitates the improvement of the grid power profile [50]. For instance, [37] develops a DR coordination control algorithm that uses controllable resources and ESS to compensate power fluctuations produced by RES to provide tie-line services. In addition, [50] presents an EMS strategy for an electro-thermal MG comprising of RES, ESS and thermal elements such as solar thermal collectors and Electric Water Heater (EWH). Moreover, following the same procedure than [51], the author presents in [55], [56] a 6 Chapter 1 fuzzy-based EMS strategy for an electro-thermal MG, where results slightly improve to those presented in [50]. Furthermore, an improved strategy for that seen in [50], [51] is designed in [36] which improves significantly the power profile exchanged with the grid by the use of both DSM and a variable battery SOC with the purpose of compensating seasonal fluctuations of the MG net power. Finally, to directly address the problems produced by previous strategies, [57] presents an enhanced EMS strategy, which uses a Central Moving Average (CMA) filter, the cumulative forecast error, and the battery SOC to minimize the fluctuation in the grid power profile. This dissertation presents the analysis, design, and comparison of the research work carried out by the author and partly referred in the publications cited above for smoothing the power profile exchanged with the grid of a residential grid-connected MG. Moreover, presents an enhanced EMS design based on FLC and microgrid power forecasting for conducting the same objective. In addition, this dissertation presents the experimental results achieved by the fuzzy-based EMS strategies, which were obtained in the MG installed at the Public University of Navarre (UPNa). Finally, presents the analysis and design of the improved fuzzy EMS strategies applied to an electro-thermal MG scenario. 1.2. Dissertation aim and objectives 1.2.1. Aim The aim of this research is the design of energy management strategies based on Fuzzy Logic Control for smoothing the grid power profile of a residential grid-connected microgrid including renewable energy sources, energy storage system, and electrical and thermal load demand. 1.2.2. Objectives The following objectives have been defined in order to achieve the aim cited above: • Definition of a set of quality criteria for quantifying the improvement of the grid power profile achieved through an EMS strategy. • Inclusion of the information related with the power fluctuations within the MG into the EMS strategy. • Analysis of the effect of using generation and demand forecasts on the power profile exchanged with the grid. • Simulation comparison according to the defined quality criteria of the grid power profile resulting from the fuzzy-based EMS designed strategies. Introduction and objectives 7 • Experimental validation in a real MG of several fuzzy-based EMS designed strategies. • Analysis of the extension of the FLC EMS strategies to an electro-thermal MG scenario. 1.3. Dissertation outline This dissertation research work is organized as follows: Chapter 2 describes the residential microgrid architectures under study. It also presents the complete description the elements of the MG installed at UPNa. In addition, it presents the mathematical models of the main elements of the MG such as RES and ESS. Finally, it includes the recorded data of power generation and load demand for the year under analysis. Chapter 3 presents on the one hand the problem formulation to solve and defines a set of energy management quality criteria, which are used to quantify the improvement of an EMS strategy. On the other hand it presents the analysis and design of Net Power Trend-based (NPT) and Energy Rate of Change (ERoC) FLC-based strategies. Subsequently, the chapter includes a simulation comparison among the features of SMA, NPT and ERoC strategies. The experimental validation of the improved fuzzy-based EMS ERoC strategy is presented at the end of this chapter. Chapter 4 presents the analysis and design of an enhanced fuzzy-based EMS strategy based on MG power forecasting (i.e. fuzzy EMS-FC). It describes the forecasting method used to estimate the power generation and load demand, which are based on weather forecasting and persistence method, respectively. It also presents the simulation results and comparison with the EMS strategies described in Chapter 3. Finally, the chapter concludes with the experimental validation of the fuzzy-based EMS strategy based on MG power forecasting. Chapter 5 presents the design extension of the fuzzy EMS strategies applied to an electro-thermal MG scenario. Simulation results and comparison of the fuzzy ERoC and fuzzy EMS-FC strategies in an electro-thermal MG are included at the end of the chapter. Finally, Chapter 6 summarizes the main conclusions of this study. It also suggests possible future lines to pursue this research. 9 Chapter 2 Residential grid-connected microgrid description This Chapter describes the electrical and electro-thermal microgrids of a residential grid-connected MG under study installed at UPNa. This description includes both, the architectures and the information of each physical element of the microgrid, which will be further used in the experimental validations of the several of the EMS strategies designed in Chapter 3 and 4. In addition, this Chapter presents the mathematical models of renewable generators and ESS which are respectively used to calculate the power generation forecast and the state-of-charge of the storage elements resulting from the EMS. Finally, the Chapter presents the records of MG power generation and load demand for the year under study, which were measured and recorded at UPNa. These data will be used to compare the different energy management strategies described in Chapters 3 and 4. 2.1. Electric and Electro-thermal microgrid configuration 2.1.1. Electric microgrid description The first architecture under study is a residential grid-connected MG [52], [54], [53], [62], [63], [51], [50], [57], which includes an Hybrid Renewable Energy System (HRES), a domestic demand and an ESS. The MG configuration is shown in Fig. 2.1 and includes the following elements: • An HRES, which includes a Photovoltaic Generator (PV) of 6 kWp and a small Wind Turbine (WT) of 6 kW. • An ESS, which consists of a lead-acid battery bank with a rated capacity of 72 kWh. • A domestic load demand, which involves typical electrical loads (e.g. electrical appliances, lighting…) with a rated power of 7 kW. 10 Chapter 2 Fig. 2.1. First architecture, residential grid-connected microgrid From Fig. 2.1, on the supply side, PPV and PWT represent the photovoltaic and wind power generation, respectively, PBAT represents the power delivered/absorbed by the battery, and PGRID represents the power delivered/injected by/to the mains. On the demand side, PLOAD stands for the load power demand required by the electric loads. Note that the power variables involved in Fig. 2.1 are considered positive when the power flows according to the direction of the corresponding arrows. Therefore, the power generated by both renewable generators, PPV and PWT, and the power consumed by the electric loads, PLOAD, are always positive. Additionally, PBAT is considered positive when the battery injects power to the MG (i.e. discharging process) and it is considered negative when the battery absorbs power from the MG (i.e. charging process). Finally, PGRID is considered positive when the grid delivers power to the MG and it is negative when the grid absorbs power from the MG. A complete description of the elements belonging to the MG is presented in section 2.2. Given the configuration shown in Fig. 2.1, the power exchanged with the mains, PGRID, could be defined as follows: , GRID LOAD GEN BAT P P PP= −− (2.1) , GEN PV WT P PP= + (2.2) being PGEN the total renewable power generation in the MG. In addition, defining the MG net power (i.e. PLG) as the difference between consumption and generation power, the grid power profile for the first architecture expressed in (2.1) can be rewritten as: Residential grid-connected microgrid description 11 , LG LOAD GEN PP P= − (2.3) . GRID LG BAT P PP = − (2.4) 2.1.2. Electro-thermal microgrid description The second architecture under study is a residential grid-connected electro-thermal MG [50], [55], [56], [36], which comprises the elements described in the first architecture and includes a Domestic Hot Water (DHW) system consisting of an Electric Water Heater (EWH) of 2 kW, a flat plate solar thermal collector array of 2 kW, and a thermal storage system represented by a water storage tank with a capacity of 800 liters. The electro-thermal MG configuration is shown in Fig. 2.2. Fig. 2.2. Second architecture, residential grid-connected electro-thermal microgrid where PWH,E is the power required by the EWH to maintain the water temperature in the storage tank between 45 °C and 65 °C, QWH,T is the rate of energy transferred from the EWH, QSC is the rate of energy collected from the solar thermal collectors, and QDHW is the domestic hot water consumption. 18 Chapter 2 where PSTC is the output power of the PV array under Standard Test Conditions (STC), G(β,α) is the incident irradiance in the plane of the panels, GSTC is incident irradiance under STC, γ is the power temperature coefficient, TSTC is the temperature under STC, and TC is the cell temperature in ºC, which can be evaluated using as follows [71], [74]: ()()( ) , 273 20 , 800 Ca G T T NOCT βα =−+ ⋅ − (2.9) where Ta is the ambient temperature in K, and NOCT is the Nominal Operating Cell Temperature in °C. Note that the values of PSTC, γ and NOCT are provided by the panel manufacturer. In contrast, the local observatories usually provide the weather report of incident solar irradiance on a horizontal plane G0. Thus, in order to obtain the photovoltaic power generation by means of (2.8) and (2.9) it is necessary to transform the solar irradiance on a horizontal plane, G0, into the solar irradiance on an tilted surface, G(β,α). In his regard, the process described in [75] can be used to perform this transformation. 2.3.2. Wind turbine model The energy available in wind is essentially the kinetic energy of large masses of air moving over the earth’s surface [76]. The kinetic energy is transformed by the blades of the wind turbine into mechanical or electrical energy, depending on the end use. Therefore, for electrical applications the output power of a wind turbine can be estimated as follows [77], [78]: 3 , () 1, 2 WT p WT Z P AC v= ⋅ρ⋅ ⋅ ⋅ (2.10) where PWT is the output power of the wind turbine, ρ is the air density, v(Z) is the wind speed at the wind turbine hub-height, A is the rotor swept area and, CP,WT is the power coefficient of the wind turbine. Note that A and CP,WT are provided by the WT manufacturer. Equation (2.10) evidences that the available power of a wind turbine could be affected by the wind speed, which is most prominent given its cubic relationship with the power, the rotor swept area, the power coefficient of the wind turbine and the air density. In this regard, factors such as the temperature and the atmospheric pressure affect the air density. Therefore, the air density ρ can be written as [76]: , a mp TR ⋅ ρ= ⋅ (2.11) Residential grid-connected microgrid description 19 where m is the molar mass of the air, p is the atmospheric pressure and, R is the universal gas constant. Moreover, wind speeds provided by the local observatories are usually measured at a height of 10 m above the ground. Therefore, the measured wind speed has to be extrapolated to the wind turbine hub-height, thus, wind turbines usually operate at a hub-height greater than 10 m. For this purpose, the relationship for the frictional terrain resistances, the height of the measured data and the wind turbine hub-height is expressed as follows [76], [78], [79]: ( ) () 0 () ( ) 0 ln , ln REF ZZ REF ZZ vv ZZ = ⋅ (2.12) where v(ZREF) is the wind speed at ZREF height, ZREF is the height at the measured data, Z is the turbine hub-height, and Z0 is the roughness index of the terrain [80]. 2.3.3. Battery bank model The ESS is one of the principal components to be considered for a successful operation of the MG. The ESS is used to balance out the irregularities and to improve the grid power quality. The ESS acts as a buffer or back-up storing the energy that can then be used to provide electricity during the period of high demand [71], [12]. The Battery Energy Storage System (BEES) stores energy as a charge in electrochemical cells, where the desired capacity and voltage can be achieved through the connection of them in series or parallel or both [71]. In this context, lead-acid batteries are eminently suitable for medium- and large-scale energy storage operations, because they offer an acceptable combination of performance parameters at a cost that is substantially below of those of an alternative system [81]. Typically lead-acid batteries have columbic (Ah) efficiencies around 85% and energy (Wh) efficiencies of around 70% over most of the SOC range, and they exhibit a self-discharge of between 1% and 5% per month at a temperature of 20 °C. The practical operational life of lead-acid battery depends on the Depth of Discharge (DOD) range and temperature to which is exposed. In addition, the batteries operation over a reduced range of DOD generally leads to a longer cycle-life than service over a wide range [81]. The battery SOC gives the estimation about the amount of energy stored in the BESS with respect to the rated battery capacity. In this concern, the current battery SOC can be estimated as follows [52], [54], [53], [62], [63], [51], [82]: 20 Chapter 2 () ( 1) (), SOC n SOC n SOC n= − −∆ (2.13) where the indices n and (n-1) represent the current and the previous samples, respectively, and ΔSOC refers to the battery SOC variation during the sampling period Ts. Moreover, ΔSOC can be estimated using the general definition of energy evolution ΔEi of a power variable Pi during a period time ΔT. Therefore, for sampled variables and assuming equal integration and sampling periods (i.e. ΔT = Ts), ΔSOC can be estimated as follows [54]: () () , tT ii t Et P d +∆ ∆ = tt ∫ (2.14) ( 1) ( ) ( ) ( 1) , s s nT BAT BAT s BAT BAT nT SOC n P d P n T CC − ηη ∆ = t t= ⋅ − ⋅ ∫ (2.15) where CBAT is the rated battery capacity, and η is the battery efficiency. In general, the efficiency of the ESS considers different efficiencies for charging and discharging processes [54], [53], [83]. Therefore η is expressed as follows: 1, 0 , ,0 D BAT C BAT P P η∀ >  η=η ∀<  (2.16) where ηD and ηC are the battery discharge and charge efficiencies, respectively. The block diagram of the battery SOC estimator is shown in Fig. 2.12 [54], [53], [62], [63]. Fig. 2.12. Battery SOC estimator block diagram In addition, the available battery bank capacity must not be less than the minimum allowable capacity, SOCMIN, and must not be higher than the maximum allowable capacity, SOCMAX, [62], [63], [72], [82], [84]. Thus, the limitations for the SOC of lead-acid battery can be expressed as follows: () , MIN MAX SOC SOC n SOC≤≤ (2.17) ( ) 1. MIN MAX SOC DOD SOC=−⋅ (2.18) – + Residential grid-connected microgrid description 21 This study considers a maximum DOD of 50% in order to not compromise the ESS lifetime [85]. 2.3.4. Solar thermal collectors model The solar thermal collector is a special type kind of heat exchanger that transforms solar radiant energy into heat, which is transfer to a fluid (i.e. usually air, water or oil) flowing through the collector [86], [87]. The advantages of flat-plate collectors are that they are inexpensive to manufacture, they collect booth beam and diffuse radiation, and they are permanently fixed in a position [86]. Since the solar collector array is not physically available in the MG at UPNa, its operation has been simulated by combining the meteorological data obtained through the MG weather station with the actual characteristics of the solar thermal collector DIUM-CL4 and assuming that the solar thermal collector array is facing south and tilted 30° as the PV array. In this regard, the rate of useful energy collected from a solar thermal collector, QSC, derived from the technical characteristics sheet of the solar collector is expressed as follows [55], [46]: ( ) ( ) ( ) ( ) ( ) ( ) ( ) ] 654 975 32 ,2 10 6 10 7 10 ... ... 0,003 0,07 8,6968 1735,5 SC WD a WD a WD a STC WD a WD a WD a G Q TT TT TT G TT TT TT −−− βα = −⋅⋅−+⋅⋅−−⋅⋅−+ + ⋅−−⋅−− ⋅−+   (2.19) being TWD the fluid temperature. 2.3.5. Thermal storage and water storage tank temperature Thermal storage is one of the main parts of a solar heating, cooling, and power generating system, since it has several functions. For instance, it improves the use of collected solar energy by providing thermal capacitance to alleviate the solar availability and load mismatch, and improve the system response to sudden peak loads or loss of solar input [87]. The solar energy is usually stored in liquids, being water the most frequently used as a storage medium, due to is inexpensive and non-toxic [87]. In addition, this fluid can be used in residential MG scenarios, where the DHW demand is required. In the second architecture under study, the control of the temperature of the fluid should be the appropriate, in order to satisfy the user requirements. Therefore, the model of water temperature in the storage tank should consider the rate of energy produced by the solar thermal collectors, QSC, the capacity of the water storage tank, QSC, the rate of energy transferred from the EWH, QWH,T, and the rate of energy loss of the storage tank as mentioned in Chapter 2.1.2. 22 Chapter 2 In this regard, the rate of energy loss of the storage tank can be expressed as follows [87], [88]: ( ) ( ) , 12 2 () , ln T LOSS T WD EXT Lk Q n TT RR π⋅ ⋅ = ⋅− (2.20) where L is the water storage tank length (i.e. L = 2.14 m), kT is the thermal conductivity of the water storage tank, which is 2.4∙10-6 kW/m∙°C for a polyurethane insolation, R1 is the inner radius of the storage tank (i.e. R1 = 0.375 m), R2 is the outer radius of the storage tank (i.e. R2 = 0.475 m considering an insolation thickness of 0.1 m) [46], and TEXT is the temperature of the environment where the storage tank is located (i.e. TEXT = 25°C). Moreover, the capacity of the water storage tank can be expressed as [87], [89], [90]: ,() (), ST T W P WD Q n CV T n =ρ ⋅ ⋅ ⋅∆ (2.21) where W ρ is the density of water (i.e. W ρ = 985.65 kg/m3), CP is the specific heat capacity of water (i.e. CP = 4.18 kJ/kg∙°C), V is the water storage tank volume (i.e. V = 0.8 m3), and ∆TWD is the water temperature variation during the sampling period Ts, which is defined as follows: ( ) ( 1) () , WD WD WD WD s dT TnTn Tn dt T −− ∆== (2.22) where TWD (n) is the new tank temperature after time interval Ts and TWD (n-1) is the water temperature before the time interval Ts. In this concern, the energy balance of the water storage tank is given by: ( ) ,, ( ) ( 1) . WD WD W P SC WH T LOSS T DHW s TnTn CV Q Q Q Q T  −− ρ⋅ ⋅ ⋅ = + − −   (2.23) Consequently, the new temperature of the water in the storage tank could be expressed as follows: ,, , () ( 1) () () () (). s WD WD WH T SC T DHW LOSS T WP T TnTn Q nQ nQ nQ n CV = −+ ⋅ + − −  ρ⋅ ⋅ (2.24) Note that the last expression assumes that the heat losses are constant in the period Ts. Residential grid-connected microgrid description 23 2.4. Generation and demand profiles 2.4.1. Photovoltaic generation As mentioned in section 2.1, this study considers a PV generator of 6 kW located at the city of Pamplona-Spain (42°49’06”N 1°38’39”O) facing south and tilted 30°. The PV generation profile is obtained by means of measuring the output power from PV array every 15 minutes (i.e. Ts = 900 s) at the UPNa microgrid. Furthermore, for simulation purposes a scaling factor of 5/3 is considered for PV power generation, due to the PV generator at UPNa has a peak power of 3.6 kWp [46]. The power generation produced by the PV array during the year under study ranging from July 2013 to July 2014 is presented in Fig. 2.13. Fig. 2.13. Photovoltaic power measured at UPNa microgrid 2.4.2. Wind turbine generation This study considers a small WT of 6 kW located at UPNa microgrid. As well as the PV generator, the generation profile of the WT, shown in Fig. 2.14, is obtained by means of measuring the output power of the WT every 15 minutes during the year under study. Fig. 2.14. Wind turbine power measured at UPNa microgrid Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 5 6 7 Months (2013-2014) Power ( kW ) P PV Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 5 6 7 Months (2013-2014) Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 5 6 7 Months (2013-2014) Power ( kW ) P WT Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 5 6 7 Months (2013-2014) Power ( kW ) 24 Chapter 2 2.4.3. Thermal generation The thermal generation of the residential MG is produced by a flat-plate solar collector with a rated power of 2 kW. The thermal generation profile, shown in Fig. 2.15, is simulated taking into account the meteorological data provided by the weather station of the MG at UPNa and considering that the solar collectors are installed with the same orientation and inclination than the PV array [46]. Similarly to PV and WT generators, the sampling period used to obtain the thermal generation profile is 15 minutes. Fig. 2.15. Rate of energy collected from the solar thermal collectors 2.4.4. Electric load power demand The electrical load shown in Fig. 2.1 contemplates typical domestic loads (e.g. electrical appliances, lighting) and a Heating, Ventilation and Air Conditioning (HVAC) system comprising of a heating pump and the EWH, where the EWH supplies the thermal energy to cover the DHW consumption of the house. In this regard, two possible scenarios are considered in this study. The first scenario considers the first MG architecture and takes into account the load demand profile of the domestic loads excluding the EWH consumption. The load demand profile shown in Fig. 2.16(a) is obtained by means of measuring the output power of the load every 15 minutes during a year under study [50]. The second scenario considers the second MG architecture and takes into account the load demand profile of the domestic loads including the EWH consumption (i.e. DHW consumption). In this scenario, the EWH operates as a passive load and it will beyond the control of the energy management strategy. In this context, the EWH consumption was obtained through a hysteresis control in order to keep mater temperature in the storage tank between 45 °C and 65 °C [46]. The load demand profile in this scenario is shown in Fig. 2.16(b). Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 Months (2013-2014) Power ( kW ) Q SC Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 Months (2013-2014) Power ( kW ) Residential grid-connected microgrid description 25 (a) (b) Fig. 2.16. Electric load demand profile (a) excluding the EWH consumption, and (b) including the EWH consumption 2.4.5. Thermal load demand The thermal load demand (i.e. DHW) consumption profile is taken from [50], where the data was obtained by simulation assuming that the daily DHW demand is the same for each day during the year under study, as shown in Fig. 2.17. Fig. 2.17. Domestic hot water demand Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 5 6 7 Months (2013-2014) Power ( kW ) P LOAD Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 5 6 7 Months (2013-2014) Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 5 6 7 Months (2013-2014) Power ( kW ) P LOAD Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 5 6 7 Months (2013-2014) Power ( kW ) 19/09/2013 20/09/2013 21/09/2013 22/09/2013 23/09/2013 0 3 6 9 12 15 Power ( kW ) Q DHW 19/09/2013 20/09/2013 21/09/2013 22/09/2013 23/09/2013 0 3 6 9 12 15 Power ( kW ) 27 Chapter 3 FLC-based Energy management strategies for a residential grid-connected electric microgrid This chapter presents the analysis and comparison of different energy management strategies, which have been developed with the purpose of smoothing the power profile exchanged with the grid. In order to help the comparison process, the Chapter begins by stating the problem and presenting a set of quality criteria to quantitatively evaluate the degree of grid power profile “smoothnes” resulting from the different energy management strategies. Then, the analysis and design of two previous approaches seeking the same goal are evaluated (i.e. SMA and fuzzy NPT strategies). From the conclusions of the behavior of these strategies, a complete design of an improved fuzzy EMS strategy based on a FLC and the MG Energy Rate-of-Change (ERoC) over time is presented in this Chapter. The new design includes the description of the optimization procedure developed in order to adjust all the parameters involved in the FLC design. The behavior of all these previous strategies is compared by means of Matlab® numerical simulation taking into account the real data recorded from July 2013 to July 2014 on the microgrid available at the UPNa described in Chapter 2. Finally, the experimental results of the improved fuzzy EMS strategy based on MG ERoC are presented at the end of the Chapter in order to confirm the feasibility of the strategy. 3.1. Problem formulation, quality criteria and baseline values 3.1.1. Problem formulation In a residential MG scenario, where RES can be easily integrated and allow residential consumers to generate their own energy, the grid power profile control facilitates reducing both the electricity bill and the mains overload [47]. However, this integration could bring certain challenges to handle when penetration of RES into the distribution network increases, due to the stochastic nature of solar and wind generation as well as the load demand which may cause significant fluctuations in the grid power profile [37]. This behavior can be seen in Fig. 3.1, which shows the grid power profile when the MG includes neither an ESS nor an energy management strategy [53], [57], [36]. In a MG without ESS (i.e. PBAT = 0), the utility grid should compensate all fluctuations produced by the RES and 34 Chapter 3 (a) (b) (c) Fig. 3.4. Simulation results of the SMA strategy excluding the EWH consumption (a) grid power profile, (b) battery SOC, and (c) grid power profile ramp-rates Table 3-2 Quality criteria comparison between SMA strategy and baseline values excluding the EWH consumption EMS Strategy PG,MAX (kW) PG,MIN (kW) PVR MPD (W/h) APD (W/h) PPV No EMS & ESS excluding the EWH consumption 5.75 -6.45 1.00 18468 1121 13.3 SMA strategy 4.71 -2.40 0.58 12839 44.42 2.51 Note that the SMA strategy exhibit a suitable behavior as long as no abrupt changes affect the MG net power from one day to the next one. However, in a real environment, the stochastic nature of the renewable energy sources and the load may significantly change the MG net power from one day to another. Consequently, the SMA strategy is not adequate under these conditions. Similarly, the same drawbacks are present when performing the simulation of the SMA strategy including the EWH consumption. As it can be seen in Fig. 3.5(a) and (b), the increase of the load demand leads to the increase the time intervals where the battery SOC reaches the secure Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Months (2013-2014) Power ( kW ) P GRID SMA Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Months (2013-2014) Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 55 60 65 70 75 80 85 90 95 100 Months (2013-2014) SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 55 60 65 70 75 80 85 90 95 100 Months (2013-2014) SOC ( % ) SOC SMA Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 2000 4000 6000 8000 10000 12000 14000 Months (2013-2014) P GRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 2000 4000 6000 8000 10000 12000 14000 MPD: 1.284e+004 (W/h) Months (2013-2014) P GRID ramp-rate (W/h) FLC-Based energy management strategies for a residential grid-connected electric microgrid 35 limits. Consequently, the fluctuations and power peaks in the grid power profile and the grid power profile ramp-rates increase as shown in Fig. 3.5(c). Finally, Table 3-3 summarizes the resulting values of the quality criteria through the SMA strategy including the EWH consumption. (a) (b) (c) Fig. 3.5. Simulation results of the SMA strategy including the EWH consumption (a) grid power profile, (b) battery SOC, and (c) grid power profile ramp-rates. Table 3-3 Quality criteria comparison between SMA strategy and the baseline values including the EWH consumption EMS Strategy PG,MAX (kW) PG,MIN (kW) PVR MPD (W/h) APD (W/h) PPV No EMS & ESS including the EWH consumption 6.53 -6.45 1.00 18468 1221 5.99 SMA strategy 6.25 -3.98 0.79 20006 57.41 1.23 Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Months (2013-2014) Power ( kW ) P GRID SMA Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Months (2013-2014) Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 55 60 65 70 75 80 85 90 95 100 Months (2013-2014) SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 55 60 65 70 75 80 85 90 95 100 Months (2013-2014) SOC ( % ) SOC SMA Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 5000 10000 15000 20000 25000 MPD: 2.001e+004 (W/h) Months (2013-2014) P GRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 5000 10000 15000 20000 25000 Months (2013-2014) P GRID ramp-rate (W/h) 36 Chapter 3 3.3. Fuzzy energy management strategy based on MG Net Power Trend (NPT) 3.3.1. Introduction A first approach to solve the drawbacks of the SMA strategy was developed and presented in [52]. This approach was designed with the aim of improving the performance of the battery energy management strategy of a grid connected MG presented in [51] by means of including the information about the Net Power Trend (NPT) of the MG into the FLC. According to the information provided by the MG net power trend, this approach increases/decreases the power delivered/absorbed by the battery in order to smooth the grid power profile. The control strategy and the FLC design are presented in the next paragraphs. 3.3.2. Control strategy and FLC design The fuzzy NPT approach focuses on the direct control of the power delivered/absorbed by the battery with the purpose of minimizing the fluctuations in the grid power profile. This approach uses the MG NPT to quantify the trend of the net power fluctuations in the MG (i.e. consumption and generation trend). In this regard, PAVG is considered as the trend of the MG net power and is defined by (3.12) as one-day average of the MG net power. The block diagram of this approach is illustrated in Fig. 3.6 [52], [54] and includes a LPF used for smoothing the grid power, a battery SOC estimator shown in Fig. 2.12, and a Mamdani-based FLC [58] of three inputs PLG (n), PAVG (n), e (n), one output PBAT (n), and 25-rules. Fig. 3.6. Block diagram of the fuzzy energy management strategy based on MG NPT In Fig. 3.6, e (n) represents for the battery capacity status respect to its half-rated capacity, i.e.: () () 2 . BAT e n SOC n C= − (3.16) LPF – + SOC Estimator Fuzzy Logic Control + – + + – + FLC-Based energy management strategies for a residential grid-connected electric microgrid 37 Note that the FLC provides the desired evolution of the low-frequency battery power PBAT,FLC. Therefore, assuming that the battery follows this power evolution, the corresponding grid power profile would be given by [54]: , () () (). G LG BAT FLC Pn P n P n= − (3.17) However, PG (n) also includes the high-frequency components of PLG (n), which can be removed by means of a LPF as suggested in [93]. This results in smoothing the grid power which now is given by [54]: , () () , GRID G LF PnP n= (3.18) where PG,LF is the low-frequency content of PG (n). As a consequence, the power handled by the battery is expressed as follows: ,, () () () , BAT BAT FLC G HF PnP nP n= + (3.19) , () () () , G HF G GRID P n Pn P n= − (3.20) where PG,HF the high-frequency content of PG (n). Regarding the FLC design, the adjustment of all parameters involved in the FLC, for instance, number of Membership Functions (MF), type, mapping and rule-base, is performed following the process described in [51], which will be further detailed in section 3.4.4. The main goal of this process is to find the FLC parameters which minimize the quality criteria defined in section 3.1.2. In short, for each controller input, PLG (n), SOC (n), 5 triangular MFs are defined. These MFs correspond to five fuzzy sets noted as NB, NS, ZE, PS and PB, where B represents “Big”, S “Small”, ZE “Zero”, P “Positive” and N “Negative”, as shown in Fig. 3.7(a) and Fig. 3.7(b). In addition, 2 trapezoidal MFs are defined for the input PAVG (n), which correspond to two fuzzy sets noted as NB and PB, as shown in Fig. 3.7(c). The MFs for the controller inputs are distributed along the variation range defined for each input variable expressed as follows: ,, () , LG MIN LG LG MAX P Pn P≤≤ (3.21) 2 ( ) 2, BAT BAT C en C− ≤≤ (3.22) () , A AVG A PPnP −+ ≤≤ (3.23) 38 Chapter 3 where A P− and A P+ are the maximum and minimum value of the MG net power trend. (a) (b) (c) Fig. 3.7. Membership functions for the FLC inputs of the fuzzy NPT strategy (a) MFs for the input PLG (n), (b) MFs for the input SOC (n), and (c) MFs for the input PAVG (n), © 2014, IEEE 0 0.2 0.4 0.6 0.8 1NB NS ZE PS PB 0 0.2 0.4 0.6 0.8 1NB NS ZE PS PB 0 0.2 0.4 0.6 0.8 1NB PB FLC-Based energy management strategies for a residential grid-connected electric microgrid 39 Note that the input PAVG uses the MF “NB” to indicate that the MG exhibits a generation trend. On the contrary, it uses the MF “PB” to indicate a consumption trend. The assignment of the MFs for the inputs variables allows the definition of at most 50 MFs for the output variable. Therefore, after applying the optimization procedure [51], 7 trapezoidal MFs are defined for the controller output PBAT,FLC (n), as shown in Fig. 3.8. These MFs are associated with seven fuzzy sets noted as NB, NM, NS, ZE, PS, PM and PB, where besides of N, P, B, S and ZE previously defined, M represents “Medium”. The output MFs are distributed along the variation range defined by: , () , B BAT FLC B kP nk−≤ ≤ (3.24) being kB the maximum power assigned at the controller output PBAT,FLC. Fig. 3.8. MFs for the FLC output of the fuzzy NPT strategy, © 2014, IEEE Finally, according to the MFs of the inputs and the output, the FLC rule-base is composed by 50-rules which establish the control policy of the output PBAT. The rule-base is set taking into account the control polices described in [52], [51]. In short, the controller rule-base assigns 25-rules when the MG exhibits a consumption trend and other 25-rules for generation trend. For 0 0.2 0.4 0.6 0.8 1NB NM NS ZE 0 0.2 0.4 0.6 0.8 1ZE PS PM PB 40 Chapter 3 instance, one of the rules is formulated as: “IF the MG net power PLG (n) is slightly negative [i.e. PLG (n) < 0, there is more generation than consumption] AND the battery is slightly charged [i.e. e (n) > 0, or equivalently SOC (n) > CBAT /2] AND the MG exhibits high consumption trend [i.e. PAVG (n) >> 0] THEN strongly charge the battery for covering this consumption trend in a near future [i.e. PBAT,FLC (n) << 0]”. IF PLG IS NS AND e IS PS AND PAVG IS PB THEN PBAT,FLC IS NB As for the inputs and output MFs, the FLC rule-base is optimized following the procedure detailed in [51] with the purpose of minimizing the quality criteria defined in section 3.1.2. The resulting rule-base is presented in Table 3-4. Table 3-4 FLC rule-base for the fuzzy NPT strategy PBAT,FLC (n) PLG (n) NB NS ZE PS PB e (n) NB NB / NB NS / NB NB / NB NB / NM NB / NB NS PM / NS NB / NM ZE / NS NS / PM PS / NM ZE NM / NB PS / ZE ZE / ZE NS / PM NS / NS PS PS / NS PS / NB PM / ZE PM / ZE PM / NB PB PB / PB PB / PB PB / PB PB / PB PB / PB PAVG (n) NB / PB 3.3.3. Simulation results and comparison The simulation results of the fuzzy NPT strategy excluding the EWH consumption are shown in Fig. 3.9. As it can be seen in Fig. 3.9(a), this approach achieves a reduction of the grid power fluctuations and power peaks. However, the grid power profile still exhibits some power peaks, since the SOC of battery occasionally reaches the secure limits, as shown in Fig. 3.9(b). Although, these time intervals are reduced with respect to the SMA strategy, which leads to a minimum reduction of the ramp-rates in the grid power profile as it can be seen in Fig. 3.9(c) and Fig. 3.9 (d). FLC-Based energy management strategies for a residential grid-connected electric microgrid 41 (a) (b) (c) (d) Fig. 3.9. Simulation results of the fuzzy NPT strategy excluding the EWH consumption (a) grid power profile, (b) battery SOC, (c) grid power profile ramp-rates comparison, and (d) maximum grid power profile ramp-rate. Despite the aforementioned drawbacks, the fuzzy NPT strategy improves the behavior with respect to the SMA strategy, this being verified through the analysis of the resulting values of the quality criteria defined in section 3.1.2. The results are summarized in Table 3-5. In short, the PG,MAX, PG,MIN, PVR, MPD and APD criteria are reduced in 16.56%, 11.67%, 15.52%, 9.34% and 19.74%, respectively. On the contrary, PPV criterion is slightly increased in 3.98%. Note that the value of the MPD criterion is high due to the power peaks in the grid power profile. Table 3-5 Quality criteria comparison for the fuzzy NPT strategy, the SMA strategy and the baseline values excluding the EWH consumption EMS Strategy PG,MAX (kW) PG,MIN (kW) PVR MPD (W/h) APD (W/h) PPV No EMS & ESS excluding the EWH consumption 5.75 -6.45 1.00 18468 1121 13.3 SMA strategy 4.71 -2.40 0.58 12839 44.42 2.51 Fuzzy EMS based on MG net power trend 3.93 -2.12 0.49 11640 35.65 2.61 Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -5 -3 -1 1 3 5 Power ( kW ) P GRID SMA Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -5 -3 -1 1 3 5 Months (2013-2014) Power ( kW ) P GRID Fuzzy NPT Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -5 -3 -1 1 3 5 Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -5 -3 -1 1 3 5 Months (2013-2014) Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 55 60 65 70 75 80 85 90 95 100 Months (2013-2014) SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 55 60 65 70 75 80 85 90 95 100 Months (2013-2014) SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 2000 4000 6000 8000 10000 12000 14000 Months (2013-2014) P GRID ramp-rate (W/h) SMA strategy Fuzzy NPT Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 2000 4000 6000 8000 10000 12000 14000 Months (2013-2014) P GRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 2000 4000 6000 8000 10000 12000 14000 MPD: 1.164e+004 (W/h) Months (2013-2014) P GRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 2000 4000 6000 8000 10000 12000 14000 Months (2013-2014) P GRID ramp-rate (W/h) 42 Chapter 3 Finally, for comparison purposes, the analysis of the fuzzy NPT strategy is carried out including the EWH consumption. The simulation results are shown in Fig. 3.10, where it can be seen that some strong the fluctuations in the grid power are removed with respect to SMA strategy. Consequently, the grid power profile ramp-rates are reduced with respect to the SMA strategy, as confirmed in Table 3-6 through the reduction of the values of the quality criteria. (a) (b) (c) (d) Fig. 3.10. Simulation results of the fuzzy NPT strategy including the EWH consumption (a) grid power profile, (b) battery SOC, (c) grid power profile ramp-rates comparison, and (d) maximum grid power profile ramp-rate. Table 3-6 Quality criteria comparison for the fuzzy NPT strategy, the SMA strategy and the baseline values including the EWH consumption EMS Strategy PG,MAX (kW) PG,MIN (kW) PVR MPD (W/h) APD (W/h) PPV No EMS & ESS including the EWH consumption 6.53 -6.45 1.00 18468 1221 5.99 SMA strategy 6.25 -3.98 0.79 20006 57.41 1.23 Fuzzy EMS based on MG net power trend 5.80 -3.28 0.70 18119 50.81 1.31 Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) P GRID SMA Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Months (2013-2014) Power ( kW ) P GRID Fuzzy NPT Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Months (2013-2014) Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 55 60 65 70 75 80 85 90 95 100 Months (2013-2014) SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 55 60 65 70 75 80 85 90 95 100 Months (2013-2014) SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 5000 10000 15000 20000 25000 Months (2013-2014) P GRID ramp-rate (W/h) SMA strategy Fuzzy NPT Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 5000 10000 15000 20000 25000 Months (2013-2014) P GRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 5000 10000 15000 20000 25000 MPD: 1.812e+004 (W/h) Months (2013-2014) P GRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 5000 10000 15000 20000 25000 Months (2013-2014) P GRID ramp-rate (W/h) FLC-Based energy management strategies for a residential grid-connected electric microgrid 43 From the simulation results, it can be concluded that the information provided through the MG net power trend is not the most appropriate to identify the fluctuations in the MG net power. In addition, the use of a new variable at the FLC input results in the increase of the fuzzy controller rule-base (i.e. fifty rules), which increases the controller complexity. In this regard, given the benefits exposed by using a FLC for the EMS design, a new energy management strategy based on FLC is described in the next section with the objective of improving the performance and simplifying the FLC complexity of the EMS strategies described so far. 3.4. Fuzzy energy management strategy based on MG energy Rate-of-Change 3.4.1. Introduction An improved fuzzy-based design is presented in this section with the aim of minimizing the power peaks and fluctuations in the grid power profile while keeping the battery SOC evolution within secure limits as well as reducing the FLC complexity. This design was presented in [53] and an extended version including experimental validation results was described in [54]. The new fuzzy-based design uses the MG Energy Rate-of-Change (ERoC) over time to quantify the magnitude of the energy changes in the MG; according to this value and the battery SOC, the new EMS design increases, decreases or maintains the power delivered/absorbed by the mains in order to concurrently satisfy the load power demand and the battery constraints defined in Chapter 2.3.3. 3.4.2. Control strategy The improved fuzzy EMS based on MG ERoC suggests calculating the grid power as the sum of the average net power of the MG, PAVG (n) defined in (3.12) and an additional component, PFLC (n), used to modify the power exchanged with the grid to keep the battery SOC within secure limits at any time. Thus, the grid power profile is defined as [54], [53]: () () (). GRID AVG FLC P nP nPn= + (3.25) where PFLC (n) is computing by means of a FLC that uses the battery SOC, SOC (n), and the MG ERoC over time , ṖAVG (n), as inputs variables. In this regard, the FLC uses the battery SOC, SOC (n), as an input to check its value at any time in order to satisfy the battery constraints established in Chapter 2.3.3 and to preserve the battery life. In addition, the FLC uses ṖAVG (n) as another input to obtain the information of the magnitude of the MG energy change of two consecutive samples (i.e. the slopes produced by 50 Chapter 3 Fig. 3.16. Initial fuzzy rule-base and grid power variation with respect to the FLC inputs • Then, the rules over the diagonal are defined to establish that the evolution of the variable ṖAVG from a X value to a Y value involves the following statements: o If X < Y implies the increase of the power delivered by the grid. For instance, when SOC is NB, if ṖAVG is NS the power assigned to the FLC output should be higher than the one assigned when ṖAVG is NB (i.e. PFLC will be positive). In short, when the battery is almost discharged (i.e. SOC is NB) and the MG energy ERoC indicates a reduction of power generation or an increase of the load demand (e.g. when ṖAVG changes from NB to NS), besides PAVG component it will be necessary the use of extra power coming from the grid in order to charge the batteries (i.e. PFLC  PSS). o On the contrary, if X > Y implies the decrease of the power delivered by the grid. Following these statements, the rules over the diagonal are defined as: RULE 6: IF ṖAVG IS NS AND SOC IS NB THEN PFLC IS PSS RULE 11: IF ṖAVG IS ZE AND SOC IS NB THEN PFLC IS PS RULE 12: IF ṖAVG IS ZE AND SOC IS NS THEN PFLC IS PSS RULE 16: IF ṖAVG IS PS AND SOC IS NB THEN PFLC IS PM RULE 17: IF ṖAVG IS PS AND SOC IS NS THEN PFLC IS PS RULE 18: IF ṖAVG IS PS AND SOC IS ZE THEN PFLC IS PSS RULE 21: IF ṖAVG IS PB AND SOC IS NB THEN PFLC IS PB RULE 22: IF ṖAVG IS PB AND SOC IS NS THEN PFLC IS PM RULE 23: IF ṖAVG IS PB AND SOC IS ZE THEN PFLC IS PS RULE 24: IF ṖAVG IS PB AND SOC IS PS THEN PFLC IS PSS As shown in Fig. 3.16, the rules over the diagonal indicate the increase of the power delivered by the grid. In addition, this analysis leads to the definition of another four MFs for the FLC output. These MFs are uniformly distributed along the positive range of the output PFLC, as shown in Fig. 3.17, and correspond to four fuzzy sets noted as PSS, PS, PM and PB where besides of P, B, and S previously defined, SS represents “Smallest” and M represents “Medium”. FLC-Based energy management strategies for a residential grid-connected electric microgrid 51 Fig. 3.17. Initial definition and distribution of the positive MFs for the FLC output • After that, the rules below the diagonal are defined in order to preserve the battery lifetime. In this concern, these rules consider the amount of energy stored in the battery (i.e. SOC input) to increase the power absorbed by the grid according to the following statements: o An increase of the amount of energy stored in the ESS implies an increase of the power absorbed by the grid in order to not overcharge the battery. For instance, when ṖAVG is NB, if SOC is NS the power assigned to the FLC output should be lower than the one assigned when SOC is NB (i.e. PFLC will be negative, PFLC  NSS). o Conversely, a decrease of the energy stored in the ESS implies a decrease of the power absorbed by the grid in order to avoid discharge the battery out the security limit. Accordingly, the rules below the diagonal are defined as follows: RULE 2: IF ṖAVG IS NB AND SOC IS NS THEN PFLC IS NSS RULE 3: IF ṖAVG IS NB AND SOC IS ZE THEN PFLC IS NS RULE 4: IF ṖAVG IS NB AND SOC IS PS THEN PFLC IS NM RULE 5: IF ṖAVG IS NB AND SOC IS PB THEN PFLC IS NB RULE 8: IF ṖAVG IS NS AND SOC IS ZE THEN PFLC IS NSS RULE 9: IF ṖAVG IS NS AND SOC IS PS THEN PFLC IS NS RULE 10: IF ṖAVG IS NS AND SOC IS PB THEN PFLC IS NM RULE 14: IF ṖAVG IS ZE AND SOC IS PS THEN PFLC IS NSS RULE 15: IF ṖAVG IS ZE AND SOC IS PB THEN PFLC IS NS RULE 20: IF ṖAVG IS PS AND SOC IS PB THEN PFLC IS NSS -k 01/4 k 1/2 k 3/4 k +k 0 0.2 0.4 0.6 0.8 1 ZE PSS PS PM PB 52 Chapter 3 This previous analysis leads to the definition of extra four MFs for the FLC output, which correspond to four fuzzy sets noted as NSS, NS, NM and NB. These MFs are uniformly distributed along the negative range of the output PFLC. Fig. 3.18 illustrates the complete initial definition of the MFs for the FLC output. Fig. 3.18. Initial definition and distribution of the MFs for the FLC output • Finally, the initial rule-base is presented in Table 3-8. The initial rule-base includes 25-rules which establish the evolution of the FLC output [54], [53]. Table 3-8 Initial FLC rule-base of the fuzzy ERoC strategy, © 2015, IEEE PFLC (n) ṖAVG (n) NB NS ZE PS PB SOC (n) NB ZE PSS PS PM PB NS NSS ZE PSS PS PM ZE NS NSS ZE PSS PS PS NM NS NSS ZE PSS PB NB NM NS NSS ZE STEP 2: MF adjustment of the FLC inputs and outputs The second step consists in the adjustment of the inputs and output MFs. This process is carried out through numerical simulations using Matlab®. The procedure for the adjustment of trapezoidal MF, is described in [51]. For instance, the optimization procedure for the SOC input is described below: • First, each triangular MF shown in Fig. 3.14 is parametrically defined according to: -k -3/4 k -1/2 k -1/4 k 01/4 k 1/2 k 3/4 k +k 0 0.2 0.4 0.6 0.8 1NB NM NS NSS ZE PSS PS PM PB FLC-Based energy management strategies for a residential grid-connected electric microgrid 53 Fig. 3.19. Triangular membership function parameters The mapping parameters X1, X2 and X3 assume that the pairs of MFs (NB, PB), (NS, PS) are mapped symmetrically with respect to the origin (i.e. 3/4 SOCMAX for the SOC input), as shown in Fig. 3.20. Note that for input ṖAVG and output PFLC, X1 = -X3 for the particular case of the MF ZE. Fig. 3.20. Mapping parameters for the MFs of the SOC input • Then, the mapping adjustment assumes the initial rule-base shown in Table 3-8 and is carried out for each pair of MFs and for ZE MF as follows: o Finding X1: the parameters X2 and X3 are fixed to the values shown in Fig. 3.14. Then, the optimum value of the parameter X1, noted as X1opt, is obtained through numerical simulations as the value which minimizes the set of defined quality criteria. o Finding X2: the parameter X3 is fixed to the value shown in Fig. 3.14 and X1 is set to X1opt. Then, the optimum value of the parameter X2, noted as X2opt, is obtained through numerical simulations as the value which minimizes the set of defined quality criteria. o Finding X3: the parameters X1 and X2 are set to X1 = X1opt and X2 = X2opt, respectively. Then, the optimum value of the parameter X3, noted as X3opt, is obtained 54 Chapter 3 through numerical simulations as the value which minimizes the set of defined quality criteria. o Finally, there is a verification procedure where the parameters X3 and X2 are set to X3 = X3opt and X2 = X2opt, respectively. Then, by numerical simulations the value of X1opt which minimizes the set of defined quality criteria is verified. If not, the adjustment procedure is repeated. • Finally, after this process, the optimized MFs for both inputs and the output are shown in Fig. 3.21, Fig. 3.22, and Fig. 3.23, respectively [54], [53]. Fig. 3.21. Optimized MFs for the input variable ṖAVG, © 2016, IEEE Fig. 3.22. Optimized MFs for the input variable SOC, © 2016, IEEE 0 0.2 0.4 0.6 0.8 1NB NS ZE PS PB 0 0.2 0.4 0.6 0.8 1NB NS ZE PS PB FLC-Based energy management strategies for a residential grid-connected electric microgrid 55 Fig. 3.23. Optimized MFs for the FLC output PFLC, © 2016, IEEE STEP 3: Optimization of the initial FLC rule-base The final step involves the adjustment of the initial rule-base presented in table 3-8. Similarly to Step 2, the optimized rule-base is obtained by modifying the rules of the initial rule-base in order to find a set of rules which minimize the quality criteria defined in section 3.1.2. For instance, the optimization of the rules 7, 8 and 9 according to MPD criterion is shown in Fig. 3.24. As it can be seen, the lowest MPD value is obtained when rule 7 is ZE, rule 8 is NSS and rule 9 is NS. Note that in Fig. 3.24, the number 9 represents the MF “PB”, the number 8 represents “PM”, then successively, PS=7, PSS=6, ZE=5, NSS=4, NS=3, NM=2 and NB=1. Fig. 3.24. Optimization of the rules 7, 8 and 9 0 0.2 0.4 0.6 0.8 1NB NM NS NSS ZE PSS PS PM PB 56 Chapter 3 Finally, this process is performed for each rule, which leads to the definition of the optimized rule-base presented in Table 3-9 [54]. Table 3-9 Optimized rule-base for the FLC of the fuzzy ERoC strategy, © 2016, IEEE PFLC (n) ṖAVG (n) NB NS ZE PS PB SOC (n) NB PSS PSS PS PM PB NS PSS ZE PSS PSS PM ZE NS NSS ZE PSS PS PS NSS NS NSS PM PSS PB NB NM NSS NSS NSS 3.4.5. Simulation results and analysis The simulation results of the fuzzy ERoC strategy excluding the EWH consumption are shown from Fig. 3.25 to Fig. 3.29. Fig. 3.25(a) compares the grid power profile achieved with the SMA, the fuzzy NPT, and the fuzzy ERoC strategies. The results highlight the improved behavior of the fuzzy ERoC strategy, since the power peaks and the strong fluctuations in the grid power profile are minimized. Moreover, Fig. 3.25(b) confirms the correct evolution of the battery SOC, which is kept within the secure bounds. As it can be seen, the battery SOC evolution achieved through the SMA strategy and the fuzzy NPT strategy reaches low values, which may cause the battery SOC falls below the secure limit, thus, compromising the battery lifetime. In contrast, the fuzzy ERoC strategy evidences a battery SOC evolution, during the year under study, close to the 75% of the rated battery capacity, which means that the ESS could further compensate net power fluctuations that may exist in the MG at any time while preserving the battery lifetime [54]. The improved behavior of the battery SOC evolution can be further appreciated in Fig. 3.26, where it can be seen that the fuzzy ERoC strategy keeps the battery SOC in a range between the 60% and 80% of the rated battery capacity during the 77% of the year under study. In contrast, the SMA strategy and the fuzzy NPT strategy keep this range in the 66% and 68% of the year under study, respectively. FLC-Based energy management strategies for a residential grid-connected electric microgrid 57 (a) (b) Fig. 3.25. Simulation results and comparison for the SMA strategy (top), the fuzzy NPT strategy (middle), and the fuzzy ERoC strategy (bottom), (a) grid power profile, and (b) battery SOC Fig. 3.26. Annual frequency of the battery SOC ranges established from the SMA, fuzzy NPT, and fuzzy ERoC strategies including the EWH consumption Moreover, the analysis of specific days which highlights the improved grid profile of the fuzzy EMS based on the MG ERoC is presented in Fig. 3.27 and Fig. 3.28. As it can be appreciated in Fig. 3.27, the energy stored in the battery through the fuzzy EMS ERoC (green solid line) is higher than the one obtained through the SMA strategy (pink dot line) and the fuzzy NPT strategy (brown dashed line), which allows compensate the net power fluctuations. Therefore, the proper control of the battery SOC evolution is ensured at every time, and consequently, the undesirable fluctuations in the grid power profile are removed. Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) P GRID SMA Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) P GRID Fuzzy NPT Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Months (2013-2014) Power ( kW ) P GRID Fuzzy ERoC Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Months (2013-2014) Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 Months (2013-2014) SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 Months (2013-2014) SOC ( % ) SOC SMA SOC Fuzzy NPT SOC Fuzzy ERoC 50%-60% 60%-70% 70%-80% 80%-90% 90%-100% 0 5 10 15 20 25 30 35 40 45 Battery SOC ranges Annual frequency (%) SMA strategy Fuzzy NPT Fuzzy ERoC 50%-60% 60%-70% 70%-80% 80%-90% 90%-100% 0 5 10 15 20 25 30 35 40 45 Battery SOC ranges Annual frequency (%) 58 Chapter 3 Fig. 3.27. Improved behavior of the fuzzy ERoC strategy with respect to the SMA and fuzzy NPT strategies Furthermore, Fig. 3.28 highlights the advantage of adding the derivative input to the FLC. As it can be seen, in front of an abrupt consumption change in the MG, the fuzzy ERoC strategy rapidly increases the power delivered by the grid (blue solid line), preventing the discharge of the battery below the secure limit. On the contrary, the slow evolution of the power delivered by the grid provided through the SMA strategy (red dot line) and the fuzzy ERoC strategy (mustard-colored dashed line), leads to the battery to reach the secure limits, thus, breaking the battery SOC constraints [54]. Fig. 3.28. Influence of the derivative input in the grid power profile, © 2016, IEEE In addition, Fig. 3.29 shows the ramp-rates of the grid power profile achieved through the fuzzy ERoC strategy during the year under study. As it can be seen in Fig. 3.29(a), the grid power ramp-rates are reduced with respect to previous strategies. This result confirms the reduction of 03/06/2014 14:00:00 04/06/2014 14:00:00 05/06/2014 14:00:00 06/06/2014 14:00:00 -6 -4 -2 0 2 4 6 Power ( kW ) 03/06/2014 14:00:00 04/06/2014 14:00:00 05/06/2014 14:00:00 06/06/2014 14:00:00 50 55 60 65 70 75 80 85 90 95 100 SOC ( % ) PGRID SMA PGRID Fuzzy NPT PGRID Fuzzy ERoC SOC SMA SOC FLC Fuzzy NPT SOC Fuzzy ERoC 03/06/2014 14:00:00 04/06/2014 14:00:00 05/06/2014 14:00:00 06/06/2014 14:00:00 -6 -4 -2 0 2 4 6 Power ( kW ) 20/12/2013 13:00:00 21/12/2013 13:00:00 -6 -5 -4 -3 -2 -1 0 1 2 3 4 Power ( kW ) 20/12/2013 13:00:00 21/12/2013 13:00:00 50 55 60 65 70 75 80 85 90 95 100 SOC ( % ) P LG P GRID SMA P GRID Fuzzy NPT P GRID Fuzzy ERoC SOC SMA SOC Fuzzy NPT SOC Fuzzy ERoC 20/12/2013 13:00:00 21/12/2013 13:00:00 -6 -5 -4 -3 -2 -1 0 1 2 3 4 Power ( kW ) FLC-Based energy management strategies for a residential grid-connected electric microgrid 59 the MPD criterion that reaches a maximum value of 817.9 W/h, as shown in Fig. 3.29(b), which leads to improve the quality of the grid power profile. (a) (b) Fig. 3.29. Simulation results for the fuzzy ERoC strategy excluding the EWH consumption (a) grid power profile ramp-rates comparison, and (b) maximum grid power profile ramp-rate. The enhanced behavior of the fuzzy ERoC strategy with respect to the strategies described so far is also verified through the analysis of the resulting values of the quality criteria defined in section 3.1.2. The results are summarized in Table 3-10 [54]. Table 3-10 Quality criteria comparison for the fuzzy ERoC strategy, the fuzzy NPT strategy, the SMA strategy and the baseline values excluding the EWH consumption EMS Strategy PG,MAX (kW) PG,MIN (kW) PVR MPD (W/h) APD (W/h) PPV No EMS & ESS excluding the EWH consumption 5.75 -6.45 1.00 18468 1121 13.3 SMA strategy 4.71 -2.40 0.58 12839 44.42 2.51 Fuzzy NPT strategy 3.93 -2.12 0.49 11640 35.65 2.61 Fuzzy ERoC strategy 1.83 -2.04 0.32 817 56.15 2.79 As it can be seen, the fuzzy ERoC strategy achieves an important reduction in four of the defined quality criteria. With respect to the SMA strategy PG,MAX, PG,MIN, and PVR are reduced in 61% , 15%, and 45% , respectively, and 53%, 4%, and 35%, respectively, with respect to the fuzzy NPT strategy. Moreover, the main improvement of the fuzzy ERoC strategy is the high reduction of the MPD criterion, achieving a reduction up to 94% and 93% with respect to the SMA and the fuzzy NPT strategies, respectively. It can be noted that the improved behavior of the fuzzy ERoC strategy comes mainly from the strong reduction of the MPD criterion, even though the APD and PPV values are slightly higher than the other strategies [54]. Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 2000 4000 6000 8000 10000 12000 14000 Months (2013-2014) P GRID ramp-rate (W/h) SMA strategy Fuzzy NPT Fuzzy ERoC Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 2000 4000 6000 8000 10000 12000 14000 Months (2013-2014) P GRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 MPD: 817.9 (W/h) Months (2013-2014) P GRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 Months (2013-2014) P GRID ramp-rate (W/h) 67 Chapter 4 FLC-based energy management strategy based on Microgrid power forecasting This Chapter presents an enhanced FLC-based energy management strategy based on MG power forecasting (EMS-FC), for smoothing the power profile exchanged with the grid. The new design includes generation and demand forecasting to predict the future behavior of the MG so that the power forecast error will be used by the FLC to modify the grid power profile according to the battery SOC. Moreover, this Chapter describes the forecasting of power generation and load demand, and presents the comparison between the forecasted and measured data. Moreover, in order to verify the enhanced behavior of the fuzzy energy management strategy based on MG power forecasting (EMS-FC), the Chapter presents the simulation results and the comparison with previous strategies described in Chapter 3. Finally, this Chapter also presents the experimental results of the enhanced FLC-based strategy based on MG power forecasting carried out in a real MG at the UPNa. The results highlight the effectiveness of the proposed design, which concurrently smooths the grid power profile and keeps the battery SOC evolution between secure limits. 4.1. Microgrid power forecasting Conversely to previous designs described in Chapter 3, the fuzzy EMS-FC strategy uses a Central Moving Average (CMA) filter to compute the average of the MG net power. Therefore, the fuzzy EMS-FC strategy removes the problem of making decisions based on the MG data of the previous 24-hours. In this regard, with the purpose of computing the central average of the MG net power, this strategy requires the forecast of both the energy production and the load demand of the MG, as addressed in the following paragraphs. 4.1.1. Power generation forecasting The MG power generation of wind and solar RES is predicted using the weather forecast data provided by Meteogalicia THREDDS Server [98], which consists in a set of weather data acquired through the Weather Research and Forecasting (WRF) model for the Iberian Peninsula. The weather data provided by Meteogalicia THREDDS Server is updated every 12-hours with a prediction horizon of three days and includes among others the ambient temperature, the wind speed at 10 m of height above the ground, the horizontal irradiance, and the atmospheric 68 Chapter 4 pressure for the following 12-hours. In addition, the server provides the weather forecast data with a resolution of 1-hour and 12x12 km grid resolution [63], [57], [46]. In this regard, the power generation forecasting is carried out by means of the Numerical Weather Prediction (NWP) [99], [100] data provided by Meteogalicia THREDDS Server and the photovoltaic and wind turbine models described in Chapter 2.2. As mentioned in Chapter 2.3.1, the estimation of the PV power forecast, PPV,FC, requires the transformation of the incident solar irradiance on an horizontal surface provided by Meteogalicia server, shown in Fig. 4.1(a), into the incident solar irradiance on a tilted plane. This transformation was carried out following the procedure described in [75]. The resulting incident solar irradiance on an inclined surface is shown in Fig. 4.1(b). As it can be seen, the prediction of the solar irradiance incident on a tilted plane obtained through this method follows the evolution of the real data measured in the MG at UPNa, as shown in Fig. 4.2. (a) (b) Fig. 4.1. Solar irradiance of the year under study (a) forecast of the incident solar irradiance on a horizontal surface provided by Meteogalicia, and (b) forecast of the incident solar irradiance on an inclined surface at UPNa, Fig. 4.2. Comparison between the forecasted and measured data of the incident solar irradiance on an inclined surface at UPNa The forecast of the PV power is therefore obtained using the estimated solar irradiance on an inclined surface, the forecast of the ambient temperature at UPNa, and the PV model described Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 1200 Months (2013-2014) Irradiance ( W/m 2 ) G 0 Meteogalicia Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 1200 Months (2013-2014) Irradiance ( W/m 2 ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 1200 Months (2013-2014) Irradiance ( W/m 2 ) G( β , α ) FC UPNa Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 1200 Months (2013-2014) Irradiance ( W/m 2 ) 30/07/2013 14:00:00 31/07/2013 14:00:00 01/08/2013 14:00:00 02/08/2013 14:00:00 03/08/2013 14:00:00 04/08/2013 14:00:00 0 200 400 600 800 1000 1200 Irradiance ( W/m 2 ) G( β , α ) FC G( β , α ) 30/07/2013 14:00:00 31/07/2013 14:00:00 01/08/2013 14:00:00 02/08/2013 14:00:00 03/08/2013 14:00:00 04/08/2013 14:00:00 0 200 400 600 800 1000 1200 Irradiance ( W/m 2 ) FLC-Based energy management strategy based on microgrid power forecasting 69 in Chapter 2.3.1. The forecast of the PV power generation for the year under study is presented in Fig. 4.3(a), whereas a comparison of six days between the PV generation power forecasted and measured at UPNa is presented in Fig. 4.3(b). (a) (b) Fig. 4.3. Forecast of photovoltaic power (a) during the year under study, and (b) comparison between forecasted and measured data Furthermore, the wind power forecasting uses the estimation of wind speed, atmospheric pressure, and temperature at UPNa. In this regard, the forecast data of wind speed provided by Meteogalicia server (i.e. measured at a height of 10 m above the ground) has to be extrapolated to the wind turbine hub-height at UPNa (i.e. 20 m above the ground). In addition, the wind speed taking into account the air density at UPNa is computed using WT model described in Chapter 2.3.2 and the forecast data provided by Meteogalicia server. The resulting prediction of the WT power during the year under study, PWT,FC, is displayed in Fig. 4.4(a), whereas the comparison of six days between the WT power forecasted and measured is presented in Fig. 4.4(b). Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 5 6 7 Months (2013-2014) Power ( kW ) P PV,FC Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 5 6 7 Months (2013-2014) Power ( kW ) 30/07/2013 14:00:00 31/07/2013 14:00:00 01/08/2013 14:00:00 02/08/2013 14:00:00 03/08/2013 14:00:00 04/08/2013 14:00:00 0 1 2 3 4 5 6 Power ( kW ) 30/07/2013 14:00:00 31/07/2013 14:00:00 01/08/2013 14:00:00 02/08/2013 14:00:00 03/08/2013 14:00:00 04/08/2013 14:00:00 0 1 2 3 4 5 6 Power ( kW ) PPV,FC PPV 70 Chapter 4 (a) (b) Fig. 4.4. Forecast of wind turbine power (a) during the year under study, and (b) comparison between forecasted and measured data Finally, the forecast of power generation, PGEN,FC, is expressed as follows: , ,, () () () , GEN FC PV FC WT FC P nP nP n= + (4.1) where PPV,FC and PWT,FC are the forecast of the photovoltaic and wind turbine power, respectively. The prediction of power generation during the year under study is shown in Fig. 4.5(a). Similarly, Fig. 4.5(b) shows the comparison between the forecasted and measured data for six specific days. Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 Months (2013-2014) Power ( kW ) PWT,FC Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 Months (2013-2014) Power ( kW ) 30/07/2013 14:00:00 31/07/2013 14:00:00 01/08/2013 14:00:00 02/08/2013 14:00:00 03/08/2013 14:00:00 04/08/2013 14:00:00 0 1 2 3 Power ( kW ) PWT,FC PWT 30/07/2013 14:00:00 31/07/2013 14:00:00 01/08/2013 14:00:00 02/08/2013 14:00:00 03/08/2013 14:00:00 04/08/2013 14:00:00 0 1 2 3 Power ( kW ) FLC-Based energy management strategy based on microgrid power forecasting 71 (a) (b) Fig. 4.5. Forecast of power generation (a) during the year under study, and (b) comparison between forecasted and measured data 4.1.2. Load demand forecasting The load forecast is estimated through the persistence forecast model assuming that the daily consumption pattern is not very distinct and steady from one day to another. In this regard, persistence model uses past data as the forecast for the next time period [62], [63], [48], [101], [102]. Thus, the load demand profile for the next day will be similar as the previous day, namely: ,( ) (), LOAD FC LOAD P nM P n+= (4.2) being PLOAD,FC the load forecast. Note that in this study the differences of load demand between weekdays and weekends or holydays are not considered. The load forecast and the load power demand measured in six days on winter and summer seasons at UPNa are shown in Fig. 4.6(a) and Fig. 4.6(b), respectively. As it can be seen, the behavior of the persistence model could be considered acceptable. Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 5 6 7 8 Months (2013-2014) Power ( kW ) PGEN,FC Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 1 2 3 4 5 6 7 8 Months (2013-2014) Power ( kW ) 30/07/2013 14:00:00 31/07/2013 14:00:00 01/08/2013 14:00:00 02/08/2013 14:00:00 03/08/2013 14:00:00 04/08/2013 14:00:00 0 1 2 3 4 5 6 7 Power ( kW ) PGEN,FC PGEN 30/07/2013 14:00:00 31/07/2013 14:00:00 01/08/2013 14:00:00 02/08/2013 14:00:00 03/08/2013 14:00:00 04/08/2013 14:00:00 0 1 2 3 4 5 6 7 Power ( kW ) 72 Chapter 4 (a) (b) Fig. 4.6. Comparison between the predicted load power demand and the load power demand measured at UPNa microgrid (a) winter season data, and (b) summer season data 4.1.3. Net power forecasting According to (2.3) the forecast of the MG net power, PLG,FC, is expressed as follows [62], [63]: , ,, () () (). LG FC LOAD FC GEN FC P nP nP n= − (4.3) Fig. 4.7 shows the comparison between the forecast of the MG net power and the MG net power measured at UNPa microgrid. As it can be seen, there is an error between the measured and the expected values (i.e. forecast error PE), therefore, the EMS design should consider this error to take the appropriate control decision in order to concurrently improve the grid power profile and to protect the battery bank from a deep discharge [62]. The MG forecast error is defined as follows [62], [63]: , () () () , E LG LG FC Pn P n P n= − (4.4) 23/12/2013 13:00:00 24/12/2013 13:00:00 25/12/2013 13:00:00 26/12/2013 13:00:00 27/12/2013 13:00:00 28/12/2013 13:00:00 0 1 2 3 4 5 6 Power ( kW ) PLOAD,FC PLOAD 23/12/2013 13:00:00 24/12/2013 13:00:00 25/12/2013 13:00:00 26/12/2013 13:00:00 27/12/2013 13:00:00 28/12/2013 13:00:00 0 1 2 3 4 5 6 Power ( kW ) 30/07/2013 14:00:00 31/07/2013 14:00:00 01/08/2013 14:00:00 02/08/2013 14:00:00 03/08/2013 14:00:00 04/08/2013 14:00:00 0 1 2 3 4 5 6 Power ( kW ) PLOAD,FC PLOAD 30/07/2013 14:00:00 31/07/2013 14:00:00 01/08/2013 14:00:00 02/08/2013 14:00:00 03/08/2013 14:00:00 04/08/2013 14:00:00 0 1 2 3 4 5 6 Power ( kW ) FLC-Based energy management strategy based on microgrid power forecasting 73 Fig. 4.7. Comparison between the prediction of the MG net power and the MG net power measured at UPNa microgrid 4.2. Fuzzy EMS design based on MG power forecasting The block diagram of the fuzzy EMS strategy based on MG power forecasting is shown in Fig. 4.8 and includes the following blocks [62], [63]: Fig. 4.8. Fuzzy EMS based on MG power forecasting block diagram 1. A Central Moving Average (CMA) filter block, used for computing the MG average net power PCTR (n), 2. A 3H filter block, used for both computing the average forecast error of the previous 3-hours, 3H E P (n), and reducing the high variability associated with the forecast error PE, 3. A LPF block, used for computing the average battery SOC of the previous 24-hours, SOCAVG (n), 4. A battery SOC Estimator block, used to estimate the SOC of the battery according to the battery model described in Chapter 2.3.3, and 30/07/2013 14:00:00 31/07/2013 14:00:00 01/08/2013 14:00:00 02/08/2013 14:00:00 03/08/2013 14:00:00 04/08/2013 14:00:00 -6 -4 -2 0 2 4 6 Power ( kW ) PLG,FC PLG PE 30/07/2013 14:00:00 31/07/2013 14:00:00 01/08/2013 14:00:00 02/08/2013 14:00:00 03/08/2013 14:00:00 04/08/2013 14:00:00 -6 -4 -2 0 2 4 6 Power ( kW ) Fuzzy Logic Control + - 24H CMA Filter SOC Estimator + - 3H Filter LPF + - + + + 74 Chapter 4 5. A Fuzzy Logic Control block, used for improving the grid power profile according to the battery SOC and the MG forecast error of the previous 3-hours. As shown in Fig. 4.8 the grid power profile of the fuzzy EMS-FC strategy is defined as the sum of three variables PCTR, PSOC and PFLC, where each variable plays a particular role in the energy management strategy. The grid power profile is expressed as follows [62], [63]: () () () (), GRID CTR SOC FLC P nPnPnPn=++ (4.5) The first variable, PCTR (n), is computed by means of a Central Moving Average (CMA) filter [103], which uses the past and the future data of the MG net power to estimate the central average of the MG net power. The CMA filter uses a window size of 24-hours, which contains the MG net power of the previous 12-hours and the forecast of the MG net power for the following 12-hours. The central average of the MG net power, PCTR, is expressed as follows [62], [63]: 12 12 , 1 () () (), 2 HH CTR LG LG FC Pn P nP n −+  =⋅+  (4.6) 12 12 1 12 1 ( ) ( ), M H LG LG k P n P nk M − = = − ∑ (4.7) 12 12 ,, 1 12 1 ( ) ( ), M H LG FC LG FC k Pn Pnk M + = = + ∑ (4.8) where 12H LG P− is the average value of MG net power of the previous 12-hours, 12 , H LG FC P+ is the average value of the MG net power forecast for the next 12-hours, and M12 is the number of samples in 12-hours. The second variable of the grid power profile, PSOC (n), is used to keep the battery SOC centered close to the 75% of the rated battery capacity [57]. In this regard, PSOC (n) is proportional to the error between the reference value of the battery SOC and the average value of the battery SOC of the previous 24-hours. This component is expressed as follows [62], [63]: [] () (), SOC e REF AVG P n k SOC SOC n=⋅− (4.9) 1 1 ( ) ( ), M AVG k SOC n SOC n k M = = − ∑ (4.10) FLC-Based energy management strategy based on microgrid power forecasting 75 where SOCREF is the reference value of the battery SOC which is set to 75% for the case under study, SOCAVG is the average value of the battery SOC of the previous 24-hours, and ke is the proportional gain constant which is set to 0.05 kW/% in order to obtain a high enough phase margin in the battery SOC control loop [57]. The third variable, PFLC, is used to improve the grid power profile according to both the battery SOC and the forecast error of the MG of the previous 3-hours. This component is computed by a FLC that assumes a Mamdani-based inference and defuzzyfication of Center of Gravity of two-input, one-output and 25 rules. The inputs of the FLC are the current battery state-of-charge SOC (n) and the power forecast error of the previous 3-hours, 3H E P (n), which is defined as follows [62], [63]: 3 3 1 3 1 ( ) ( ), M H EE k P n Pnk M = = − ∑ (4.11) being M3 the number of samples in the previous 3-hours. Finally, according to (2.4) the battery power is defined as follows: () () (). BAT LG GRID P n PnP n= − (4.12) Regarding the FLC design, similarly to the previous fuzzy EMS strategies, the adjustment of all parameters involved in the fuzzy controller design was performed by an off-line optimization process [51] considering the real recorded data and the forecasted data of the renewable electricity production and load demand with the purpose of minimizing the energy management quality criteria defined in Chapter 3.1.2. The optimization procedure was described in Chapter 3.4.4. Therefore, only the results from this procedure are presented in this Chapter. As a result, five triangular MFs are defined for the input variables 3H E P (n) and SOC (n). As illustrated in Fig. 4.9, these MFs are associated with five fuzzy sets noted as NB, NS, ZE, PS and PB, and are distributed along the variation range defined for each input. In this regard, the variation range for the input SOC (n) has to satisfy the battery constraints defined in Chapter 2.3.3, whereas the variation range for the input 3H E P is defined as follows [62], [63]: 3() , H eE e PPn P− ≤ ≤+ (4.13) being Pe the maximum forecast error. Note that the case under study assumes a maximum forecast error of 6 kW. 82 Chapter 4 Fig. 4.15. Annual frequency of the battery SOC ranges established from the SMA, fuzzy NPT, fuzzy ERoC, and fuzzy EMS-FC strategies including the EWH consumption As it can be seen, the fuzzy EMS-FC strategy leads to keep the battery SOC in a range between the 70% and 80% of the rated battery capacity during the 45% of the year under study. In contrast, the SMA, the fuzzy NPT, and the fuzzy ERoC strategies keep the battery SOC in this range the 24%, 26% and 33% of the year under study, respectively. In addition, the improved behavior of the fuzzy EMS-FC strategy with respect to the strategies described so far is verified by computing the energy management quality criteria defined in Chapter 3.1.2. The results are reported in Table 4-2. Table 4-2 Quality criteria comparison for the fuzzy EMS-FC strategy, the fuzzy ERoC strategy, the fuzzy NPT strategy, the SMA strategy and the baseline values excluding the EWH consumption EMS Strategy PG,MAX (kW) PG,MIN (kW) PVR MPD (W/h) APD (W/h) PPV No EMS & ESS excluding the EWH consumption 5.75 -6.45 1.00 18468 1121 13.3 SMA strategy 4.71 -2.40 0.58 12839 44.42 2.51 Fuzzy NPT strategy 3.93 -2.12 0.49 11640 35.65 2.61 Fuzzy ERoC strategy 1.83 -2.04 0.32 817 56.15 2.79 Fuzzy EMS-FC strategy 1.89 -1.48 0.28 480 51.79 2.76 As it can be seen in Table 4-2, the fuzzy EMS-FC strategy achieves an important reduction in the performance indicators with respect to previous strategies. In short, the maximum power fed into the grid PG,MIN, PVR, MPD, APD and PPV quality criteria have been reduced in 27.4%, 12.5%, 41.2%, 7.8%, and 1.1%, respectively, with respect to the fuzzy ERoC strategy. Therefore, the slightly increase of the PG,MAX criterion can be considered irrelevant. 50%-60% 60%-70% 70%-80% 80%-90% 90%-100% 0 5 10 15 20 25 30 35 40 45 Battery SOC ranges Annual frequency (%) SMA strategy Fuzzy NPT Fuzzy ERoC Fuzzy EMS-FC 50%-60% 60%-70% 70%-80% 80%-90% 90%-100% 0 5 10 15 20 25 30 35 40 45 Battery SOC ranges Annual frequency (%) FLC-Based energy management strategy based on microgrid power forecasting 83 Finally, Fig. 4.16 compares the grid power ramp-rates achieved through the EMS strategies described so far. As it can be seen in Fig. 4.16(a) and Fig. 4.16(b), the grid power ramp-rates are reduced through the fuzzy EMS-FC strategy, which confirms the reduction of the MPD criterion reaching a maximum value of 480.5 W/h, as shown in Fig. 4.16(c). (a) (b) (c) Fig. 4.16. Simulation results for the fuzzy EMS-FC strategy excluding the EWH consumption (a) grid power ramp-rates comparison, (b) grid power ramp-rates comparison with respect to the fuzzy ERoC strategy, and (c) maximum grid power profile ramp-rate In the same manner of previous strategies, for comparison purposes the analysis of the fuzzy EMS-FC strategy is conducted including the EWH consumption. The simulation results are illustrated in Fig. 4.17 and Fig. 4.18, where it can be appreciated the enhanced behavior of the fuzzy EMS-FC strategy. In short, with respect to previous strategies, the grid power fluctuations are reduced, as shown in Fig. 4.17(a), while the energy stored in the battery is kept between secure limits, as illustrated in Fig. 4.17(b). In addition, the energy stored in the battery is kept in a range between the 70% and 80% of the rated battery capacity during the 47% of the year under study, as it can be seen in Fig. 4.17(c). Furthermore, the grid power ramp-rates are reduced with respect to previous strategies, as shown in Fig. 4.18(a) and Fig. 4.18(b), reaching a maximum grid power ramp-rate of 983.1 W/h, as is depicted in Fig. 4.18(c). Finally, this Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 2000 4000 6000 8000 10000 12000 14000 Months (2013-2014) P GRID ramp-rate (W/h) SMA strategy Fuzzy NPT Fuzzy ERoC Fuzzy EMS-FC Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 2000 4000 6000 8000 10000 12000 14000 Months (2013-2014) P GRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 Months (2013-2014) P GRID ramp-rate (W/h) Fuzzy ERoC Fuzzy EMS-FC Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 Months (2013-2014) P GRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 MPD: 480.5 (W/h) Months (2013-2014) P GRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 Months (2013-2014) P GRID ramp-rate (W/h) 84 Chapter 4 improved behavior is reflected in the reduction of the defined quality criteria summarized in Table 4-3. (a) (b) (c) Fig. 4.17. Simulation results accomplished through the defined EMS strategies including the EWH (a) grid power comparison, (b) battery SOC comparison, and (c) annual frequency of the battery SOC ranges Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) P GRID SMA Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) P GRID Fuzzy NPT Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) P GRID Fuzzy ERoC Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Months (2013-2014) Power ( kW ) P GRID Fuzzy EMS-FC Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Months (2013-2014) Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 Months (2013-2014) SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 Months (2013-2014) SOC ( % ) SOC SMA SOC Fuzzy NPT SOC Fuzzy ERoC SOC Fuzzy EMS-FC 50%-60% 60%-70% 70%-80% 80%-90% 90%-100% 0 5 10 15 20 25 30 35 40 45 50 Battery SOC ranges Annual frequency (%) SMA strategy Fuzzy NPT Fuzzy ERoC Fuzzy EMS-FC 50%-60% 60%-70% 70%-80% 80%-90% 90%-100% 0 5 10 15 20 25 30 35 40 45 50 Battery SOC ranges Annual frequency (%) FLC-Based energy management strategy based on microgrid power forecasting 85 (a) (b) (c) Fig. 4.18. Simulation results for the fuzzy EMS-FC strategy including the EWH consumption (a) grid power ramp-rates comparison with respect to the designed EMSs, (b) grid power ramp-rates comparison with respect to the fuzzy ERoC strategy, and (c) maximum grid power profile ramp-rate Table 4-3 Quality criteria comparison for the fuzzy EMS-FC strategy, the fuzzy ERoC strategy, the fuzzy NPT strategy, the SMA strategy and the baseline values including the EWH consumption EMS Strategy PG,MAX (kW) PG,MIN (kW) PVR MPD (W/h) APD (W/h) PPV No EMS & ESS including the EWH consumption 6.53 -6.45 1.00 18468 1221 5.99 SMA strategy 6.25 -3.98 0.79 20006 57.41 1.23 Fuzzy NPT strategy 5.80 -3.28 0.70 18119 50.81 1.31 Fuzzy ERoC strategy 2.94 -2.52 0.42 1252 79.93 1.51 Fuzzy EMS-FC strategy 2.46 -1.92 0.33 1016 75.93 1.42 Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 5000 10000 15000 20000 25000 Months (2013-2014) P GRID ramp-rate (W/h) SMA strategy Fuzzy NPT Fuzzy ERoC Fuzzy EMS-FC Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 5000 10000 15000 20000 25000 Months (2013-2014) P GRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 1200 1400 Months (2013-2014) PGRID ramp-rate (W/h) Fuzzy ERoC Fuzzy EMS-FC Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 1200 1400 Months (2013-2014) PGRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 1200 1400 MPD: 1016 (W/h) Months (2013-2014) PGRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 1200 1400 Months (2013-2014) PGRID ramp-rate (W/h) 86 Chapter 4 4.4. Experimental validation and analysis In the same manner that the fuzzy ERoC strategy, the fuzzy EMS strategy based on MG power forecasting is accomplished and compiled through LabVIEW® platform. The fuzzy EMS-FC strategy is experimentally tested from Sep. 1st to Oct. 25th, 2015. The experimental results for different months are presented from Fig. 4.19 to Fig. 4.22 [63]. Fig. 4.19 presents the forecasted and measured data from Sep. 8th to Sep. 14th, 2015 obtained by the MG at UPNa. As it can be seen, excluding the WT power generation shown in Fig. 4.19(b), the magnitude and evolution of the forecast data is similar than measured [63]. Although, these differences (i.e. forecast error) are compensated by the fuzzy EMS-FC strategy as shown in Fig. 4.20. (a) (b) (c) (d) Fig. 4.19. Forecasted and measured data obtained at UPNa MG from Sep. 08th to Sep.14th, 2015. (a) Photovoltaic power, (b) wind turbine power, (c) load power, and (d) MG net power 08 09 10 11 12 13 14 0 1 2 3 4 Power (kW) September 2015 P PV P PV,FC 08 09 10 11 12 13 14 0 1 2 3 4 Power (kW) September 2015 08 09 10 11 12 13 14 0 0.2 0.4 0.6 0.8 1 Power (kW) September 2015 PWT PWT,FC 08 09 10 11 12 13 14 0 0.2 0.4 0.6 0.8 1 Power (kW) September 2015 08 09 10 11 12 13 14 0 1 2 3 4 Power (kW) September 2015 PLOAD PLOAD,FC 08 09 10 11 12 13 14 0 1 2 3 4 Power (kW) September 2015 08 09 10 11 12 13 14 -4 -3 -2 -1 0 1 2 3 4 Power (kW) September 2015 PLG PLG,FC 08 09 10 11 12 13 14 -4 -3 -2 -1 0 1 2 3 4 Power (kW) September 2015 FLC-Based energy management strategy based on microgrid power forecasting 87 Fig. 4.20. Experimental results through the fuzzy EMS-FC strategy from Sep. 8th to Sep. 14, 2015 at UPNa MG As it can be seen in Fig. 4.20, the fuzzy EMS-FC strategy manages the battery power in order to absorb the MG net power fluctuations, consequently smoothing the grid power profile. Similarly, Fig. 4.21 illustrates the forecasted and measured data from Oct. 10th to Oct. 25th, 2015 obtained by the MG at UPNa [63]. (a) (b) 08 09 10 11 12 13 14 -4 -2 0 2 4 Power ( kW ) September 2015 50 60 70 80 90 100 SOC ( % ) P LG P BAT P GRID SOC 08 09 10 11 12 13 14 -4 -2 0 2 4 Power ( kW ) September 2015 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 0 1 2 3 4 Power (kW) October 2015 P PV P PV,FC 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 0 1 2 3 4 Power (kW) October 2015 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 0 1 2 3 Power (kW) October 2015 P WT P WT,FC 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 0 1 2 3 Power (kW) October 2015 88 Chapter 4 (c) (d) Fig. 4.21. Forecasted and measured data obtained at UPNa MG from Oct. 10th to Oct. 25th, 2015 (a) PV power generation, (b) WT power generation, (c) load demand, and (d) MG net power and resulting grid power profile Finally, Fig. 4.22 shows the resulting behavior featured by the fuzzy EMS-FC strategy, which validates the fuzzy EMS-FC strategy that concurrently minimizes the power profile exchanged with the grid and keeps the battery SOC between secure limits [63]. Fig. 4.22. Experimental results achieved through the fuzzy EMS based on MG power forecasting from Oct. 10th to Oct. 25th, 2015 at UPNa MG 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 0 1 2 3 Power (kW) October 2015 P LOAD P LOAD,FC 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 0 1 2 3 Power (kW) October 2015 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 -4 -3 -2 -1 0 1 2 3 4 Power (kW) October 2015 P LG P LG,FC P GRID 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 -4 -3 -2 -1 0 1 2 3 4 Power (kW) October 2015 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 -4 -2 0 2 4 Power ( kW ) October 2015 50 60 70 80 90 100 SOC ( % ) P LG P BAT P GRID SOC 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 -4 -2 0 2 4 Power ( kW ) October 2015 89 Chapter 5 FLC-based Energy management strategies for a residential grid-connected electro-thermal microgrid This Chapter presents the design and comparison of a fuzzy EMS strategies applied to an electro-thermal MG scenario. The electro-thermal MG scenario under study, shown in Fig. 5.1, includes renewable generation system (i.e. photovoltaic and wind generation), electric storage system (i.e. lead-acid battery bank), thermal generation system (i.e. electric water heater and solar thermal collectors), thermal storage system (i.e. water storage tank), and electric and thermal load demand (i.e. electrical appliances and domestic hot water consumption). In this new scenario, the main goal of the EMS strategy is to use the surplus power of the MG to supply the power required by the EWH in order to keep the water temperature in the storage tank between specific ranges. Fig. 5.1. Residential grid-connected electro-thermal microgrid In this regard, given the positive results achieved through the fuzzy EMS strategies described in Chapter 3.4 and Chapter 4 (i.e. fuzzy ERoC and fuzzy EMS-FC strategies), this Chapter 90 Chapter 5 proposes the use of the fuzzy-based EMS strategies in an electro-thermal MG scenario. Therefore, some variations in the control algorithms of the previous strategies are introduced with the purpose of using the energy stored in the ESS to supply part of the energy required by the EWH. In this manner, the EMS strategies minimize both the grid power profile and the amount of energy supplied by the mains to satisfy the EWH demand. 5.1. Fuzzy EMS strategy based on MG energy rate-of-change applied to an electro-thermal microgrid 5.1.1. Introduction The EMS strategy developed in Chapter 3.4 (i.e. fuzzy ERoC strategy) is now applied for an electro-thermal MG scenario, now referred as fuzzy ERoC ETH-MG strategy. In this scenario, the appropriate control of the EWH leads to concurrently minimize both the grid power consumption and the fluctuations in the power exchanged to the grid [55], [56]. The goal of the EMS strategy is the suitable use of the energy stored in the ESS to meet the load demand required by the EWH in order to keep the water temperature in the storage tank between the established limits. According to the configuration shown in Fig. 5.1 the grid power profile and the MG net power are defined as follows: , GRID LG BAT P PP= − (5.1) ,. LG LOAD GEN WH E PP P P= −+ (5.2) 5.1.2. Controller design The design follows the control policies described in Chapter 3.4 and includes some additional policies for the EWH control. The design includes an electric water heater (EWH) control block, which is used to calculate the amount of energy that the ESS supplies to the EHW, B WH P (n). By this way, the power required by the EWH is handled by the ESS and the mains, thus, reducing the MG net power (5.2) since now part of the energy is provided by the ESS instead by the mains. In this regard, the MG net power is modified as follows: * () () (), B LG LG WH Pn PnPn= − (5.3) where B WH P (n) is the amount of power delivered by the battery for the EWH consumption, which is assigned as follows: FLC-Based energy management strategies for a residential grid-connected electro-thermal microgrid 91 , 1, (), if () () 0 () , 0, otherwise WH E R WH E B WH P n SOC n SOC P n Pn >∧ >  =  (5.4) where SOCR1 is the threshold which allows the power injection from the ESS. Equation (5.4) highlights that the ESS will provide the EWH power as long as the battery has enough energy at the time that the EWH requires it. Therefore, according to (5.3) the amount of energy supplied by the mains is reduced. On the contrary, B WH P (n) is null for other cases, which implies that the energy supplied by the mains is maintained. As presented in Chapter 3.4, the grid power profile of the fuzzy ERoC strategy is defined as follows: * () () (), GRID AVG FLC P nP nPn= + (5.5) being * AVG P (n) the average net power of * LG P (n), which is computed as follows: ** 1 1 ( ) ( ), M AVG LG k P n P nk M = = − ∑ (5.6) In addition, the PFLC (n) component is computed by means of a FLC, which uses as input variables the battery SOC and the modified MG ERoC over time, * AVG P  (n). In this concern, the modified energy rate-of-change of the MG is defined as follows: * ** () () ( 1) . AVG AVG AVG s Pn PnPn T  = −−   (5.7) In contrast to the EMS strategy described in Chapter 3.4, the battery power PBAT (n), is now defined as the sum of two components as follows: () () (), MG B BAT BAT WH P nP nPn= + (5.8) () () (), MG BAT GRID LG P n P nPn= + (5.9) where MG BAT P (n) is computed through (5.1) and B WH P (n) is the power supplied by the ESS for the EWH consumption according to the conditions defined in (5.4). In this regard, the use of the energy stored in the ESS to supply part of the energy required by the EWH leads to the reduction of the energy supplied by the mains, which reduces the 98 Chapter 5 Fig. 5.8. Annual frequency of the battery SOC ranges established through the SMA, fuzzy NPT, fuzzy ERoC strategies including the EWH consumption and the fuzzy ERoC strategy applied to an electro-thermal MG Furthermore, in order to highlight the effectiveness of the fuzzy ERoC strategy applied to an electro-thermal MG, Fig. 5.9 presents the comparison of the principal variables of the MG during three consecutive days between the fuzzy ERoC strategy including the EWH consumption and the fuzzy ERoC ETH-MG strategy. Fig. 5.9. Grid power profile and battery SOC comparison between the fuzzy ERoC strategy including the EWH consumption and the fuzzy ERoC strategy applied to an electro-thermal MG 50%-60% 60%-70% 70%-80% 80%-90% 90%-100% 0 5 10 15 20 25 30 35 40 45 Battery SOC ranges Annual frequency (%) SMA strategy Fuzzy NPT Fuzzy ERoC Fuzzy ERoC ETH-MG 50%-60% 60%-70% 70%-80% 80%-90% 90%-100% 0 5 10 15 20 25 30 35 40 45 Battery SOC ranges Annual frequency (%) 09/11/2013 13:00:00 10/11/2013 13:00:00 11/11/2013 13:00:00 12/11/2013 13:00:00 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 Power ( kW ) PLG P* LG 09/11/2013 13:00:00 10/11/2013 13:00:00 11/11/2013 13:00:00 12/11/2013 13:00:00 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 Power ( kW ) 50 55 60 65 70 75 80 85 90 95 100 SOC ( % ) P GRID Fuzzy ERoC P GRID Fuzzy ERoC ETH-MG SOC Fuzzy ERoC SOC Fuzzy ERoC ETH-MG FLC-Based energy management strategies for a residential grid-connected electro-thermal microgrid 99 As it can be seen in Fig. 5.9(top), part of the power required by the EWH is supplied by the ESS; therefore, the MG net power (pink dot line) is reduced (mustard-colored solid line). Accordingly, the battery discharges reducing the energy stored in the ESS (green solid line) as shown in Fig. 5.9 (bottom). In addition, as shown in Fig. 5.9 (bottom), this behavior minimizes the grid power fluctuations (blue solid line) with respect to the fuzzy ERoC strategy including the EWH consumption (red dashed-line), since the ESS can absorb the future power generation produced by both RES, as it can be appreciated on Nov. 9th and 10th close to 13:00 PM. The proper behavior of the fuzzy ERoC strategy applied to an electro-thermal MG is verified through the analysis of the energy management quality criteria defined in Chapter 3.1.2, which are summarized in Table 5-2. Table 5-2 Quality criteria comparison for the fuzzy ERoC strategy applied to an electro-thermal microgrid, the fuzzy ERoC, the fuzzy NPT strategy, the SMA strategy and the baseline values including the EWH consumption EMS Strategy PG,MAX (kW) PG,MIN (kW) PVR MPD (W/h) APD (W/h) PPV No EMS & ESS including the EWH consumption 6.53 -6.45 1.00 18468 1221 5.99 SMA strategy 6.25 -3.98 0.79 20006 57.41 1.23 Fuzzy EMS based on MG net power trend 5.80 -3.28 0.70 18119 50.81 1.31 Fuzzy ERoC strategy including the EWH consumption 2.94 -2.52 0.42 1252 79.93 1.51 Fuzzy ERoC strategy applied to an electro-thermal MG 2.95 -2.31 0.41 1052 75.67 1.26 As it can be noticed, the fuzzy ERoC strategy applied to an electro-thermal MG achieves a reduction in five of the energy management quality criteria. In short, PG,MIN, PVR, MPD, APD, and PPV criteria are reduced in 8.3%, 2.4%, 16%, 5.3%, and16.6% with respect to the fuzzy ERoC strategy including the EWH consumption. Conversely, PG,MAX criterion exhibits a negligible increase that has not a negative impact on the global strategy features. Finally, the comparison of the grid power profile ramp-rates through the EMS strategies including the EWH consumption described in Chapter 3 and the fuzzy ERoC strategy applied to an electro-thermal MG is presented in Fig. 5.10. 100 Chapter 5 (a) (b) (c) Fig. 5.10. Grid power profile ramp-rates analysis (a) grid power ramp-rates comparison for the described EMS strategies, (b) grid power ramp-rates comparison with respect to the fuzzy ERoC strategy including the EWH consumption, and (c) maximum grid power profile ramp-rate achieved through the fuzzy ERoC ETH-MG strategy As it can be seen in Fig. 5.10(a) and Fig. 5.10(b), the grid power ramp-rates are reduced through the use of the electro-thermal MG, which confirms the reduction of the MPD criterion reaching a maximum value of 1052 W/h, as shown in Fig. 5.10(c). 5.2. Fuzzy EMS strategy based on MG power forecasting applied to an electro-thermal microgrid 5.2.1. Introduction Similarly to the previous design, the energy management strategy based on MG power forecasting is applied to an electro-thermal MG scenario. Similarly, the goal of the strategy is to control the ESS power to supply part of the power required by the EWH to keep the water temperature in the storage tank between the established limits. Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 5000 10000 15000 20000 25000 Months (2013-2014) PGRID ramp-rate (W/h) SMA strategy Fuzzy NPT Fuzzy ERoC Fuzzy ERoC ETH-MG Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 5000 10000 15000 20000 25000 Months (2013-2014) PGRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 1200 1400 Months (2013-2014) P GRID ramp-rate (W/h) Fuzzy ERoC Fuzzy ERoC ETH-MG Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 1200 1400 Months (2013-2014) P GRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 1200 1400 MPD: 1052 (W/h) Months (2013-2014) P GRID ramp-rate (W/h) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 0 200 400 600 800 1000 1200 1400 Months (2013-2014) P GRID ramp-rate (W/h) FLC-Based energy management strategies for a residential grid-connected electro-thermal microgrid 101 5.2.2. Controller design The block diagram of the fuzzy EMS-FC strategy presented in Chapter 4.2 is modified to include the EWH control block. In this regard, the new block diagram is illustrated in Fig. 5.11 and includes the blocks described in Chapter 4.2 as well as the EWH Control block presented in section 5.1.2. Fig. 5.11. Block diagram of the Fuzzy EMS-FC strategy applied to an electro-thermal microgrid In this regard, the control strategy developed in Chapter 4 is adapted in order to use the energy stored in the ESS to supply, as much as possible, the power required by the EWH. Similarly to the previous design, the use of the battery power, B WH P (n), to supply part of the power required by the EWH implies the reduction of the MG load demand. Thus, the load demand is modified as follows: *() () (). B LOAD LOAD WH PnPnPn= − (5.17) Fuzzy Logic Control + - 24H CMA Filter SOC Estimator + - 3H Filter LPF + - + + + EWH Control + + + - + + - 102 Chapter 5 Consequently, the load forecast is affected, thus, is necessary to recalculate the load forecast considering the modified load demand, * LOAD P (n). Hence, PLOAD,FC is changed into * ,LOAD FC P (n). In addition, according to (4.3) the forecast of the MG net power is modified as follows: ** , ,, () () (). LG FC LOAD FC GEN FC P nP nP n= − (5.18) The block diagram to calculate the forecast of the modified MG net power, * ,LG FC P (n) is displayed in Fig. 5.12. Note that the renewable generation power is not affected by the use of the EWH, thus, the forecast of power generation is maintained. Fig. 5.12. Net power forecasting block diagram Since a part of the power required by the EWH is supplied by the ESS the MG net power is modified as follows: * () () (). B LG LG WH Pn PnPn= − (5.19) According to (4.5) the grid power for the fuzzy EMS-FC applied to an electro-thermal MG scenario (fuzzy EMS-FC ETH-MG) is defined as follows: * () () () (), GRID CTR SOC FLC P nPnPnPn=++ (5.20) where * CTR P (n) is the modified average net power of the MG, which is calculated at each sample by means of both the modified MG net power * LG P (n) and the modified forecast of the MG net power * ,LG FC P (n). Note that for computing the modified average of the MG net power it is necessary to use the expressions from (4.6) to (4.8), which are defined in Chapter 4.2 by means of replacing PLG and PLG,FC for * LG P (n) and * ,LG FC P (n), respectively. Additionally, in order to compute the PFLC (n) component it is necessary to determine the modified forecast error of the MG for the previous 3-hours 3*H E P (n), which now is calculated as follows: ** * , () () (), E LG LG FC Pn P n P n= − (5.21) Load Forecasting + - + - FLC-Based energy management strategies for a residential grid-connected electro-thermal microgrid 103 3 3* * 1 3 1 ( ) ( ), M H EE k P n Pnk M = = − ∑ (5.22) Finally, the battery power and the energy saved during the year under study through the fuzzy EMS-FC strategy applied to an electro-thermal MG scenario are computed using from (5.8) to (5.13) 5.2.3. Fuzzy logic controller design The FLC design follows the procedure described in Chapter 4.2, but considering the modified power forecast error of the MG. In short, the FLC uses the same configuration (i.e. Mamdani-based inference and defuzzyfication of Center of Gravity), inputs [i.e. 3*H E P (n) and SOC (n)], output [i.e. PFLC (n)], and MFs number (i.e. 5 MFs for each input and 9 MFs for the output), type (i.e. triangular), and mapping (see Fig. 4.9) of the fuzzy EMS-FC strategy described in Chapter 4.2. However, due to the reduction of the MG net power, the reassignment of the limits of the FLC output is needed. Consequently, the optimization process will deliver a new set of rules to minimize the energy management quality criteria defined in Chapter 3.1.2 according to the new MG conditions. In this regard, the variation range for the output variable is established between PN = -0.8 kW and PP = 1.35 kW by the optimization procedure. The resulting rule-base is presented in Table 5-3. Table 5-3 Optimized fuzzy rule-base for the FLC of the fuzzy EMS-FC strategy applied to an electro-thermal microgrid PFLC (n) 3*H E P (n) NB NS ZE PS PB SOC (n) NB PB PM PS PM PB NS PM PS PSS PS PM ZE NS ZE ZE PSS NSS PS NM NS NSS NS NM PB NB NSS NM NM NB Finally, the block diagram of the FLC is shown in Fig. 5.13. Similarly to previous designs, the FLC assumes a Mamdani-based inference and defuzzyfication of Center of Gravity with two inputs, 3*H E P (n) and SOC (n), one output PFLC (n) and 25-rules. 104 Chapter 5 Fig. 5.13. Fuzzy logic system: 2 inputs, 1 output, and 25-rules 5.2.4. Simulation results and analysis The simulations results of the fuzzy EMS-FC strategy applied to an electro-thermal MG scenario are presented from Fig. 5.14 to Fig. 5.18. As aforementioned in section 5.2.2, the main objective of the strategy is to use the energy stored in the ESS to supply part of the energy required by the EWH, which results in minimizing the total load required by the MG, as can be seen in Fig. 5.14(a). Consequently, the EMS strategy should recalculate the load demand forecast considering its reduced value, this leading to decrease the load forecast, as can be appreciated in Fig. 5.14(b). Hence, the MG net power and its forecasts are modified, as displayed in Fig. 5.14(c) and Fig. 5.14(d). In the same manner, this behavior modifies the average net power profile of the MG, which now is lower than the initial value due to the reduction of the load demand, as can be illustrated in Fig. 5.15(a). Consequently, the new strategy reduces the grid power profile with respect to the fuzzy EMS-FC strategy, as can be seen in Fig. 5.15(b). In addition, Fig. 5.16 shows the grid power profile and the battery SOC comparison for the EMS strategies including the EWH consumption described in Chapter 3 and Chapter 4, and the fuzzy EMS-FC strategy applied to an electro-thermal MG scenario. As it can be seen, the use of the energy stored in battery to supply part of the energy required by the EWH leads to the reduction of the grid power profile, as shown in Fig. 5.16(a), since the discharge of the battery allows the ESS to absorb greater amount of energy produced by the RES. Additionally, Fig. 5.15(b) shows the battery SOC evolution during the year under study. As it can be seen, the fuzzy EMS-FC ETH-MG strategy satisfies the ESS constraints defined in Chapter 2.3.3. P 3H* E (n) (5) SOC(n) (5) P FLC (n) (9) FLC (Mamdani) 25-rules FLC-Based energy management strategies for a residential grid-connected electro-thermal microgrid 105 (a) (b) (c) (d) Fig. 5.14. Comparison between the initial and the modified variables of the MG (a) load demand comparison, (b) load demand forecast comparison, (c) MG net power comparison, and (d) forecast of the MG net power comparison (a) (b) Fig. 5.15. (a) Initial and modified average net power of the MG, (b) Grid power profile comparison between the fuzzy EMS-FC strategy including the EWH consumption and the fuzzy EMS-FC strategy applied to an electro-thermal MG 14/01/2014 13:00:00 15/01/2014 13:00:00 16/01/2014 13:00:00 17/01/2014 13:00:00 0 2 4 6 Power ( kW ) P LOAD P * LOAD 14/01/2014 13:00:00 15/01/2014 13:00:00 16/01/2014 13:00:00 17/01/2014 13:00:00 0 2 4 6 Power ( kW ) 14/01/2014 13:00:00 15/01/2014 13:00:00 16/01/2014 13:00:00 17/01/2014 13:00:00 0 2 4 6 Power ( kW ) P LOAD,FC P * LOAD,FC 14/01/2014 13:00:00 15/01/2014 13:00:00 16/01/2014 13:00:00 17/01/2014 13:00:00 0 2 4 6 Power ( kW ) 14/01/2014 13:00:00 15/01/2014 13:00:00 16/01/2014 13:00:00 17/01/2014 13:00:00 -6 -4 -2 0 2 4 6 Power ( kW ) P LG P * LG 14/01/2014 13:00:00 15/01/2014 13:00:00 16/01/2014 13:00:00 17/01/2014 13:00:00 -6 -4 -2 0 2 4 6 Power ( kW ) 14/01/2014 13:00:00 15/01/2014 13:00:00 16/01/2014 13:00:00 17/01/2014 13:00:00 -6 -4 -2 0 2 4 6 Power ( kW ) P LG,FC P * LG,FC 14/01/2014 13:00:00 15/01/2014 13:00:00 16/01/2014 13:00:00 17/01/2014 13:00:00 -6 -4 -2 0 2 4 6 Power ( kW ) Jan Feb -3 -2 -1 0 1 2 3 Months (2013-2014) Power ( kW ) P CTR P * CTR Jan Feb -3 -2 -1 0 1 2 3 Months (2013-2014) Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) Months (2013-2014) P GRID Fuzzy EMS-FC P GRID Fuzzy EMS-FC ETH-MG Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) Months (2013-2014) 106 Chapter 5 (a) (b) Fig. 5.16. Grid power profile and battery SOC comparison for the SMA, the fuzzy NPT, the fuzzy ERoC, and the fuzzy EMS-FC strategies including the EWH consumption and the fuzzy EMS-FC strategy applied to an electro-thermal MG Moreover, Fig. 5.17(a) depicts the distribution of the energy required by the EWH between the ESS and the mains. As it can be seen, the grid has a major contribution for the EWH consumption. Conversely, the ESS supplies an energy of only B WH E = 318.5 kWh during the year under study, which represents an 18.5% savings in the EWH consumption. Furthermore, Fig. 5.17(b) illustrates the SOC intervals where the battery is located the most of the year under study. As it can be seen, the results obtained through the fuzzy EMS-FC ETH-MG are similar than those obtained through the fuzzy EMS-FC including the EWH consumption. In short, the battery SOC is kept in the 70%-80% range of the rated battery capacity over the 45% of the year under study, which means that the ESS could further compensate the MG net power fluctuations while preserving the battery lifetime. Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) P GRID SMA Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) P GRID Fuzzy NPT Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) P GRID Fuzzy ERoC Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) P GRID Fuzzy EMS-FC Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Months (2013-2014) Power ( kW ) P GRID Fuzzy EMS-FC ETH-MG Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul -6 -4 -2 0 2 4 6 Months (2013-2014) Power ( kW ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 Months (2013-2014) SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 SOC ( % ) Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Jul 50 60 70 80 90 100 Months (2013-2014) SOC ( % ) SOC SMA SOC Fuzzy NPT SOC Fuzzy ERoC SOC Fuzzy EMS-FC SOC Fuzzy EMS-FC ETH-MG FLC-Based energy management strategies for a residential grid-connected electro-thermal microgrid 107 (a) (b) Fig. 5.17. (a) Contribution of the energy required by the EWH achieved through the fuzzy EMS-FC ETH-MG strategy, (b) Annual frequency of the battery SOC ranges achieved through the SMA, fuzzy NPT, fuzzy ERoC, the fuzzy EMS-FC strategies including the EWH consumption and the fuzzy EMS-FC strategy applied to an electro-thermal MG Moreover, the resulting values for the energy management quality criteria defined in Chapter 3.1.2 are summarized in Table 5-4 and confirm the proper behavior of the fuzzy EMS-FC strategy applied to an electro-thermal MG. Table 5-4 Quality criteria comparison for the fuzzy EMS-FC strategy applied to an electro-thermal microgrid, the fuzzy EMS-FC strategy, the fuzzy ERoC strategy, the fuzzy NPT strategy, the SMA strategy and the baseline values including the EWH consumption EMS Strategy PG,MAX (kW) PG,MIN (kW) PVR MPD (W/h) APD (W/h) PPV No EMS & ESS including the EWH consumption 6.53 -6.45 1.00 18468 1221 5.99 SMA strategy 6.25 -3.98 0.79 20006 57.41 1.23 Fuzzy EMS based on MG net power trend 5.80 -3.28 0.70 18119 50.81 1.31 Fuzzy ERoC strategy including the EWH consumption 2.94 -2.52 0.42 1252 79.93 1.51 Fuzzy EMS-FC strategy including the EWH consumption 2.46 -1.92 0.33 1016 75.93 1.42 Fuzzy EMS-FC strategy applied to an electro-thermal MG 2.56 -1.89 0.34 846 75.13 1.26 It can be noticed that the fuzzy EMS-FC strategy applied to an electro-thermal MG minimizes four of the defined quality criteria. MPD and PPV criteria are reduced in 16.7% and 11.2% with respect to the fuzzy EMS-FC strategy including the EWH consumption. Conversely, PG,MIN and APD criteria reach a minimum reduction, whereas PG,MAX and PVR criteria present an slightly increase, which do not represent a significant influence in the overall strategy performance. 14/01/2014 15/01/2014 16/01/2014 17/01/2014 0 2 4 6 8 10 12 14 X = 156 Y = 7.5 Energy ( kWh ) X = 156 Y = 6.5 X = 156 Y = 1 X = 159 Y = 9 X = 159 Y = 1.5 X = 159 Y = 7.5 Energy required by the EWH Energy supplied by the ESS Energy supplied by the mains 50%-60% 60%-70% 70%-80% 80%-90% 90%-100% 0 5 10 15 20 25 30 35 40 45 50 Battery SOC ranges Annual frequency (%) SMA strategy Fuzzy NPT Fuzzy ERoC Fuzzy EMS-FC Fuzzy EMS-FC ETH-MG 50%-60% 60%-70% 70%-80% 80%-90% 90%-100% 0 5 10 15 20 25 30 35 40 45 50 Battery SOC ranges Annual frequency (%) 115 References In reference to IEEE copyrighted material which is used with permission in this thesis, the IEEE does not endorse any of UPC’s products or services. Internal or personal use of this material is permitted. If interested in reprinting/republishing IEEE copyrighted material for advertising or promotional purposes or for creating new collective works for resale or redistribution, please go to http://www.ieee.org/publications standards/publications/ rights/rights link.html to learn how to obtain a License from RightsLink. [1] International Energy Agency, “Key World Energy Statistics 2015,” pp. 1–81, 2015. [2] International Energy Agency, “CO2 Emissions from Fuel Combustion Highlights,” IEA Stat., no. IEA - STATISTICS, pp. 1–15, 2015. [3] M. Soshinskaya, W. H. J. Crijns-Graus, J. M. Guerrero, and J. C. Vasquez, “Microgrids: Experiences, barriers and success factors,” Renew. Sustain. Energy Rev., vol. 40, pp. 659–672, Dec. 2014. [4] International Energy Agency, “Excerpt from Renewables Information (2015 Edition),” pp. 1–8, 2015. [5] H. Kanchev, D. Lu, F. Colas, V. Lazarov, and B. Francois, “Energy Management and Operational Planning of a Microgrid With a PV-Based Active Generator for Smart Grid Applications,” IEEE Trans. Ind. Electron., vol. 58, no. 10, pp. 4583–4592, Oct. 2011. [6] K. Rahbar, J. Xu, and R. Zhang, “Real-Time Energy Storage Management for Renewable Integration in Microgrid: An Off-Line Optimization Approach,” IEEE Trans. Smart Grid, vol. 6, no. 1, pp. 124–134, Jan. 2015. [7] P. Basak, S. Chowdhury, S. Halder nee Dey, and S. P. Chowdhury, “A literature review on integration of distributed energy resources in the perspective of control, protection and stability of microgrid,” Renew. Sustain. Energy Rev., vol. 16, no. 8, pp. 5545–5556, Oct. 2012. [8] W. Huang, M. Lu, and L. Zhang, “Survey on Microgrid Control Strategies,” Energy Procedia, vol. 12, pp. 206–212, 2011. [9] E. Unamuno and J. A. Barrena, “Hybrid ac/dc microgrids—Part I: Review and classification of topologies,” Renew. Sustain. Energy Rev., vol. 52, pp. 1251–1259, Dec. 2015. [10] D. E. Olivares, A. Mehrizi-Sani, A. H. Etemadi, C. a. Cañizares, R. Iravani, M. Kazerani, A. H. Hajimiragha, O. Gomis-Bellmunt, M. Saeedifard, R. Palma-Behnke, G. a. Jiménez-Estévez, and N. D. Hatziargyriou, “Trends in microgrid control,” IEEE Trans. Smart Grid, vol. 5, no. 4, pp. 1905–1919, 2014. [11] F. Katiraei, R. Iravani, N. Hatziargyriou, and A. Dimeas, “Microgrids management,” IEEE Power Energy Mag., vol. 6, no. 3, pp. 54–65, May 2008. [12] A. M. Bouzid, J. M. Guerrero, A. Cheriti, M. Bouhamida, P. Sicard, and M. Benghanem, “A survey on control of electric power distributed generation systems for microgrid applications,” Renew. Sustain. Energy Rev., vol. 44, pp. 751–766, Apr. 2015. [13] B. Lasseter, “Microgrids [distributed power generation],” in Proc. IEEE Power Engineering Society Winter Meeting, 2001, vol. 1, pp. 146–149. 116 References [14] R. H. Lasseter, “MicroGrids,” in IEEE Power Engineering Society Winter Meeting, 2002, vol. 1, pp. 305–308. [15] N. Hatziargyriou, Microgrids: Architectures and Control. Chichester, UK: Wiley, 2014. [16] N. Hatziargyriou, H. Asano, R. Iravani, and C. Marnay, “Microgrids,” IEEE Power Energy Mag., vol. 5, no. 4, pp. 78–94, Jul. 2007. [17] H. Laaksonen, “Technical Solutions for Low-Voltage Microgrid Concept,” Aalto University, 2011. [18] B. Liu, F. Zhuo, Y. Zhu, and H. Yi, “System Operation and Energy Management of a Renewable Energy-Based DC Micro-Grid for High Penetration Depth Application,” IEEE Trans. Smart Grid, vol. 6, no. 3, pp. 1147–1155, May 2015. [19] W. Su and J. Wang, “Energy Management Systems in Microgrid Operations,” Electr. J., vol. 25, no. 8, pp. 45–60, Oct. 2012. [20] M. Yazdanian and A. Mehrizi-Sani, “Distributed Control Techniques in Microgrids,” IEEE Trans. Smart Grid, vol. 5, no. 6, pp. 2901–2909, Nov. 2014. [21] Q. Jiang, M. Xue, and G. Geng, “Energy Management of Microgrid in Grid-Connected and Stand-Alone Modes,” IEEE Trans. Power Syst., vol. 28, no. 3, pp. 3380–3389, Aug. 2013. [22] A. Tascikaraoglu, A. R. Boynuegri, and M. Uzunoglu, “A demand side management strategy based on forecasting of residential renewable sources: A smart home system in Turkey,” Energy Build., vol. 80, pp. 309–320, 2014. [23] Y.-H. Chen, S.-Y. Lu, Y.-R. Chang, T.-T. Lee, and M.-C. Hu, “Economic analysis and optimal energy management models for microgrid systems: A case study in Taiwan,” Appl. Energy, vol. 103, pp. 145–154, Mar. 2013. [24] M. Marzband, A. Sumper, J. L. Domínguez-García, and R. Gumara-Ferret, “Experimental validation of a real time energy management system for microgrids in islanded mode using a local day-ahead electricity market and MINLP,” Energy Convers. Manag., vol. 76, pp. 314–322, Dec. 2013. [25] R. Palma-Behnke, C. Benavides, F. Lanas, B. Severino, L. Reyes, J. Llanos, and D. Saez, “A Microgrid Energy Management System Based on the Rolling Horizon Strategy,” IEEE Trans. Smart Grid, vol. 4, no. 2, pp. 996–1006, Jun. 2013. [26] P. Malysz, S. Sirouspour, and A. Emadi, “An Optimal Energy Storage Control Strategy for Grid-connected Microgrids,” IEEE Trans. Smart Grid, vol. 5, no. 4, pp. 1785–1796, Jul. 2014. [27] P. G. Arul, V. K. Ramachandaramurthy, and R. K. Rajkumar, “Control strategies for a hybrid renewable energy system: A review,” Renew. Sustain. Energy Rev., vol. 42, pp. 597–608, Feb. 2015. [28] J. M. Guerrero, J. C. Vasquez, J. Matas, L. G. de Vicuna, and M. Castilla, “Hierarchical Control of Droop-Controlled AC and DC Microgrids-A General Approach Toward Standardization,” IEEE Trans. Ind. Electron., vol. 58, no. 1, pp. 158–172, Jan. 2011. [29] O. Palizban, K. Kauhaniemi, and J. M. Guerrero, “Microgrids in active network management—Part I: Hierarchical control, energy storage, virtual power plants, and market participation,” Renew. Sustain. Energy Rev., vol. 36, pp. 428–439, Aug. 2014. References 117 [30] E. Unamuno and J. A. Barrena, “Hybrid ac/dc microgrids—Part II: Review and classification of control strategies,” Renew. Sustain. Energy Rev., vol. 52, pp. 1123– 1134, Dec. 2015. [31] D. Tran and A. M. Khambadkone, “Energy Management for Lifetime Extension of Energy Storage System in Micro-Grid Applications,” IEEE Trans. Smart Grid, vol. 4, no. 3, pp. 1289–1296, Sep. 2013. [32] M. Marinelli, F. Sossan, G. T. Costanzo, and H. W. Bindner, “Testing of a Predictive Control Strategy for Balancing Renewable Sources in a Microgrid,” IEEE Trans. Sustain. Energy, vol. 5, no. 4, pp. 1426–1433, Oct. 2014. [33] A. Anvari-Moghaddam, H. Monsef, and A. Rahimi-Kian, “Optimal Smart Home Energy Management Considering Energy Saving and a Comfortable Lifestyle,” IEEE Trans. Smart Grid, vol. 6, no. 1, pp. 324–332, Jan. 2015. [34] A. Anvari-Moghaddam, H. Monsef, A. Rahimi-Kian, J. M. Guerrero, and J. C. Vasquez, “Optimized energy management of a single-house residential micro-grid with automated demand response,” in 2015 IEEE Eindhoven PowerTech, 2015, pp. 1–6. [35] A. Anvari-Moghaddam, J. C. Vasquez, and J. M. Guerrero, “Load shifting control and management of domestic microgeneration systems for improved energy efficiency and comfort,” in Proc. IECON 41st Annu. Conf. IEEE Ind. Electron. Soc., 2015, pp. 000096 – 000101. [36] J. Pascual, P. Sanchis, and L. Marroyo, “Implementation and Control of a Residential Electrothermal Microgrid Based on Renewable Energies, a Hybrid Storage System and Demand Side Management,” Energies, vol. 7, no. 1, pp. 210–237, Jan. 2014. [37] D. Wang, S. Ge, H. Jia, C. Wang, Y. Zhou, N. Lu, and X. Kong, “A Demand Response and Battery Storage Coordination Algorithm for Providing Microgrid Tie-Line Smoothing Services,” IEEE Trans. Sustain. Energy, vol. 5, no. 2, pp. 476–486, Apr. 2014. [38] I. Prodan and E. Zio, “A model predictive control framework for reliable microgrid energy management,” Int. J. Electr. Power Energy Syst., vol. 61, pp. 399–409, 2014. [39] G. Bruni, S. Cordiner, V. Mulone, V. Rocco, and F. Spagnolo, “A study on the energy management in domestic micro-grids based on Model Predictive Control strategies,” Energy Convers. Manag., vol. 102, pp. 50–58, 2015. [40] P. García, J. P. Torreglosa, L. M. Fernández, and F. Jurado, “Optimal energy management system for stand-alone wind turbine/photovoltaic/hydrogen/battery hybrid system with supervisory control based on fuzzy logic,” Int. J. Hydrogen Energy, vol. 38, no. 33, pp. 14146–14158, Nov. 2013. [41] J. Lagorse, M. G. Simoes, and A. Miraoui, “A Multiagent Fuzzy-Logic-Based Energy Management of Hybrid Systems,” IEEE Trans. Ind. Appl., vol. 45, no. 6, pp. 2123–2129, 2009. [42] G. Kyriakarakos, A. I. Dounis, K. G. Arvanitis, and G. Papadakis, “A fuzzy logic energy management system for polygeneration microgrids,” Renew. Energy, vol. 41, pp. 315– 327, May 2012. [43] Y.-K. Chen, Y.-C. Wu, C.-C. Song, and Y.-S. Chen, “Design and Implementation of Energy Management System With Fuzzy Control for DC Microgrid Systems,” IEEE Trans. Power Electron., vol. 28, no. 4, pp. 1563–1570, Apr. 2013. 118 References [44] L. Roine, K. Therani, Y. S. Manjili, and M. Jamshidi, “Microgrid energy management system using fuzzy logic control,” in 2014 World Automation Congress (WAC), 2014, pp. 462–467. [45] R. G. C. Secretariat, “Grid connection code for renewable power plants (RPPs) connected to the Electricity Transmission System (TS) or the Distribution System (DS) in South Africa,” 2012. [46] J. Pascual, “Estrategias avanzadas de gestión energética basadas en prediccion para microrredes electrotérmicas,” Universidad Pública de Navarra, Pamplona, España, 2015. [47] W. A. Bisschoff and R. Gouws, “Energy management system for a residential grid-tied micro-grid,” in 2015 International Conference on the Domestic Use of Energy (DUE), 2015, pp. 85–91. [48] R. Hanna, J. Kleissl, A. Nottrott, and M. Ferry, “Energy dispatch schedule optimization for demand charge reduction using a photovoltaic-battery storage system with solar forecasting,” Sol. Energy, vol. 103, pp. 269–287, May 2014. [49] H. Zhou, T. Bhattacharya, D. Tran, T. S. T. Siew, and A. M. Khambadkone, “Composite Energy Storage System Involving Battery and Ultracapacitor With Dynamic Energy Management in Microgrid Applications,” IEEE Trans. Power Electron., vol. 26, no. 3, pp. 923–930, Mar. 2011. [50] J. Barricarte, “Integración en la red eléctrica de microrredes electrotérmicas: dimensionado, estrategias de gestión energética e implementación experimental,” Universidad Pública de Navarra, Pamplona, España, 2011. [51] D. A. Aviles, F. Guinjoan, J. Barricarte, L. Marroyo, P. Sanchis, and H. Valderrama, “Battery management fuzzy control for a grid-tied microgrid with renewable generation,” in Proc. IECON 38th Annu. Conf. IEEE Ind. Electron. Soc., 2012, pp. 5607–5612. [52] D. Arcos-Aviles, N. Espinosa, F. Guinjoan, L. Marroyo, and P. Sanchis, “Improved Fuzzy Controller Design for Battery Energy Management in a Grid Connected Microgrid,” in Proc. IECON 40th Annu. Conf. IEEE Ind. Electron. Soc., 2014, pp. 2128– 2133. [53] D. Arcos-Aviles, J. Pascual, L. Marroyo, P. Sanchis, F. Guinjoan, and M. P. Marietta, “Optimal Fuzzy Logic EMS design for residential grid-connected microgrid with hybrid renewable generation and storage,” in Proc. IEEE 24th Int. Symp. Ind. Electron. (ISIE), 2015, pp. 742–747. [54] D. Arcos-Aviles, J. Pascual, L. Marroyo, P. Sanchis, and F. Guinjoan, “Fuzzy Logic- Based Energy Management System Design for Residential Grid-Connected Microgrids,” IEEE Trans. Smart Grid, pp. 1–14, Apr. 2016. [55] D. Arcos-Aviles, C. Vega, F. Guinjoan, L. Marroyo, and P. Sanchis, “Fuzzy logic controller design for battery energy management in a grid connected electro-thermal microgrid,” in Proc. IEEE 23th Int. Symp. Ind. Electron. (ISIE), 2014, pp. 2014–2019. [56] D. Arcos-Aviles, F. Guinjoan, and L. Marroyo, “Estrategia de gestión energética mediante controladores fuzzy logic para sistemas de almacenamiento de una microrred electro-térmica con conexión a red,” Rev. Cienc., vol. 16, no. 2, pp. 193–207, Sep. 2014. [57] J. Pascual, J. Barricarte, P. Sanchis, and L. Marroyo, “Energy management strategy for a renewable-based residential microgrid with generation and demand forecasting,” Appl. Energy, vol. 158, pp. 12–25, Nov. 2015. References 119 [58] K. Passino and S. Yurkovich, Fuzzy Control. Menlo Park, CA: Addisson-Wesley, 1998. [59] M. Serraji, J. Boumhidi, and E. H. Nfaoui, “MAS energy management of a microgrid based on fuzzy logic control,” in 2015 Intelligent Systems and Computer Vision (ISCV), 2015, pp. 1–7. [60] A. Mohamed and O. Mohammed, “Real-time energy management scheme for hybrid renewable energy systems in smart grid applications,” Electr. Power Syst. Res., vol. 96, pp. 133–143, Mar. 2013. [61] J. P. Fossati, A. Galarza, A. Martín-Villate, J. M. Echeverría, and L. Fontán, “Optimal scheduling of a microgrid with a fuzzy logic controlled storage system,” Int. J. Electr. Power Energy Syst., vol. 68, pp. 61–70, Jun. 2015. [62] D. Arcos-Aviles, F. Guinjoan, P. M. Marietta, J. Pascual, L. Marroyo, and P. Sanchis, “Energy management strategy for a grid-tied residential microgrid based on fuzzy logic and power forecasting,” submitted paper, 2016. [63] D. Arcos-Aviles, J. Pascual, L. Marroyo, P. Sanchis, and Francesc Guinjoan, “Fuzzy Logic Controller Design for Energy Management in a Grid Connected Residential Microgrid with Generation and Demand Forecasting,” working paper, 2016. [64] B. Solar, “BP585,” 2002. [Online]. Available: http://www.comel.gr/pdf/bpsolar/BP585.pdf. [Accessed: 08-Mar-2016]. [65] Bornay, “Aerogenerador Bornay 6000,” 2010. [Online]. Available: http://www.bornay.com/userfiles/descargas/bornay_6000_rev_6.pdf. [Accessed: 08- Mar-2016]. [66] AMETEK, “AMREL eLoad PLA Series,” 2014. [Online]. Available: http://www.programmablepower.com/electronicload/PLA/downloads/PLA_Datasheet.pdf. [Accessed: 08-Mar-2016]. [67] FIAMM, “SMG (OPzV).” [Online]. Available: http://www.interstatebatteries.com/powercare/stationary/pdf/SMG_OPzV_VRLA.pdf. [Accessed: 08-Mar-2016]. [68] Ingeteam Energy S.A., “Manual de Instalación Ingecon Hybrid MS,” 2010. [Online]. Available: http://www.ingeteam.com/Portals/0/Catalogo/Producto/Documento/PRD_128_Archivo_ ptd22-manual-de-instalacion-ingecon-hybrid-ms.pdf. [Accessed: 08-Mar-2016]. [69] National Instruments, “PXI Platform,” 2016. [Online]. Available: http://www.ni.com/pxi/#. [Accessed: 08-Mar-2016]. [70] D. Rekioua and E. Matagne, Optimization of Photovoltaic Power Systems. London: Springer London, 2012. [71] A. H. Fathima and K. Palanisamy, “Optimization in microgrids with hybrid energy systems – A review,” Renew. Sustain. Energy Rev., vol. 45, pp. 431–446, May 2015. [72] B. Zhao, X. Zhang, J. Chen, C. Wang, and L. Guo, “Operation Optimization of Standalone Microgrids Considering Lifetime Characteristics of Battery Energy Storage System,” IEEE Trans. Sustain. Energy, vol. 4, no. 4, pp. 934–943, Oct. 2013. [73] J. Yoo, B. Park, K. An, E. A. Al-Ammar, Y. Khan, K. Hur, and J. H. Kim, “Look-Ahead Energy Management of a Grid-Connected Residential PV System with Energy Storage under Time-Based Rate Programs,” Energies, vol. 5, no. 12, pp. 1116–1134, Apr. 2012. 120 References [74] F. Bizzarri, M. Bongiorno, A. Brambilla, G. Gruosso, and G. S. Gajani, “Model of Photovoltaic Power Plants for Performance Analysis and Production Forecast,” IEEE Trans. Sustain. Energy, vol. 4, no. 2, pp. 278–285, Apr. 2013. [75] E. Lorenzo, “Energy Collected and Delivered by PV Modules,” in Handbook of Photovoltaic Science and Engineering, A. Luque and S. Hegedus, Eds. Chichester, UK, UK: John Wiley & Sons, Ltd, 2011, pp. 984–1042. [76] S. Mathew, “Wind energy : fundamentals, resource analysis and economics,” Berlin: Springer, 2006, pp. 11–88. [77] W. T. Chong, W. P. Hew, S. Y. Yip, A. Fazlizan, S. C. Poh, C. J. Tan, and H. C. Ong, “The experimental study on the wind turbine’s guide-vanes and diffuser of an exhaust air energy recovery system integrated with the cooling tower,” Energy Convers. Manag., vol. 87, pp. 145–155, Nov. 2014. [78] J. F. Manwell, J. G. McGowan, and A. L. Rogers, “Wind Energy Explained: Theory, Design and Application,” Chichester, UK: John Wiley & Sons, Ltd, 2009, pp. 23–87. [79] C. Ally, S. Bahadoorsingh, A. Singh, and C. Sharma, “A review and technical assessment integrating wind energy into an island power system,” Renew. Sustain. Energy Rev., vol. 51, pp. 863–874, Nov. 2015. [80] Danish wind industry Association, “Wind Energy Reference Manual Part 1: Wind Energy Concepts.” [Online]. Available: http://drømstørre.dk/wpcontent/wind/miller/windpower web/en/stat/unitsw.htm#roughness. [81] D. A. J. Rand and P. T. Moseley, “Energy Storage with Lead–Acid Batteries,” in Electrochemical Energy Storage for Renewable Sources and Grid Balancing, P. T. Moseley and G. Jürgen, Eds. Kidlington: Elsevier, 2015, pp. 201–222. [82] H. Tazvinga, B. Zhu, and X. Xia, “Optimal power flow management for distributed energy resources with batteries,” Energy Convers. Manag., vol. 102, pp. 104–110, Sep. 2015. [83] J. P. Fossati, A. Galarza, A. Martín-Villate, and L. Fontán, “A method for optimal sizing energy storage systems for microgrids,” Renew. Energy, vol. 77, pp. 539–549, 2015. [84] F. Guo, H. Li, C. Yao, M. Alsolami, A. Lang, X. Lu, and J. Wang, “Residential usage profile optimization and experimental implementation of the retired HEV battery with a hybrid microgrid testbed,” in 2014 IEEE Energy Conversion Congress and Exposition (ECCE), 2014, pp. 428–435. [85] S. Anuphappharadorn, S. Sukchai, C. Sirisamphanwong, and N. Ketjoy, “Comparison the Economic Analysis of the Battery between Lithium-ion and Lead-acid in PV Standalone Application,” Energy Procedia, vol. 56, pp. 352–358, 2014. [86] J. A. Duffie and W. A. Beckman, Solar Engineering of Thermal Processes, 4th ed. Hoboken, NJ, EEUU: John Wiley & Sons, Inc., 2014. [87] S. A. Kalogirou, Solar Energy Engineering Processes and Systems. Burlington, MA, EEUU: Elsevier, 2009. [88] T. L. Bergman, A. S. Lavine, F. P. Incropera, and D. P. Dewitt, Fundamentals of Heat and Mass Transfer, 7th ed. Hoboken, NJ, USA: John Wiley & Sons, Inc., 2011. [89] F. H. Fahmy, D. M. Atia, N. M. A. El-Rahman, and H. T. Dorrah, “Optimal sizing of solar water heating system based on genetic algorithm for aquaculture system,” in 2010 References 121 International Conference on Chemistry and Chemical Engineering, 2010, pp. 221–226. [90] D. Wang and Y. Liu, “Study on Heat Storage Tank of Solar Heating System,” in 2010 International Conference on Digital Manufacturing & Automation, 2010, vol. 2, pp. 493–497. [91] L. Zhang, N. Gari, and L. V. Hmurcik, “Energy management in a microgrid with distributed energy resources,” Energy Convers. Manag., vol. 78, pp. 297–305, Feb. 2014. [92] Seul-Ki Kim, Jin-Hong Jeon, Chang-Hee Cho, Jong-Bo Ahn, and Sae-Hyuk Kwon, “Dynamic Modeling and Control of a Grid-Connected Hybrid Generation System With Versatile Power Transfer,” IEEE Trans. Ind. Electron., vol. 55, no. 4, pp. 1677–1688, Apr. 2008. [93] J. Pascual, I. S. Martín, A. Ursúa, P. Sanchis, and L. Marroyo, “Implementation and control of a residential microgrid based on renewable energy sources , hybrid storage systems and thermal controllable loads,” in 2013 IEEE Energy Conversion Congress and Exposition (ECCE), 2013, pp. 2304–2309. [94] T. Butz, Fourier Transformation for Pedestrians, Second. Cham, Switzerland: Springer International Publishing, 2015. [95] Kiam Heong Ang, G. Chong, and Yun Li, “PID control system analysis, design, and technology,” IEEE Trans. Control Syst. Technol., vol. 13, no. 4, pp. 559–576, Jul. 2005. [96] J. Marcos, I. de la Parra, M. García, and L. Marroyo, “Control Strategies to Smooth Short-Term Power Fluctuations in Large Photovoltaic Plants Using Battery Storage Systems,” Energies, vol. 7, no. 10, pp. 6593–6619, Oct. 2014. [97] National Instruments, “Fuzzy System Designer,” 2011. [Online]. Available: http://zone.ni.com/reference/en-XX/help/370401H-01/lvpid/fuzzy_system_designer_db/. [Accessed: 08-Mar-2016]. [98] Meteogalicia, “Servidor THREDDS de MeteoGalicia.” [Online]. Available: http://www.meteogalicia.es/web/index.action. [Accessed: 10-Mar-2016]. [99] A. M. Foley, P. G. Leahy, A. Marvuglia, and E. J. McKeogh, “Current methods and advances in forecasting of wind power generation,” Renew. Energy, vol. 37, no. 1, pp. 1– 8, Jan. 2012. [100] C. Yang, A. A. Thatte, and L. Xie, “Multitime-Scale Data-Driven Spatio-Temporal Forecast of Photovoltaic Generation,” IEEE Trans. Sustain. Energy, vol. 6, no. 1, pp. 104–112, Jan. 2015. [101] X. Lü, T. Lu, C. J. Kibert, and M. Viljanen, “A novel dynamic modeling approach for predicting building energy performance,” Appl. Energy, vol. 114, pp. 91–103, Feb. 2014. [102] H. Madsen, P. Pinson, G. Kariniotakis, H. A. Nielsen, and T. Nielsen, “Standardizing the Performance Evaluation of ShortTerm Wind Power Prediction Models,” Wind Eng., vol. 29, no. 6, pp. 475–489, Dec. 2005. [103] C. Vamos and M. Craciun, “Noise Smoothing,” in Automatic Trend Estimation, C. Vamos and M. Craciun, Eds. Dordrecht: Springer Netherlands, 2012, pp. 43–59.