Fault detection algorithm for wind turbines’ pitch actuator systems

Pujol Vázquez, Gisela,Acho Zuppa, Leonardo,Gibergans Bàguena, José

Abstract

A fault detection innovation to wind turbines’ pitch actuators is an important subject to guarantee the efficiency wind energy conversion and long lifetime operation of these rotatory machines. Therefore, a recent and effective fault detection algorithm is conceived to detect faults on wind turbine pitch actuators. This approach is based on the interval observer framework theory that has proved to be an efficient tool to measure dynamic uncertainties in dynamical systems. It is evident that almost any fault in any actuator may affect its historical-time behavior. Hence, and properly conceptualized, a fault detection system can be successfully designed based on interval observer dynamics. This is precisely our main contribution. Additionally, we realize a numerical analysis to evaluate the performance of our approach by using a dynamic model of a pitch actuator device with faults. The numerical experiments support our main contribution.

Full text

energies Article Fault Detection Algorithm for Wind Turbines’ Pitch Actuator Systems Gisela Pujol-Vazquez *,† , Leonardo Acho †and José Gibergans-Báguena † Department of Mathematics, Universitat Politècnica de Catalunya (UPC), 08222 Terrassa, Spain; [email protected] (L.A.); jose.giber[email protected] (J.G.-B.) *Correspondence: [email protected] † These authors contributed equally to this work. Received: 19 April 2020; Accepted: 29 May 2020; Published: 4 June 2020   Abstract: A fault detection innovation to wind turbines’ pitch actuators is an important subject to guarantee the efficiency wind energy conversion and long lifetime operation of these rotatory machines. Therefore, a recent and effective fault detection algorithm is conceived to detect faults on wind turbine pitch actuators. This approach is based on the interval observer framework theory that has proved to be an efficient tool to measure dynamic uncertainties in dynamical systems. It is evident that almost any fault in any actuator may affect its historical-time behavior. Hence, and properly conceptualized, a fault detection system can be successfully designed based on interval observer dynamics. This is precisely our main contribution. Additionally, we realize a numerical analysis to evaluate the performance of our approach by using a dynamic model of a pitch actuator device with faults. The numerical experiments support our main contribution. Keywords: fault detection; interval observer; pitch actuator; wind turbines 1. Introduction Nowadays, wind turbines are essential machines to produce green energy from the natural air current. One way to increase this green energy is by increasing the wind-turbine blade dimensions. Hence, its price is increased too. Therefore, to ensure a good feasibility and long lifetime operation of the wind turbines blade-dynamics to effectively capture the wind, a fault detection system design for the pitch actuator systems of a wind turbine results in being virtually mandatory [1–4]. Recently, the benefit impact of wind turbines on earth and, in a near future, on Mars too is well accepted [ 5 , 6 ]. In wind turbine literature, an important topic is to improve its performance. In [ 7 ], a study on misalignment of the wind turbine nacelle with respect to the wind direction is presented, and a study [ 8 ] on the major driven force on the mooring line tension of offshore wind turbines. In [ 9 ], the effect of age in the performance of wind turbine is investigated. The damage effects caused by the fatigue of the wind turbine components is an important issue to perform the behavior of wind turbines [ 10 ]. In addition, improving the design can be an effective way to ameliorate the performance of the whole system [ 11 ]. For example, the blade aerodynamic design of the wind turbine is studied in [ 12 ]. Moreover, vibration control and fatigue reduction are studied to develop new strategies with the objective of increasing the performance and decreasing pitch actuator usage [ 13 , 14 ]. To fulfill this objective, stochastics models can be built to study fatigue loads [ 15 ], or to predict drive-train vibrations [ 16 ]. Furthermore, it is crucial to prevent system failures in order to ensure the performance. Innovative fault detection and diagnosis are essential to realize the required levels of reliability in recent wind turbines [ 17 – 19 ]. To assure efficient operation on energy conversion of these wind systems, an efficient pitch actuator fault detection methodology is mandatory [ 20 ]. Fault detection techniques can be classified into two major categories: model-based methods and signal processing-based methods. Energies 2020,13, 2861; doi:10.3390/en13112861 www.mdpi.com/journal/energies Energies 2020,13, 2861 2 of 14 For model-based fault detection, the system model could be mathematical [ 21 ]. Faults are detected based on the residual generated by state variable or model parameter estimation (see [ 22 ] and a reference on it). For signal processing-based fault detection, mathematical or statistical operations are performed on the measurements (see, for example, [23]). Hence, the main objective of this paper is to present a recent algorithm to detect a fault in pitch actuators of wind rotary mechanisms. In the presence of pitch actuator faults, pitch systems may present changes on its behavior, affecting the pitching performance with the possibility of oscillation on the generator speed and making the turbine system unstable and unsafe [ 24 ]. A fault on pitch actuator induces changes on dynamics, as high air content in oil, pump wear, or hydraulic leakage [ 22 ]. In literature, there are many contributions on it. Some are based on data analysis [ 25 ], others are based on the frequency response of the system actuator to a given input signal [ 26 ], and so on [ 27 ]. On the other hand, the use of interval observers has proved to be an excellent tool to measure uncertainties in dynamical systems [ 28 – 31 ]. Taking advantage of this, we use the main interval observer statement to postulate our fault detection method. Then, and by using a given training input signal, the performance of our approach is numerically validated. According to these numerical experiments, a pitch actuator fault is highlighted. The rest of this paper is structured as follows. Section 2shows the theoretical frame on interval observers design and our general fault detection algorithm for any linear dynamic system. Then, in Section 3, the application to wind turbine system is presented, along with the novel fault detection and fault classification algorithms. A set of numerical experiments support the main contribution of this paper. We use a wind turbine pitch actuator under three common faults. According to these numerical experiments, our approach is able to to discern the faulty stages from the healthy one. Finally, a brief conclusion and future work are discussed in Section 4. Notation 1. For a real matrix M or a vector, M> 0means that its components are positive, and M≥ 0 means that its components are non-negative. Additionally, Rn×m + denotes that the set of real n×m matrices have non-negative entries [ 28 ]. In consequence, Rn×m − denotes the set of real n×m matrices having non-positive entries. 2. Fault Detection Algorithm: Interval Observer Approach This section presents the first approach to our main objective: to design a rule for a fault detection on a pitch actuator of a wind turbine system by using the residual signals of interval observers. To achieve this objective, we consider a linear dynamic system and we design a general fault detection algorithm. To succeed, first some definitions and results on interval observer theory are presented. Then, our general result is stated. 2.1. Interval Observers Design First of all, we present some definitions [32]: (i) The relation M1≤M2must be understood at the element-wise. (ii) A matrix Mis a Metzler matrix if its off-diagonal elements are non-negative ones. (iii) A matrix Mis Hurwitz (or stable) if every eigenvalue of Mhas strictly negative real part. We also need the next theorem, where the non-negative solutions to a linear dynamic system is characterized. Theorem 1 ( [28] ) . Given a Metzler matrix M , the system ˙ z=Mz +r(t) , z∈Rn , r(t)≥ 0, is called cooperative or non-negative system if due to z(0)≥0, then z(t)≥0,∀t≥0. On the other hand, it is well-known that any system may present uncertainties, due to model parameters variation or unknown input disturbances. An option to estimate an uncertainty in a Energies 2020,13, 2861 3 of 14 linear dynamic system is by invoking the classical approach on constructing a Luenberger observer. For example, consider the system ˙ x(t) = Ax(t) + Bu(t),x(0) = 0∈Rn, (1) where x∈Rn is the state, A∈Rn×n is a constant matrix, B> 0 ∈Rn is a vector, and u(t)∈R is the input excitation signal and assumed bounded. To detect or observe the state variable x(t) , with input u(t), a Luenberger observer can be constructed (see [33] for an introduction to observers): ˙ z(t) = Az(t) + Bu(t) + L(x(t)−z(t)). (2) Variable z(t) observes x(t) , in the sense that the state error dynamic z(t)−x(t) is stable. Then, if the matrices A and B in Equation (1) present uncertainties, a natural question is how to modify the observer structure to overcome these uncertainties. Broadly speaking, it can be inferred that there are two main approaches: (1) by employing adaptive laws for an estimation on the system parameters variation [ 34 ], and (2) by designing interval observers [ 35 , 36 ]. The main advantage of using interval observers is its dynamic response to give a finite range of possible values for the state variable [29]. For a basic reference, next we introduce the general definition of interval observer for linear systems. Definition 1 ([35]).For system (1), the dynamical system    ˙ z(t) = a(z,u) hx(t)T¯ x(t)TiT=b(z,u)(3) is an interval observer for (1), if x(0)≤x(0)≤¯ x(0), then ∞<x(t)≤x(t)≤¯ x(t)<∞for all t ≥0. The functions a(· , ·) and b(· , ·) in (3) are carefully designed to capture the state dynamics of the given system with a required performance. Usually, they are defined based on Luenberger observer structure (2). Therefore, a Luenberger matrix Lmust be constructed. Additionally, the stability of the interval observer dynamic z(t)in (3) must be ensured too. By accurately defining the functions a(·,·) and b(· , ·) , this stability issue can be accomplished. In a general approach, the residual errors e(t) = x(t)−x(t) and ¯ e(t) = ¯ x(t)−x(t) are usually studied to evaluate the observer design performance. Hence, if these dynamics are stable, then the inclusion condition x(t)≤x(t)≤¯ x(t)is ensured. Now, suppose that system matrices A and B in Equation (1) are faulty but bounded by known matrices ALand AU, and BLand BU, respectively: AL≤A≤AU, BL≤B≤BU.(4) An approach to determine an interval for the system state variable x(t) is by using the inequalities sated in (4), allowing for structuring an interval observer. That is, the functions a(· , ·) and b(· , ·) (in Equation (3)) will depend not only on AL , AU , BL and BU , but also on the Luenberger observer matrix L. 2.2. General Fault Detection Algorithm In this section, a new faulty algorithm based on interval observers is presented. It is based on the fact that interval observers allow for detecting if the observed variable overcomes a prefixed healthy value. To do that, we introduce a slight modification on the classical Luenberger observer stated in Equation (2). The main idea is to monitor interval (4) as a possible faulty interval: the nominal value A takes values in [AL , AU] when a fault is present in the system (the same for B ). Moreover, Energies 2020,13, 2861 4 of 14 the observer dynamic depends only on a nominal value of matrices A and B . That is, the interval observer is designed despite inequation (4). If a fault occurs, matrices in system (1) reflect this faulty scenario. However, the observers do not depend on it, as expected due to the faulty scenario being unknown. In fact, we do not need the interval state observer for the detection alert, and we work directly with the observed residual signals e(t)and ¯ e(t)to confirm a fault. This is realized below. We now present a novel interval observer by introducing a design function g(t) , with a design parameter α∈R+into an state-observer Luenberger frame-scheme Equation (2): ˙ w(t) = Aw(t) + Bu(t) + L(x(t)−w(t)) −αBg(t),w(0)∈Rn −, (5) ˙ z(t) = Az(t) + Bu(t) + L(x(t)−z(t)) + αBg(t),z(0)∈Rn +, (6) with w( 0 )≤x( 0 )≤z( 0 ) . The additional term ±αBg(t) is an artificial external perturbation that uses the same canal as u(t) . The term α is introduced to tune the dynamic observer to accurately detect a faulty case on our system. Consider now the residual signals of these observations (also named observed errors), defined as: eL(t) = x(t)−w(t), eU(t) = z(t)−x(t).(7) Hence, the process monitoring is realized by manipulating these residual observed signals (7) in comparison to the nominal (non-faulty) case. Therefore, under a faulty system scenario, the system matrices (1) are affected, but the observer systems (5) and (6) only depend on the non-faulty system data giving its ability to claim a fault on the system if it occurs. To fulfill this objective, we first need to ensure the stability of the proposed method. Proposition 1 ( Lower and Upper bounds ) . Consider the system (1) , with α∈R+ , and a non-negative function g(t). If there exists matrix L such that A −L is Metzler, then w(t)≤x(t)≤z(t),t≥0, (8) w(t) and z(t) being solutions to the systems (5) and (6) . Moreover, if g(t) is bounded and A−L is Hurwitz, the bounded-input bounded-output (BIBO) stability is ensured. Proof. From definition in (7), it suffices to note that the errors eL(t) and eU(t) are non-negative, and then concluding by using Theorem 1. Then, differentiating Equation (7) with respect t, we obtain: ˙ eL(t) = ˙ x(t)−˙ w(t) =Ax(t) + Bu(t)−(Aw(t) + Bu(t) + L(x(t)−w(t)) −αBg(t)) =Ax(t)−Aw(t)−L(x(t)−w(t)) + αBg(t) = (A−L)eL(t) + αBg(t). Taking into account that A−L is Metzler, and αBg(t)≥ 0, by Theorem 1, we have eL(t)≥ 0, and conclude that x(t)≥w(t) . Moreover, if A−L is Hurwitz, ˙ eL(t) is BIBO stable. Consider now the upper error eU(t)defined in Equation (7): ˙ eU(t) = ˙ z(t)−˙ x(t) =Az(t) + Bu(t) + L(x(t)−z(t)) + αBg(t)−(Ax(t) + Bu(t)) =Az(t) + L(x(t)−z(t)) + αBg(t)−Ax(t) = (A−L)eU(t) + αBg(t). Again, from Theorem 1, we conclude that eU(t)≥ 0, so z(t)≥x(t) , and, if the Hurwitz condition is verified, BIBO stability is ensured. Energies 2020,13, 2861 5 of 14 Note that, in order to design the interval observers (5) and (6), it is necessary to know the nominal value of system matrices Aand Bin Equation (1). This is the case for the wind turbine [37,38]. The interval observer (8) in Proposition 1 may not be the best interval observer. This is not the purpose of this work: we only ensure that the error is BIBO to construct an algorithm for fault detection. That is, no optimization process is involved. Our aim is to detect a fault on the system, and not really to determine an interval to the system state vector. Algorithm 1summarizes the fault detection algorithm. Thus, we only require using the residual errors (7) of upper and lower bounds of interval observer (8). Hence, in the healthy scenario, we determine its maximum value and then take it as a threshold for comparison. Thus, if this threshold is violated, then a fault is presented.Moreover, we may also be able to classify the kind of fault, an important issue in wind-turbines. We summarize this in a general fault detection algorithm based on the interval observers (5) and (6). Its stability is ensured by Proposition 1. Algorithm 1: General fault detection algorithm. Step 1: Define L,g(t)and αsuch Proposition 1 holds. Step 2: Healthy case: Find a threshold Thfor residual errors (7). Step 3: General scenario: evaluate residual errors (7) and compare with Th. 3. Interval Observer Statement Applied to Fault Detection in a Pitch-Actuator of a Wind-Turbine We now present a fault detection algorithm applied to a wind turbine. To succeed, we first need to present the wind turbine mathematical model, and then adapt the general fault detection algorithm presented in Section 2, in order to obtain a rule allowing for discerning if a fault on pitch actuator appears or not. The pitch-actuator dynamic behavior, see Figure 1, of a wind-turbine can be captured by using the next representation [20,37,38]: β(s) u(s)=w2 n s2+2ζwns+w2 n , (9) where β(t) is the pitch angle related to its actuator, u(t) is the reference command signal supplied by the control power management system, and s represents the Laplace variable of a related signal in time-domain, t . Additionally, wn and ζ represent the natural frequency and the damping ration of the pitch actuator, respectively. On the other hand, in hydraulic pitch actuators, its degradation performance comes from different faulty operation cases, such as pump wear, hydraulic leakage, and high air oil content [ 20 , 37 ]. For a general report on fault detection in wind turbine, see [ 1 , 2 ], and Ref. [ 3 ] presents a faulty scenario classification. In the present paper, we only consider the pitch actuator faults. Access to real wind turbine data sets is usually proprietary, and therefore they may not be openly accessible. To overcome this difficulty, in this work, numerical data were obtained from existing literature, presented in Table 1[ 37 , 38 ], where the nominal (H) and faulty ( F1 , F2 and F3 ) scenarios’ values of wnand ζin Equation (9) under study in this work are defined. Table 1. System parameters for a hydraulic pitch actuator under common faulty scenarios [37,38]. Scenario wn(rad/s) ζ No fault (H) 11.11 0.6 High air oil content (F1) 5.73 0.45 Hydraulic leakage (F2) 3.42 0.9 Pump wear (F3) 7.27 0.75 Energies 2020,13, 2861 6 of 14 Figure 1. A schematic representation of the pitch actuator location in a wind-turbine. System (9) can be transformed into the state-space scheme as: ˙ x(t) = Ax(t) + Bu(t)(10) with A= 0 1 −w2 n−2ζwn!,B= 0 w2 n!. Here, x1(t) = β(t) , and x2(t) = ˙ β(t) such as xT(t)=[x1(t)x2(t)] . To apply Proposition 1, and ensure stability, we need to define L , α , and g(t) for wind turbine system (10). The next lemma collects it. Lemma 1. The system (5)and (6), with L= 1 1 −w2 n1−2ζwn!, (11) define an interval observer (8)for the pitch actuator system (10)with g(t) = |u(t)|and α=0.01. The value of α is tuned to discriminate the pitch dynamic if a fault occurs (see Table 1). Function g(t) is designed to fulfill the hypothesis of Proposition 1, ensuring BIBO stability. Note that, if we define g(t) = 0 in Equations (5) and (6), the residual signals (13) vanish because both systems (1), (5), and (6) consider the same matrices Aand B, obtaining Luenberger observers. Observe that the dynamic of the interval observer (5) and (6) is defined under the non-faulty scenario (H in Table 1). Hence, the system matrices A and B in system (10), and L in Equation (11), take values given by wn=wH=11.11 and ζ=ζH=0.6; and then labeled as AH,BHand LH, as follows: AH= 0 1 −w2 H−2ζHwH!,BH= 0 w2 H!,L= 1 1 −w2 H1−2ζwH!. (12) Therefore, to detect a fault, we can go on analyzing the related residual signals: eL2(t) = x2(t)−w2(t), eU2(t) = z2(t)−x2(t),(13) where the variable x2(t) is selected because, besides representing the pitch system, ˙ β(t) is the dynamical variable most sensitive to faults. We can now present an algorithm to design the fault detection system. Next, we present some simulations to test our proposal fault detection method. First, the total time of simulation is set to 250 s, sufficiently enough to evaluate our fault detection design. Then, we program the system observers (5) and (6) and applied to the pitch actuator process (9). This observer just uses the healthy parameters of the pitch actuator prototype. In our testing numerical experiments, Energies 2020,13, 2861 7 of 14 we program the input prove signal as shown in Figure 2; jointly, we have the response of the state variables for the healthy actuator. Here, we set x1( 0 ) = 0, x2( 0 ) = 0, w1( 0 ) = − 1, w2( 0 ) = − 1, z1(0) = 1, and z2(0) = 1 for each test and then hereafter. Figure 2. Test input signal and state variables x1(t) and x2(t) for the healthy actuator response (with x1(0) = 0 and x2(0) = 0). By following the FD-Algorithm stated in Algorithm 2, we need to define Th from the nominal case H, as stated in Table 1. We obtain Figure 3, where both errors (13) for this case are displayed. Then, we can define a threshold (third step of FD-Algorithm): Th = 2.5 (this value can be obtained from Figure 3or evaluating a bound for supt{eL2(t) , eU2(t)} ). Finally, we can use it to obtain a fault detection system (step 4 in Algorithm 2): faulty system (10) is considered and residual signals eL2(t)and eU2(t) are evaluated. The obtained simulation results for each faulty scenario are shown in Figures 4–6. By using the stated excitation signal (or input signal), the occurrence of a fault is simple to realize: if sup0≤t≤250 eL2(t)≥Th , then a fault has occurred. Figures 4–6picture both errors (13), proving that it is necessary to consider eL2(t) and eU2(t) in Equation (13) to detect a fault because they do not detect a system fault at the same time. Thus, the designer has to evaluate (13) and the first to overcome Th detects a system fault. Algorithm 2: Wind turbine fault detection algorithm (FD-Algorithm) Step 1 Consider the healthy parameters shown in Algorithm 1, and then define matrix L(11). Step 2 Define a non-constant excitation signal u(t). Step 3 From the nominal plant (H), define a threshold Th as a bound to the system dynamic (13): 3.1 Solve (10) for AH,BHand LH(12), along with (5) and (6). 3.2 Define a threshold Thto the dynamic in (13). Step 4 Decision rule. 4.1 Solve (10) for faulty Aand B. 4.2 Solve (5) and (6), with AH,BHand LH(12). 4.3 If residual signals (13) are greater than the set threshold Th, then a fault is detected. Figure 3. Observed errors or residual signals eU2(t) and eL2(t) for the nominal case H (see Algorithm 1). We can state Th= 2.5 as a bound for the residual signals (dashed). Note that both errors are identical because no fault is present. Energies 2020,13, 2861 8 of 14 In Figure 3, the positiveness of the residual signal can be shown. When the faulty system is considered, the Metzler condition can be lost, so the non-negativeness of eU(t)(t) and eL(t)(t) in Equation (7) is not ensured. For instance, this can be noted in Figure 4, where both errors take negative values. Figure 4. Fault F1 scenario. Residual signals eU2(t) and eL2(t) . Once one of the two errors overcomes the dashed line, a fault is detected. Figure 5. Fault F2 scenario. The first fault detection for both residual signals or observed error is in red. Figure 6. Fault F3 scenario. In this case, the residual signal eU2allows for detecting a fault faster than eL2. Energies 2020,13, 2861 9 of 14 On the other hand, an important experimental issue is to evaluate how fast our detection system responds. Table 2presents when the first fault is detected, for each case, and for both residual signals eL2(t)and eU2(t): tL=min 0≤t≤tf {eL2(tL)>Th}, tU=min 0≤t≤tf {eU2(tU)>Th},(14) where tfis the total time of simulations. Table 2. Time estimation of the first detection by using the residual signals (13). Scenario tU(seconds) tL(seconds) High air oil content (F1) 79.9382 58.0804 Hydraulic leakage (F2) 31.3493 13.1228 Pump wear (F3) 42.3287 55.9148 Note that it takes less than a minute to detect a fault. In comparison to the technique stated, for instance in [ 20 ], our approach may be considered as a fast response method for detecting a fault. Moreover, from Figures 4and 5and Table 2, a classification of a system fault can be stated, once the threshold value Th is defined. In a general scenario, once eL2(t) or eU2(t) are greater than the stated value Th , a fault is detected. However, how may we classify it as F1 , F2 or F3 ? From Table 2, a response to this question can be inferred using (14). A classification algorithm is stated in Algorithm 3. Algorithm 3: Fault classification algorithm (FC-Algorithm) Step 1 Nominal plant: determine Th. Step 2 General plant: Evaluate the first value of t(14) such that eL2(t)or eU2(t)(13) verify: 2.1 If eL2(t)>Thfor t≤15: then F2 2.2 If eU2(t)>Thfor 15 <t≤55: then F3 2.3 If eL2(t)>Thfor 58 ≤t: then F1. Finally, in real applications, even when we are actuating by using a known control signal to the pitch-actuator system of the wind turbine, there may exist a wind on the blades and then inducing of random dynamics on our structure. Hence, we repeat the previous simulations by adding a random signal to our control action as shown in Figure 7. The obtained results are shown in Figures 8–11. From these figures, we see that the same fault detection algorithm is still possible. Figure 7. Top: Input signal with random noise; Down: variables of wind turbine system (10).