An intelligent electronic fuse for selective isolation of faulty switching cells in power electronic converter legs to guarantee continuous operation

Filba Martínez, Àlber,Busquets Monge, Sergio,Alepuz Menéndez, Salvador,García Rojas, Gabriel,Luque Acera, Adrià,Bordonau Farrerons, José

Abstract

This article proposes a novel device designated as an intelligent electronic fuse (iFuse) intended to be connected in series with any current-bidirectional voltage-unidirectional active switch present in a power converter. The iFuse duty is to selectively isolate its series-associated switch from the rest of the converter circuit immediately after detecting that this switch has failed in short circuit. Nonetheless, it maintains the reverse (free-wheeling) current path originally offered by the failed switch. The failure detection is typically performed when the failed switch causes a shoot-through event. Therefore, the iFuse is able to block large currents. The iFuse allows increasing the power-converter fault tolerance and reliability with regard to switch short-circuit failures (SCFs), as in converters featuring switches in parallel, redundant legs, and multilevel neutral-point-clamped topologies. The reliability model analysis of a two-level converter leg with two parallel switches per position reveals that its reliability can be increased up to four times when an iFuse is implemented in series with each switch. The iFuse device feasibility and good performance are verified through experimental tests, proving that it can detect and isolate the associated-switch failure in 6 µs , while stopping short-circuit currents of up to 1 kA without incurring in harmful di / dt values.

Full text

1 JESTPE-2022-02-0172.R1 An Intelligent Electronic Fuse for Selective Isolation of Faulty Switching Cells in Power Electronic Converter Legs to Guarantee Continuous Operation Alber Filba-Martinez, Sergio Busquets-Monge, Senior Member, IEEE, Salvador Alepuz, Senior Member, IEEE, Gabriel Garcia-Rojas, Adria Luque, and Josep Bordonau, Member, IEEE Abstract- This paper proposes a novel device designated as an intelligent electronic fuse (iFuse) intended to be connected in series with any current-bidirectional voltage-unidirectional active switch present in a power converter. The iFuse duty is to selectively isolate its series-associated switch from the rest of the converter circuit immediately after detecting that this switch has failed in short circuit. Nonetheless, it maintains the reverse (freewheeling) current path originally offered by the failed switch. The failure detection is typically performed when the failed switch causes a shoot-through event. Therefore, the iFuse is able to block large currents. The iFuse allows increasing the power-converter fault tolerance and reliability with regard to switch short-circuit failures, as in converters featuring switches in parallel, redundant legs, and multilevel neutral-point-clamped topologies. The reliability model analysis of a two-level converter leg with two parallel switches per position, reveals that its reliability can be increased up to four times when an iFuse is implemented in series with each switch. The iFuse device feasibility and good performance is verified through experimental tests, proving that it can detect and isolate the associated-switch failure in 6 µs, while stopping short-circuit currents of up to 1 kA without incurring in harmful di/dt values. I. INTRODUCTION At present day, power electronics is an essential subsystem in an extensive range of applications and power ratings [1]. Some of these applications are categorized as critical, that is, the continuity of the service must be assured at all time, mainly because of safety or economic reasons [2], not allowing an unexpected system shutdown, although a degraded operation can be eventually accepted [3]. Therefore, fault-tolerant operation of the system, and specifically of the power electronics converter, is required [3]. For example, in electric vehicles, a motor drive failure may risk the passenger safety [2]–[4], and a limp-home mode is desirable. It is estimated that typically 50% of faults in power converters are due to power switch failures [5], [6], which are This publication is part of Grant DPI2017-89153-P, funded by MCIN/AEI/10.13039/501100011033 and by ERDF A way of making Europe. (Corresponding author: Alber Filba-Martinez). A. Filba-Martinez is with Electronic Engineering Department, Universitat Politècnica de Catalunya, 08028-Barcelona, Spain and Power Systems Group, Catalonia Institute for Energy Research, 08930 Sant Adrià del Besòs, Spain (email: [email protected]). typically caused by power-semiconductor damage or switchgate-driver damage or malfunction [7]. Moreover, these failures typically cause the power switch to remain in a permanent OFF state; i.e., a switch open-circuit failure (OCF) , or to remain in a permanent low-ohmic ON state; i.e., a switch short-circuit failure (SCF) [8]. The ease in achieving fault tolerance depends on the type of switch fault. In a voltage-source converter topology, a switch OCF provides inherent fault isolation. In contrast, a switch SCF implies the short-circuit of a voltage source; i.e., a shootthrough event, when the switch complementary to the failed switch is turned on. A simple example is power converters employing parallel switches for reduced conduction losses, as in the two-level three-phase traction inverter of Tesla Model S, with six parallel discrete IGBTs per switch position [9]. Thanks to the inherent redundancy provided by the parallel switches, these converters can sustain multiple switch OCFs. However, a SCF of one of the switches forces disabling the whole converter leg in order to avoid a shoot-through event, and converter operation must stop. Another example are converters employing active neutralpoint-clamped (ANPC) topologies, which also feature inherent redundancy thanks to the multiple leg switching states available. As shown in [10], when SCFs occur in an ANPC leg, the resulting switching states feature, on average, less available connections to the dc-link points than in the switch OCF case. There are solutions in the literature to reduce the impact caused by switch SCFs on converters fault tolerance. These solutions consist on introducing additional hardware in order to isolate the switch in SCF, or the part of the circuit affected by the switch SCF, from the rest of the circuit. For instance, [11]– [13] present dc-ac fault-tolerant power converters with leg redundancy. In [11] a fast fuse in series with each active switch S. Busquets-Monge, G. Garcia-Rojas, A. Luque and J. Bordonau are with the Electronic Engineering Department, Universitat Politècnica de Catalunya, 08028-Barcelona, Spain (e-mail: sergio.busq[email protected]; gabriel. [email protected]u; [email protected]m; [email protected]). S. Alepuz is with the Escola Superior Politècnica, Tecnocampus Mataró- Maresme, Universitat Pompeu Fabra, 08302-Mataró, Spain (e-mail: [email protected]rg). This article has been accepted for publication in IEEE Journal of Emerging and Selected Topics in Power Electronics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/JESTPE.2022.3183160 © 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. 2 JESTPE-2022-02-0172.R1 is employed, such that when a shoot-through event occurs due to a switch SCF, the fuses are blown, isolating the short-circuit failed switches from the switching-leg output. However, there is no guarantee that the fuse in series with the short-circuited switch will blow, since the fuse of the complementary switch could blow first. A more advanced solution is proposed in [12] for the same topology, where again a fast fuse is placed in series with each active switch but the fuses are selectively blown with a robust active switch (thyristor) and the energy stored in the dc link. In contrast, [13] presents a two-level three-phase dc-ac converter employing two switches in series per position (one of them in permanent ON state) and two legs per phase (one of them in stand-by). When a switch SCF or OCF occurs on the active leg, all switches in this leg are turned off and the redundant leg is enabled and operated with the same switching strategy as the faulty leg previous to the fault. In [10], the connection of the active switches to the dc-link capacitors in an ANPC leg can be opened through four-quadrant (4Q) switches, in order to cut the short-circuit current path. Similarly, in [14], the connection of a three-level ANPC leg to the dc-link neutral point can be opened through a fast fuse placed in the connection path. As in [11], these fuses are deliberately blown with thyristors and the energy stored in the dc-link capacitors. After opening the dc-link-neutral-point connection, an alternative modulation strategy is employed to operate the converter with the remaining switching states. A similar approach is proposed in [15] for a multilevel converter employing a flying-capacitor topology, where 4Q switches are employed to disconnect the necessary flying capacitors to avoid the shoot-through event caused by a switch SCF. The presented solutions mitigate the consequences of switch SCFs, but present some drawbacks. For instance, fuses are bulky [16] and its typical melting profile requires a short-circuit current much higher than the nominal current to have reduced melting times [16], which could lead the healthy devices in the short-circuit current path to fail. Also, the fuse resistance and stray inductance increase the conduction losses and voltage spikes during switching transitions in normal operation [2]. Replacing fuses with switches allows performing the isolation action in less time and yields less conduction losses during normal operation [13]. Nonetheless, all the solutions employing switches to open the short-circuit current path caused by a switch SCF [10], [13], [15] rely on a centralized control that first has to detect the failure and then commands the turn off of the corresponding protection switch. Typical solutions to open the short-circuit current path caused by a switch SCF without relying on a centralized control employ either switch gate drivers with short-circuit protection (GDSCP), solid-state circuit breakers (SSCB) [17], or electronic fuses (eFuses) [18]–[20]. It should be noted that eFuses and SSCBs are equivalent in their basic functionality when protecting against a short-circuit current and, from now on, both will be referred as eFuses. For instance, eFuses could replace the fast fuses employed in the fault-tolerant converters from [11], [12], and [14]. A general solution would be employing a GDSCP for each switching device or placing an eFuse in series with each device. Nonetheless, this general solution is not satisfactory since it cannot provide selective isolation of the short-circuit-failed switch. This is illustrated in Fig. 1, which assumes an initial switch SCF on a two-level leg with two parallel devices per position. As shown in Fig. 1(a), when the GDSCP is employed as a protection mechanism, the short-circuit current flowing through switches S1a and S1b is detected by their corresponding GDSCP and both switches are subsequently turned off. This scenario ends up in a state where the leg output terminal can no longer be connected to dc-link point 1 (it is permanently connected to point 2), and the leg must stop its operation. As shown in Fig. 1(b), when eFuses are employed as protection devices, and assuming that they are configured to trip as soon as a short-circuit current is detected, all three eFuses in the short-circuit path will trip, leaving the leg output terminal floating. The leg output terminal can no longer be connected to point 1 and the leg must stop operating. Therefore, currently existing standalone protection devices do not allow the selective isolation of the switches in SCF, which is necessary to take full advantage of the switch-level redundancy offered by many topologies. Consequently, it is desirable to conceive a device with such selective isolation capability, able to transform all switch failures into an equivalent OCF. This paper proposes a new device to accomplish the above purpose, designated as intelligent electronic fuse (iFuse). The iFuse is conceived to be connected in series with a CBVU active switch, performing an automatic continuous monitoring at component level of its associated active switch in order to detect its failure. In case the failure of the associated active switch is detected, the iFuse proceeds to block the forward current path, stopping the eventual short-circuit current and preventing future shoot-through events. Moreover, it also maintains the free-wheeling path that was offered by the active switch previous to the failure. This principle of operation is illustrated in Fig. 1(c), where the iFuse in series with the shortcircuit-failed switch opens the short-circuit current path, while the rest of iFuses in the same path remain ON. Thanks to this, the switch SCF isolation process is performed in a stand-alone manner, and the converter leg can reliably continue its operation without any break or change in the operating strategy. Thus, the proposed iFuse allows the fault-tolerant operation of power converters under switch SCFs taking full advantage of the converter switch-level redundancy, and significantly improving the reliability of the converter itself and the system where it is employed. The manuscript is organized as follows. Section II describes the functional blocks constituting the iFuse and its working principle. Section III describes which kind of power converters would be most benefited in terms of fault-tolerance by incorporating iFuses. Section IV demonstrates the reliability increase thanks to the use of the iFuse in a two-level inverter leg with two parallel switches per position. Section V presents This article has been accepted for publication in IEEE Journal of Emerging and Selected Topics in Power Electronics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/JESTPE.2022.3183160 © 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. 3 JESTPE-2022-02-0172.R1 experimental results to demonstrate the feasibility and good performance of the proposed iFuse device. Finally, Section VI outlines the conclusions. II. IFUSE CONFIGURATION AND OPERATING PRINCIPLE Fig. 2 presents a diagram of the series connection of an iFuse with a CBVU active switch (Sm). This series connection can be regarded as a new compound device; i.e., a switching cell (SC), featuring power terminals pt1 and pt2, input binary signal S for the control of Sm, and output binary signal st to report the health status of Sm. The iFuse is composed of an active switch (SiF) together with its driving circuitry, the circuitry to quickly diagnose Sm fault, and the iFuse power supply. SiF is a CBVU switch. This allows maintaining the freewheeling path after the Sm SCF, which in pre-fault condition is offered by Sm antiparallel diode. The diode shown in the iFuse symbol of Fig. 2(a) denotes the availability of the abovementioned freewheeling path. Isolated drivers are required to transfer digital signals between the converter control and the converter power circuit. The self-powered-supply circuit conceived in [21] can be used to power the gate driver of Sm (GDPS) and the iFuse circuitry (iFPS) by recycling Sm turn-off switching losses. Fig. 3 and Fig. 4 show in full detail the circuit of the four main functional blocks making up the proposed iFuse. An nchannel metal-oxide-semiconductor field-effect transistor (MOSFET) is here selected to implement the SiF switch. The Sm-fault automatic-detection circuitry is composed of the forward-current detection circuit (FCDC) and the fault detection logic (FDL). Fig. 4 shows the circuit of the iFPS, following the design of [21] but modified to deliver two voltage supplies, Vfuse and Vcc, the latter stabilized with linear voltage regulator U5. The iFPS is isolated from the power converter control and does not require or involve any inductive, capacitive or optical coupling with any circuit outside the SC. Thus, it is not affected by the floating nature and switching voltage of nodes pt1 and pt2. Fig. 5 shows the evolution of the main iFuse analog and digital signals described in this section. The compound device shown in Fig. 2(a) is to be integrated in a power converter. A SCF of Sm will be typically followed by a switching state where Sm control signal is low (S = 0) and a positive current iS flows through Sm, with reference to Fig. 2(b). The proposed iFuse solution will stand-alone detect this situation to diagnose the SCF of Sm, to then immediately isolate it from the rest of the circuit by blocking its forward current path. (a)  Connection to node 1 lost. Leg operation stops.  No connection lost. Leg operation continues. (b) (c) Initial state Protection activation Final state  Connection to node 1 lost. Leg operation stops. S 2a S 1b S 1a S 2b 2 1 eFuse eFuse eFuseeFuse S 2a S 1b S 1a S 2b 2 1 iFuse iFuse iFuse iFuse S 2a S 1b S 1a S 2b 2 1 GD SCP GD SCP GD SCP GD SCP eFuse eFuse eFuseeFuse iFuse iFuse iFuse iFuse GD SCP GD SCP GD SCP GD SCP GD SCP GD SCP GD SCP GD SCP eFuse eFuse eFuseeFuse iFuse iFuse iFuse iFuse Fig. 1. Chronological evolution (from left to right) of a switch SCF event on a two-level switching leg with two parallel devices per position. The chronogram starts with S 2a failing in short circuit and the switching-leg output connected to dclink point 1, leading to a short circuit of the dc -link capacitor (short-circuit current path marked in red). After the ini tial state, some of the protective devices are activated (highlighted in blue), leading to the final state where the short - circuit current is interrupted. Three configurations are considered, depending on the device in charge of opening the short -circuit c urrent path: (a) GDSCP. (b) eFuse. (c) iFuse. This article has been accepted for publication in IEEE Journal of Emerging and Selected Topics in Power Electronics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/JESTPE.2022.3183160 © 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. 4 JESTPE-2022-02-0172.R1 In normal operation, SiF is kept permanently ON thanks to voltage Vfuse feeding SiF gate through fuse Flatch (see Fig. 3). During this condition, and since MOSFET SiF acts as a shunt when ON, the FCDC senses the current iS by amplifying the voltage across SiF with the circuit formed by operational amplifier OP and resistors Rf-Rg. The sensed current is then compared through comparator COMP and resistors RIS1-RIS2 to the threshold value IS,th, in order to determine if a positive current is flowing through Sm. This is indicated by Boolean variable IS, such that S S,th S S,th 0 when 1 when . IS i I IS i I = < = ≥ (1) It seems then straightforward that the FDL just needs to look for a concurrent S = 0 and IS = 1 to determine the SCF of Sm. S m iFuse pt1 pt2 (b) (a) iF S st + – Forward- Current Detection Circuit Fault Detection Logic pt1 pt2 iFPS V cc V cc V f us e V cc V f us e Del ay S S m S dly st S GDPS V cc V dig V dig V cc V dig iFuse OiF i S Driving, Latching, and Status Reporting V cc S iF Sm Isolated Gate Driver IS IS Isolated Digital- Signal Drivers GND 0 GND 2 V dd V dd GND 0 GND 2 GND 0 GND 1 GND 2 GND 1 Fig. 2. Diagram of the compound device constituted by switch Sm and the proposed iFuse; i.e. the switching cell. (a) Compact representation of the compound device, showing the iFuse symbol. (b) Expanded view of the iFuse device, showing its internal functional blocks. Relevant digital signals appear in red. Fig. 3. Schematic of the fault detection logic, the driving, latching, and status-reporting circuit, and the forwardcurrent detection circuit . Relevant digital signals appear in red. All ground symbols are connected to GND2. Forward-Current Detection Circuit pt1 S iF R Z2 + – R g V cc IS V cc CLK D CLR Q Q V cc SS dly IS V fuse F latch R off-fa st R off-slow Z 1 S off R pd1 st V cc V cc OiF Fault Detection Logic Driving, Latching, and Status-Reporting Circuit R dly C dly R rst C rst Z 2 R pd2 R f R IS2 OP S st U 2 U 3 U 4 G S D + – V cc COMP V cc R IS1 SFD V cc R pu1 GND 2 pt2 Sm Z3 Vfuse Vcc IN OUT GND RZ3 QPS D1 D2Rlim Cf us e Ccc2 iFPS Ccc1 U5 SiF pt1 GND 2 Fig. 4. Schematic of the iFPS circuit. This article has been accepted for publication in IEEE Journal of Emerging and Selected Topics in Power Electronics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/JESTPE.2022.3183160 © 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. 5 JESTPE-2022-02-0172.R1 However, it must be taken into account that the described conditions can also be met during the Sm turn-off transient in normal operation. Therefore, to avoid a false Sm-failure detection, the fault detection must be disabled during this time interval. To do so, a disable signal dly D SS= ⋅ (2) is defined, where Sdly is a replica of S delayed Tdis seconds and generated with Rdly and Cdly RC network. Tdis should be selected to be larger by some margin than the maximum turn-off transient time of Sm. Finally, the switch fault detection signal IS S SIS S DSFD ⋅⋅ =⋅ ⋅= dly (3) is generated, where SFD = 1 indicates the detection of Sm SCF. When signal SFD transitions from 0 to 1, it latches signal 𝑂𝑂𝑂𝑂𝑂𝑂 � � � � � to zero with the D bistable U3. Therefore, when a fault is detected 𝑂𝑂𝑂𝑂𝑂𝑂 � � � � � = 0 permanently, causing MOSFET Soff to turn on, which performs two actions: turning SiF off by discharging its gate and fusing Flatch. Moreover, pull-up resistance Rpu1 ensures that, in case of failure of the FDL block, the iFuse is engaged, turning SiF off. The D bistable is reset to 𝑂𝑂𝑂𝑂𝑂𝑂 � � � � � = 1 during the iFuse device power up with Rrst and Crst RC network. Sm SCF may result in a short-circuit current flowing through the failed switch as well as other switches. Such event will trigger the gate-driver overcurrent protection of the healthy switches in the short-circuit current path. The FDC must be fast enough to assert Sm SCF before the triggering of the healthy switches overcurrent protection. Otherwise, once the overcurrent protection is engaged, current would be mitigated and the FDC would be unable to detect any fault. Moreover, the short-circuit current scenario also imposes that SiF turn off must be performed taking into account two considerations. First, SiF turn off must be quick enough to avoid damaging SiF and other healthy switches located in the shortcircuit current path. The maximum energy absorption capability of MOSFET and IGBT chips is around 4 to 5 J per cm2 of die surface, resulting in a maximum permissible shortcircuit event duration around 10 µs [8], [22]. However, on a second consideration, SiF turn off must be slow enough to avoid high diS/dt values that could cause voltage spikes in the parasitic inductances present in the short-circuit current path, damaging SiF and other healthy devices due to overvoltage. For this reason, the turn off of SiF is performed in two stages. In the first stage, SiF gate is discharged until its gate-to-source voltage vGS,SiF reaches the threshold value VGS,th. In this interval, SiF remains ON since vGS,SiF > VGS,th and SiF gate discharge is performed quickly to account for the first consideration. In the second stage, vGS,SiF is discharged from VGS,th to zero volts. This is the interval where the true turn off takes place. To account for the second consideration, the gate discharge is performed slower than in the first stage. The abovementioned discharge process is accomplished through the network composed of Roffslow, Roff-fast, and zener diode Z1, with Roff-slow >> Roff-fast and zener voltage VZ ≈ VGS,th. This way, SiF gate is initially discharged fast thanks to the low-impedance path offered by the series connection of Roff-fast and Z1 until vGS,SiF ≈ VZ, when Z1 turns off. Afterwards, SiF gate is discharged slowly through Roff-slow, to ensure a low-di/dt turn-off transition. The purpose of Flatch is to serve as a one-time latch. When Soff is turned on, Vfuse voltage supply is short-circuited through Soff and Flatch, effectively fusing Flatch. Once Flatch is fused, SiF is guaranteed to remain OFF through pull-down resistor Rpd1, thus permanently blocking any forward current through Sm, regardless of any possible malfunction in the circuit due to the failure event. It is therefore only used to prevent a subsequent undesired turn-on of SiF due to the loss of power or damage in the SiF control circuitry. Flatch current rating can be quite small since the fuse does not have a current limiting function, which allows a low capacitance value for Cfuse in Fig. 4. The steady-state drain-to-source voltage of Soff (VDS,Soff) reflects the state of Flatch and hence, the health status of Sm. For convenience, the output health-status reporting binary variable st is defined from this voltage. The value of this variable is st = 1 when VDS,Soff = Vfuse (Flatch is unfused and Sm is in healthy condition) and it is st = 0 when VDS,Soff = 0 V (Flatch is fused and Sm has failed). Variable st can be fed back to the power converter control such that the switching strategy and/or converter structure can be reconfigured after the failure, if necessary. The advantage of the iFuse local control is that it is faster than a centralized control, as the iFuse does not need to establish a communication with such centralized control, and it enables a quick reaction to clear the short-circuit currents that S = S 1 S dly D S 2 i S IS SFD OiF v GS,Si F v DS,Si F I S,th V GS,th di S /dt T dis T det T act t t t t t t t t t t t st Fig. 5. T ypical evolution of the main analog and digital signals from the iFuse circuitry during a shootthrough event due to a SCF of the switch associated to the iFuse, as in the circuit shown in Fig. 11(a). The event is > Is,th does not need to take place before any predefined time such as Tdis. This article has been accepted for publication in IEEE Journal of Emerging and Selected Topics in Power Electronics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/JESTPE.2022.3183160 © 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. 6 JESTPE-2022-02-0172.R1 may occur after the short-circuit failure of the main switch. Still, a centralized control of the iFuse tripping is also possible, for redundancy or for other purposes, though the inclusion of an input signal to the iFuse circuitry to be able to externally command the tripping of the iFuse. Referring to Fig. 5, the detection time Tdet is the time the automatic-diagnosis circuit takes to identify Sm SCF, and the actuation time Tact is the time it takes for the driving circuit to turn off SiF. SiF CBVU switch is not a standard switch, as it is not required to switch frequently. Its main requirements are: • ON-state voltage drop should be as small as possible in order to minimize the increment of converter conduction losses incurred when adding the iFuse. • It should be able to withstand short-circuit currents for a few µs. • Drain-to-source breakdown voltage should match the associated switch Sm breakdown voltage. A low conduction voltage drop generally implies high switching losses. However, SiF switching losses can be neglected, since it will only turn on at zero current during the converter power up and it will turn off only once, when the fault of its associated switch is detected. Moreover, low-conduction- loss devices are also more robust under short-circuit currents since they feature a higher current rating than low-switching- loss devices for the same voltage rating and semiconductor technology. III. APPLICATIONS The proposed iFuse device is meant to be employed in power converters where the forward current path of the short-circuit- failed switches must be cleared to prevent the short circuit of any voltage source involved in the converter operation. When these converters feature some sort of redundancy, such action allows continuing the operation. In the following, some cases of interest are discussed. A. Power Converters Employing Parallel Switches As explained in Section I, power converters employing parallel switches allow easily demonstrating the impairment caused by a switch SCF on the converter inherent faulttolerance capabilities. Fig. 6(a) presents the same leg topology and switch SCF scenario shown in Fig. 1(c) but also depicting the two leg switching states with their corresponding current paths after the switch S2a SCF and the engagement of switch S2a iFuse. Compared to the case employing eFuses (Fig. 1(b)), employing iFuses allows selectively isolating the switch failed in short circuit. Moreover, when the leg output terminal is connected to dc-link node 2 and io < 0, current will partially flow through the S2a iFuse free-wheeling diode, allowing similar conduction-loss values to the pre-fault case. B. ANPC Topologies As explained in Section I, these topologies are more vulnerable to switch SCF than to switch OCF. As an example, Fig. 6(b)-(c) shows a three-level ANPC converter leg [10] where two switches have failed in short circuit: Sp12 and Sn22. The same switching states employed in [10] to connect to the three dc-link points are assumed. In Fig. 6(b), without iFuses, a short circuit of a dc-link capacitor occurs when the leg is connected to dc-link nodes 1 and 3. Therefore, the leg is inoperative since only the connection to one of the dc-link nodes remains. In Fig. 6(c), with iFuses, the short circuit of a dc-link capacitor is avoided, and the connection of the output terminal to the three dc-link points is preserved, without the need to modify the switching states. This is a general interesting advantage of the introduction of the iFuse. Failures Connection to node 1 (a) (b) (c) S2a S2b S1a S1b iFuse iFuse iFuse 2 1 Connection to node 2 S2a S2b S1a S1b iFuse iFuse iFuse iFuse 2 1 Connection to node 1 ioio iFuse Sp21 Sp11 Sn22 Sp12 Sn11 Sn21 1 2 3 io Sp21 Sp11 Sn22 Sp12 Sn11 Sn21 1 2 3 io Sp21 Sp11 Sn22 Sp12 Sn11 Sn21 1 2 3 io Sp21 Sp11 Sn22 Sp12 Sn11 Sn21 1 2 3 io iFuse iFuse iFuse iFuse iFuse iFuse iFuse iFuse Sp21 Sp11 Sn22 Sp12 Sn11 Sn21 io iFuse iFuse iFuse iFuse 1 2 3 Sp21 Sp11 Sn22 Sp12 Sn11 Sn21 io iFuse iFuse iFuse iFuse iFuse 1 2 3 iFuse Connection to node 2Connection to node 3 Fig. 6. Ex amples of converter legs where the iFuse device can be employed to take advantage of switch-level redundancy . Switches failed in short circuit and the short -circuit current paths are marked in red. The iFuses that have been engaged ( OFF state) are marked i n blue. Current paths for any polarity of i o are marked in green solid lines. Current paths for only io < 0 or only io > 0 are marked in green dashed lines. (a) Twolevel leg with two parallel switches per position. (b) Three - level ANPC leg without iFuses. (c) Three-level A NPC leg with iFuses. This article has been accepted for publication in IEEE Journal of Emerging and Selected Topics in Power Electronics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/JESTPE.2022.3183160 © 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. 7 JESTPE-2022-02-0172.R1 under the iFuse protection do not need a change of the converter switching states. The converter can continue operating with the same switching states used before the failure. It is worth noting that connection to dc-link-point 2 is preserved thanks to the iFuse reverse-conduction feature. C. Multiphase Dc-Ac Converters Featuring Leg Redundancy [2], [3], [7], [11]–[13] This case is illustrated in Fig. 7. As explained in Section I, conventional solutions employ different strategies involving additional hardware (fast fuses, thyristors, capacitors, redundant series switches) and a centralized control to isolate the faulty leg. The proposed iFuse can replace these conventional solutions, allowing for a simpler implementation thanks to its standalone operation, and substantially improving the performance of the fault-tolerance mechanism, especially when substituting fault-isolation mechanisms employing fast fuses. D. Interleaved Dc-Dc Converters This last case corresponds to interleaved dc-dc converters, as for example two-level multiple-phase boost converters [3], [23], illustrated in Fig. 8. In such converters, a SCF of an active switch leads to the saturation of the inductor and eventually the short circuit of the input power supply. Employing an iFuse in series with each switch avoids this situation and allows reporting the failure to the converter closed-loop control, through signal st, such that proper action can be taken to continue the operation with the remaining phases. E. Converters featuring 4Q switches Combining two SCs (main switch + iFuse) in anti-series results in a 4Q SC with switch SCF protection; i.e., in case one of the two main switches in the 4Q SC fails in short circuit, its associated iFuse will open. Thus, after a switch SCF the 4Q SC will still maintain the bidirectional voltage-blocking capability, while thanks to the reverse current conduction path offered by the iFuse, the SC will allow current flow in one of the two directions. The proposed SC anti-series association would be useful in power converters employing 4Q switches, such as matrix converters and converters featuring t-type and π-type ANPC switching legs, among others. IV. RELIABILITY IMPROVEMENT A two-level converter leg with two switches in parallel per position (Fig. 6(a)) serves as a good and simple example to study and quantify the reliability improvement offered by the iFuse. First, let us consider the converter leg in Fig. 6(a) but without iFuses. In this case, when any switch SCF occurs, the converter must be shut down. Instead, if a switch OCF occurs, the converter can still operate as long as there remains at least one switch per position. Moreover, it will be assumed that whenever the first OCF occurs, the leg output current is halved. This way, the failure rate of the switch in parallel with the failed switch does not increase above its nominal value. Next, let us consider the converter leg shown in Fig. 6(a) with the iFuses. Thanks to these iFuses, the converter can continue in operation regardless of the type of failure as long as there remains at least one operating switch per position. As in the previous case, it will be assumed that whenever the first switch failure occurs, the leg output current is halved. The reliability of both cases can be easily evaluated deriving their Markov chain model and then computing the system mean-time to failure (MTTF), as presented in [24]. Fig. 9 shows the Markov chain model for both cases, where the states are defined in Table I. The transition rate between states is defined by the addition of the relevant main switch failure rates. λO is the switch OCF rate and λS is the switch SCF rate, both at the nominal switch current, with the total failure rate being λ = λO + λS. λOh and λSh are the corresponding failure rates at half the nominal switch current, with λh = λOh + λSh. For the sake of simplicity, it will be set that λh = λ /2. Let us also define α = λO / λ = λOh / λh as the probability of OCF occurrence, while 1 − α represents the probability of SCF occurrence. Note that the Markov chain model of Fig. 9(b) assumes that the iFuse failure rate is much smaller than λ and λh, since the iFuse is permanently in the ON state with only conduction loss, zero switching loss, and no switching stress, as opposed to the main switch, where much more conduction loss, substantial switching loss, and substantial switching stress takes place. In addition, a robust design of the iFuse auxiliary circuitry is also iFuse iFuse + - V dc iFuse Fig. 8. Interleaved multiphase boost dc-dc converter. iFuse iFuse iFuse iFuse iFuse iFuse Multi-phase ac load + - Vdc Fig. 7. Multiphase dcac converter that can continue operating after the failure of one or more legs, feeding, for instance, a multiphase motor with five or more phases. This article has been accepted for publication in IEEE Journal of Emerging and Selected Topics in Power Electronics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/JESTPE.2022.3183160 © 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. 8 JESTPE-2022-02-0172.R1 assumed. Thus, under these assumptions, the iFuse failure rate can be neglected. The resulting MTTF in both cases (without and with iFuses, respectively) is 2 niF iF 1 21 4 1. MTTF MTTF α + α+ = ⋅ λ =λ (4) The ratio between both is plotted in Fig. 10 as a function of α. As expected, when all failures are OCF (α = 1), then both MTTF are equal. However, when the probability of SCF increases (α decreases), MTTFniF decreases. With an equal probability of switch OCF and SCF (α = 0.5), the MTTF of the converter leg employing iFuses is 1.7 greater than the leg not employing iFuses. When all failures are SCF (α = 0), the MTTF of the leg employing iFuses is 4 times greater. V. EXPERIMENTAL RESULTS Experimental tests have been carried out to demonstrate the feasibility and effectiveness of the proposed solution. In the first test, a SCF is forced in the bottom switch S1 of the twolevel converter leg shown in Fig. 11(a). A shoot-through event will subsequently occur when the leg output transitions from the connection to the negative dc-link rail to the connection to the positive dc-link rail; i.e., when S1 transitions from high to low and then S2 transitions from low to high. At S2 turn on, the dc-link capacitor will be short circuited and then iFuse iF1 should turn off after a short time interval. This scenario has been reproduced with the simplified circuit configuration of Fig. 11(b). In this circuit, both S1 and iF2 have been replaced by a short, since they behave as a low-ohmic contact. Signal S in iF1 is set low. In the experiment, the dc-link capacitors, formed by a parallel connection of electrolytic and PET film capacitors, are first pre-charged to voltage VS,init. Then, shortly after, S2 is turned on. Resistor Rsense is employed to measure current iS. Switches S2 and SiF are implemented with MOSFETs IRFR4510 and IPT015N10N5, respectively, both rated at 100 TABLE I MARKOV CHAIN DIAGRAM STATES DEFINITION State Fig. 9(a) Fig. 9(b) 1 All switches are healthy. All switches are healthy. 2 One switch OCF has occurred. One switch has failed. 3 Two switch OCFs, one in each leg position, have occurred. Two switches, one from each leg position, have failed. 0 One switch SCF or two switch OCFs from the same leg position have occurred. The leg is shut down. Two switches from the same leg position have failed. The leg is shut down. (a) (b) Fig. 9. Markov chain diagrams of a twolevel converter leg with two switches in parallel per position. (a) Without employing the iFuse. (b) With one iFuse in series with each switch (Fig. 6(a)). 1 2 3 0 4λ 2λ h λ 2λ 1 2 3 0 4λ Ο 2λ Οh λ Ο + λ S + 2λ Sh 2λ O + 2λ S 4λ S Fig. 10. Ratio of the MTTF of the converter leg in Fig. 6 (a) to the MTTF of the same leg without employing iFuses. 0 0.2 0.4 0.6 0.8 1 1 2 3 4 TABLE II EXPERIMENTAL TEST PARAMETER VALUES Parameter Value VC,init 50 V C 440 µF (electrolytic cap.) + 13.2 µF (PET film cap.) R sense 2.5 m Ω ± 1% R off-fast 10 Ω R off-slow 330 Ω V Z1 5.1 V V fuse 15 V IS,th 200 A RDS,on (S 2 ) 11.1 m Ω RDS,on (SiF) 1.3 m Ω (a) (b) Fig. 11. First experimental test schematic. (a) Reproduced scenari o. (b) Simplified circuit configuration used for the experimental test. S1 iFus e iF1 S2 iFus e iF1 S2 0 Rsense S2 S1 S2 S1 CC + – VC iS iFus e iF2 This article has been accepted for publication in IEEE Journal of Emerging and Selected Topics in Power Electronics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/JESTPE.2022.3183160 © 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. 9 JESTPE-2022-02-0172.R1 V. The device selection has been performed to emulate the typical characteristics of both devices: the main switch S2 featuring a good switching performance with moderate conduction performance, while SiF features an optimal conduction performance. Table II shows the main component parameter values of Fig. 11(b). As it can be seen, IPT015N10N5 RDS,on is very low. In fact, it was the commercial 100 V-rated Si MOSFET with the lowest ON-state channel resistance at the time of the experimental tests. With the abovementioned S2 and SiF MOSFET selection, a power converter incorporating an iFuse in series with each switch, would only experience a 12% increase in its conduction losses. Nonetheless, due to the novelty of the concept and the intended switch functionality, it is reasonable to expect some room for optimizing the design of switches to be used in iFuses and further reduce the conduction losses. Fig. 12 shows the results of the described experimental test. As it can be observed, once S2 gate-to-source voltage vGS,S2 begins to rise, shoot-through current iS rises abruptly, reaching a peak value of 1.1 kA. After 1.7 µs, digital signal IS goes high indicating that current iS > IS,th (a certain delay is introduced by the detection circuit), followed by the activation of SFD and OiF signals. Once 𝑂𝑂𝑂𝑂𝑂𝑂 � � � � � = 0, the SiF turn-off procedure begins by discharging its gate in two stages, as can be observed in vGS,SiF and as explained in Section II. SiF true turn off starts when vGS,SiF reaches VGS,th (around 4 V) with its drain-to-source voltage (vDS,SiF) and current (iS) presenting slopes of approximately 30 V/µs and –340 A/µs, respectively. Thanks to the moderate diS/dt value, the peak value of vDS,SiF during the turn off process is limited to 57 V, corresponding to an overshoot of only 14%. The time intervals for Tdet and Tact are 2.4 µs and 3.6 µs, respectively. Therefore, the iFuse is capable of detecting the switch in SCF and blocking the forward current path of its associated switch in 6 µs. Time interval Tdet = 2.4 µs is shorter than the typical response time of the overcurrent protection of the healthy-switches gate driver, which typically is between 8 to 10 µs. Therefore, the iFuse is able to engage successfully without the negative interference of the healthy-switch driver overcurrent protection. During the shoot-through, S2 drain-to-source voltage vDS,S2 reaches an average value of approximately 25 V, indicating that the device is working in the saturation region. During this interval, S2 junction temperature increases rapidly due to the high power loss, which in turn decreases the saturation current. This phenomenon is consistent with the findings in [22] and explains why iS current starts decreasing before SiF starts turning off. The capacitor voltage (VC) decreases 8 V after the shootthrough event, indicating that approximately 15 mJ have been dissipated in Rsense, S2, SiF, and the parasitic elements of the circuit. This energy value is far below the maximum shortcircuit energy that S2 and SiF can withstand, which is around 750 mJ and 2.5 J, respectively, considering a die surface of i S OiF OiF SFD IS D S v GS,S2 v GS,SiF v DS,SiF v DS,S2 T det T act Fig. 12. Experimental results showing digital (top) and analog (channels 1 to 4 and R1) signals. S1a O 1 2 S1b S2a S2b Fig. 13. Prototype of a twolevel leg with two parallel switches per position according to Fig. 6(a). All switches are equipped SiF Sm Saux Saux gate driver Temperature sensors (a) (b) Fig. 14. Detail of the SC implementation. Saux is an auxiliary switch in parallel with S m used to emulate shortcircuit faults of the main switch Sm.(a) Top. (b) Bottom. This article has been accepted for publication in IEEE Journal of Emerging and Selected Topics in Power Electronics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/JESTPE.2022.3183160 © 2022 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.