RESEARCH ARTICLE Impact of solar reflectivity and infrared emissivity on the thermal performance of metal and concrete roofs in cloudy warmhumid climate Jefferson Torres-Quezada a,* , Antonio Isalgue ´ b , Helena Coch b a CONSISO Lab, Universidad Cato ´lica de Cuenca, Cuenca 010102, Ecuador b Architecture, Energy and Environment, Polytechnic University of Catalonia, Barcelona 08028, Spain Received 17 January 2024; received in revised form 29 February 2024; accepted 13 March 2024 KEYWORDS Concrete roof; Metal roof; Radiative properties; Simulations; Measurements Abstract Regions near latitude 0are characterized by warm-humid climate and also by high cloudiness. In these regions, metal roofs has been the most widely used typology. However, in the last decades, the use of heavy concrete roofs has increased significantly. Given its material characteristics, this roof typology offers a higher thermal resistance and thermal mass than a metal roof. Most strategies focus on the use of these characteristics, as well as the use of high reflectivity and emissivity. However, the impact of cloudiness on the effectiveness of these strategies has been little addressed. This research focuses on the impact of reflectivity and emissivity change on the thermal performance of these two roofs in a cloudy warm-humid climate. To achieve this objective, simulations validated with measurements were used. The results show that the efficiency of reflectivity and emissivity is lower in this region compared to other regions. The impact of these properties is further reduced with increasing thermal mass or decreasing thermal transmittance, so the effectiveness of reflectivity and emissivity is minimal on the concrete roof. Finally, this study supports that a metal roof with a reflectivity and emissivity above 0.70 can offer lower daily average temperatures than a concrete roof. ª2024 The Author(s). Publishing services by Elsevier B.V. on behalf of KeAi Communications Co. Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/ licenses/by-nc-nd/4.0/). * Corresponding author. E-mail address:
[email protected] (J. Torres-Quezada). Peer review under responsibility of Southeast University. +MODEL Please cite this article as: J. Torres-Quezada, A. Isalgue ´and H. Coch, Impact of solar reflectivity and infrared emissivity on the thermal performance of metal and concrete roofs in cloudy warm-humid climate, Frontiers of Architectural Research, https://doi.org/10.1016/ j.foar.2024.03.003 https://doi.org/10.1016/j.foar.2024.03.003 2095-2635/ª2024 The Author(s). Publishing services by Elsevier B.V. on behalf of KeAi Communications Co. Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/). Available online at www.sciencedirect.com ScienceDirect journal homepage: www.keaipublishing.com/foar Frontiers of Architectural Research xxx (xxxx) xxx
1. Introduction In buildings located in warm-humid climates near the equator, nearly half (52%) of the heat gains are through the roof (Chou et al., 2013;Torres-Quezada et al., 2018). The significance of this factor in influencing indoor conditions is attributed to the urban and geographic context of these regions, where low-rise buildings are prevalent (Diulio et al., 2016;United Nations, 2018) and there is high solar exposure on a horizontal plane (Boulifa et al., 2015; Kolokotroni et al., 2018). Therefore, in these regions, assessing the thermal behavior of roofs is essential to mitigate indoor thermal discomfort and, consequently, reduce the load on air conditioning systems. This is also applicable to similar regions (Al-Obaidi et al., 2014; Vijaykumar et al., 2007). In several countries with such climate and geographic conditions, like Malaysia (Allen et al., 2008), Singapore (Jusuf et al., 2007), Indonesia (Lauber et al., 2005), Costa Rica (INEC, 2011), Dominican Republic (ONE, 2010)or Ecuador (INEC, 2010), light metal sheets have traditionally been the most commonly used material for roofs. However, in recent decades, many of these countries, including the coastal areas of Ecuador, have witnessed a substantial shift in roofing materials, with a significant increase in the use of concrete roofs. In 1990, 67% of all roofs were constructed using metal sheets, while 16% were made of concrete (INEC, 1990). However, by 2018, these proportions had shifted to 27% for metal sheets and 26% for concrete (INEC, 2019). Although concrete roofs (CR) entail high installation costs, their material characteristics offer superior thermal resistance and thermal mass compared to metal roofs (MR). Consequently, CR can substantially decrease the heat flux through this roofing element. Typically, strategies for mitigating indoor overheating in climates with high solar radiation prioritize the utilization of materials with low thermal transmittance or the incorporation of roof insulation (Arumugam et al., 2015;Meddage et al., 2022). For example, Jim (2015), through an experimental work, analyzes the use of insulation in concrete roofs in a subtropical climate in China. The use of this strategy reduces daytime heat flux to the interior by 20% on sunny days. However, it also reduces heat losses during nighttime. Moreover, Tong et al. (2014) investigate the impact of using 2.5 cm of Expanded Polystyrene (EPS) on the interior surface temperature of concrete roofs. Simulations, validated by field experiments, were employed for this purpose. The study reveals a 5 C reduction in the maximum interior surface temperature and a slight 0.5 C increase in the minimum temperature on a clear-sky day. Although the majority of studies and regulations primarily focus on the use of insulation, it’s important to note that there are other parameters that also significantly affect the flow of heat into the interior (Santana et al., 2022). These parameters include reflectivity (Fantucci and Serra, 2019;Herna ´ndez-Pe ´rez et al., 2018;Pisello, 2017;Qiu et al., 2018) and emissivity (Mohd Ashhar and Haw, 2022;Synnefa et al., 2006). Both parameters are directly correlated with the climatic characteristics specific to each region: solar reflectivity is linked to solar radiation, and thermal emissivity is associated with the cooling radiative capacity of the sky (Geetha and Velraj, 2012;Ziming et al., 2020). For instance, Kolokotroni et al. (2018) analyze the influence of these variables on a concrete roof of a single-story house in Jamaica, considering a day with an average daily radiation of 5.8 kWh/m 2 and an average outdoor air temperature of 28 C. This study demonstrates that the application of high reflectivity and high emissivity materials reduces the interior surface temperature of the roof by an average of 6.8 C. Likewise, a study conducted in Palermo, Italy, found that the use of cool roof paint reduces the interior surface temperature by an average of 6.50 C during the hottest month (July), which experiences an average solar radiation of 5.2 kWh/ m 2 and a temperature of 27 C(Shittu et al., 2020). Furthermore, in the study of Zinger (2015a), the performance of a concrete roof and a metal roof was compared on a day with a daily solar radiation of 5.4 kWh/m 2 and an average sky temperature of 7 C. According to this study, conducted in Singapore, even though both roofs have the same reflectivity and emissivity values (rZ0.85, εZ0.95), the concrete roof reduces the heat flux to the interior more during the daytime due to its lower thermal transmittance. At night, owing to its high thermal mass, the concrete roof experiences fewer heat losses than the metal roof; however, it still maintains lower interior surface temperatures. Therefore, depending on these climatic conditions, the concrete roof consistently offers lower interior surface temperatures than the metal roof throughout the day. These studies indicate that the utilization of high solar reflectivity and high emissivity materials has significantly reduced roof overheating, particularly in climates characterized by high solar radiation and a strong cooling capacity of the sky. On one hand, they emphasize the significance of high reflectivity when confronted with elevated levels of solar radiation during the daytime. On the other hand, they underscore the importance of high emissivity and the cooling capacity of the sky, which not only impacts the daytime period but also plays a role during the nighttime. Nevertheless, Ecuador, much like several other regions around the world, experiences a warm-humid climate characterized by predominantly overcast skies (Torres- Quezada et al., 2017,2019), which can significantly diminish its radiative cooling capacity. While a previous study (Torres-Quezada et al., 2019) has examined the performance of the metal roof in climates with high cloud cover, there is no comprehensive analysis of the thermal behavior of the concrete roof in such climates, let alone a comparative study between these two types of roofs. So, the applicability of simulation models used in other regions, focused on sky models with high radiative cooling capacity, would likely result in higher inaccuracies in the study region. This could lead to the implementation of strategies with low efficiency. Furthermore, as mentioned earlier, the utilization of insulation or high thermal mass values has a significant effect on diminishing heat gains; however, they also reduce heat losses. In climates characterized by extensive cloud cover, where the radiative cooling capacity of the sky is comparatively lower than in other regions (Torres-Quezada et al., 2016), the impact of the radiative properties of the J. Torres-Quezada, A. Isalgue ´and H. Coch +MODEL 2
surface may or may not be decisive, depending on the thermal mass of the roofs. The primary focus of this research is to bridge the gap in understanding the impact of this climatic factor on the thermal performance of both types of roofs. To this end, characterizing the sky conditions in detail, and thereby developing a more refined simulation model, will be crucial to obtain more accurate results tailored to the study region. Thus, this study undertakes a comparative analysis of the thermal behavior of the light metal roof with the heavy concrete roof in regions with warm-humid climates and high cloudiness. The research analyzes the impact of modifying solar reflectivity and thermal emissivity on the inside surface temperature (T si ) of MR and CR in this specific climate conditions. 2. Materials and methods The methodology employed in this study relies on a process that combines simulations with validated measurements. This process was divided into four stages, as depicted in Fig. 1. Firstly, in situ measurements were conducted, focusing on capturing climatic conditions and the thermal and construction properties of the validation models. In the second stage, the climate data and the validation models were configured based on these measurements. The third stage involved model validation, achieved by comparing simulation results with the measured data. Finally, a parameterization of the thermal outcomes of the roofs was carried out, considering the two radiative properties. This parameterization was used to analyze the influence of reflectivity and emissivity on both MR and CR. Additionally, a comparative analysis of the thermal behavior of these two types of roofs was conducted. 2.1. Measurements These measurements were conducted in Santa Rosa-El Oro- Ecuador, in October and December of 2016. This city is located on the southern coast of this country, at a latitude of approximately 3270S and an altitude of 14 masl. 2.1.1. Climatic factors measurements Santa Rosa city experiences a consistently warm-humid climate year-round, with an average temperature and relative humidity of approximately 26 C and 85%, respectively. The temperature exhibits a daily fluctuation of 6 C and an annual variation of 4 C(WeatherCompanyLLC, 2016). Moreover, this city, along with the entire Coastal region of Ecuador, is known for its significant cloud cover, with an annual average of approximately 78% (Wilson and Jetz, 2016). The meteorological factors measured included air temperature, relative humidity, air velocity, and global solar radiation. These data were gathered from a meteorological station (Davis Vantage Pro2 Plus_Wireless) situated at coordinates 3.30S latitude, 79.89W longitude, and an elevation of 20 masl (WeatherCompanyLLC, 2016). The sensors used to measure these four parameters have an accuracy of 0.5 C for temperature, 3% for relative humidity, 3 km/h for air velocity, and 5% for global solar radiation. These measurements were collected at 15-min intervals throughout the entirety of 2016. The calibration and the details of all sensors of this meteorological station are specified in Torres-Quezada et al. (2021). In addition to these measurements, recognizing the significance of cloudiness in this region, two other climate factors were also collected in situ: cloud cover and sky temperature. The first factor (Wilson and Jetz, 2016) was obtained from direct observation (Luiz et al., 2018;Wacker et al., 2015). The process involved dividing the celestial vault into 4 equal spherical wedges. Cloudiness was quantified in each segment through observation, supported by photographs. The data from the four segments were averaged to obtain the final value for each measurement period. The data and methodology applied was obtained from a previous study (Torres-Quezada et al., 2019). Due to the anisotropy of the sky (Garcı ´a et al., 2021), multiple measurements of the sky vault, from the horizon to the zenith, were taken to obtain an average of the temperature of the sky. This sky factor was measured with an infrared thermometer TESTO 830 T4 with accuracy of 1.5 C(20 Ce0C) 1Cor1% of mv. The calibration procedure of this equipment was made according to ISO/IEC 17025:2017. The measurements were collected at 2 h intervals in October and December of 2016, as well as the cloud cover factor. Moreover, Torres-Quezada et al. (2021) contained the entire data obtained from these measurements. This collected data was used to configure the weather file in the next stage. In addition, these measurements served to determine the climatic factors of the day of analysis, which was established by considering all the data collected throughout that year and employing statistical analysis. The selection of this specific day was based on an emphasis on the region’s average extreme heat conditions, particularly the average extreme solar values, given the Fig. 1 Methodology diagram applied in the research. Frontiers of Architectural Research xxx (xxxx) xxx +MODEL 3
consistency of air temperature throughout the year. Fig. 2 shows the average, maximum, minimum, and standard deviation of the solar radiation values every month. According to them, a day with average extreme conditions corresponds to a day with solar radiation of around 4.5 kWh/m 2 . 2.1.2. Validation models measurements The validation models refer to two distinct residential buildings located in the study city. The first model with a MR and the second with a CR. The MR of the first model corresponds to a steel sheet panel, which is sheltered by a Galvalume coating (aluminum 55% þzinc 45%) (INEN, 2008) (ASTM A792/A792M-10, 2015), as shown in Fig. 3. The CR of the second model is a horizontal ribbed slab made of reinforced concrete and filled with hollow pumice blocks, as shown in Fig. 3. Measurements of these two roofs were conducted in two scenarios: under current conditions and after they were painted. The term “current conditions” refers to the original, unpainted, and aged surface, as both roof samples were more than 5 years old at the time the measurements were taken. Due to the passing of time and the lack of maintenance, the metal roof appears dusty and old though it has not rusted. This indicates that the roof surface had changed its appearance compared to a new metal sheet, as it had lost its shine and high reflectivity primarily due to the accumulation of dust on it. Furthermore, although the metal sheet shows no traces of rust, its surface exhibits greater roughness. In the case of the concrete roof, its surface finish has become moldy. This indicates that the roof surface had changed its appearance compared to the new concrete, as it had acquired a dark color due to the accumulation of residues from small layers of dried mold. These layers of mold can influence the change in the thermal transmittance of the roof. From this point onward, these samples are referred to as MR_old and CR_old. The “Painted conditions” denote the two roofs painted with high-reflective coatings. Both roofs were initially painted with a standard commercial white paint. However, MR was subsequently painted with a cool roof coating. These processes were carried out in January 2017. These samples are named as MR_white, CR_white, and MR_cool. Table 1 shows the specific features of all these samples. The surface temperature of the two sets of samples has been simulated and validated with measurements. Sincethescopeofthisstudy is the thermal behavior of the roofs, the measurements focus on visible reflectivity, thermal infrared emissivity, outside surface temperature (T s ), and inside surface temperature (T si )in both roofs. In addition to these parameters, indoor air temperature and infiltrations were measured within the interior of the two spaces covered by each of the roofs. However, it’s important to note that these parameters were solely utilized to configure and validate the software model. The process of measuring reflectivity begins by comparing the MR and CR surfaces with a reference surface (white paper, 80 g/m 2 ) through the capture of photographic images. This method is grounded in previous studies (Baneshi et al., 2016;Levinson et al., 2010;Lo ´pez-Besora et al., 2014). Next, the histograms of each sample and the white paper were generated using Adobe Photoshop. The visible reflectivity of the reference surface was obtained through calculations from measured apparent luminance and illuminance. The reflectivity value of white paper was established through Eq. (1), assuming a Lambertian reflection of this surface. rZ pL E;ð1Þ where ris the reflectivity value, Lis the luminance value expressed in cd/m 2 and Eis the illuminance value expressed in luxes. The instruments used to measure the illuminance and luminance values were a Light meter LX1010B with an accuracy of 5%, and a Konica Minolta LS 110 luminance meter with an accuracy of 2% of measured values, respectively. After this process, the value obtained for the visible reflectivity of the reference surface was 0.85. Regarding the emissivity measurements, the procedure commences with the measurement of the external radiant temperature using an infrared camera (FLIR I7) with an accuracy of 2%. The camera is adjusted to an emissivity value of 1.00. Simultaneously, the outside surface temperature is measured using a multi-logger thermometer equipped with a thermocouple type K (Amprobe TMD 56) with an accuracy of 0.05%. This method was based on other studies (ASTM, 1999;Vollmer and Mo ¨llmann, 2018). Subsequently, the infrared camera software (FLIR Tools) was employed to adjust the radiant temperature to match the surface temperature by modifying the emissivity value. Once this adjustment was achieved, the emissivity value was determined. Another parameter configured in the software was the reflected temperature, which was assumed to be the same as the sky temperature value. Fig. 2 Average value, maximum, minimum, and standard deviation values of the solar radiation in every month of 2016 measured in Ecuador, and a monthly average of solar radiation simulated without clouds. Data obtained from WeatherCompanyLLC (2016). J. Torres-Quezada, A. Isalgue ´and H. Coch +MODEL 4
Both the interior and exterior surface temperatures of these roofs were measured using the same multi-logger thermometer as specified earlier, as shown in Fig. 3(c) and (d). The instrument was configured to collect data at 10-min intervals during October and December of 2016. The measurements of interior and exterior surface temperature were used to validate the results obtained from simulations. Regarding the measurement of interior air temperature, data were collected at 10-min intervals using the datalogger TESTO 174H, which has an accuracy of 0.5 C(20 to þ70 C). The measurement of infiltrations followed the method outlined in (Instituto_Nacional_Seguridad_e_Higiene_en_el_Trabajo, 1994). By measuring CO 2 concentrations in both rooms for several hours, an estimation of infiltrations was obtained. Fig. 3 (a) Constructive detail, (b) thermocouple position in the residential building, (c) outside and (d) inside surface temperature measurements of metal roof (left) and concrete roof (right). Frontiers of Architectural Research xxx (xxxx) xxx +MODEL 5
2.2. Software configuration The software used at this stage was Design Builder 4.5.0.148 interface (DesignBuilder, 2016) and Energy Plus as a computation engine (DOE, 2017). DesignBuilder is considered as the advanced user interface for EnergyPlus which is an energy simulation program for heat transfers, energy consumption and more (Pelaz et al., 2017). Simulation tool was used to generate the results of surface temperature and air temperature. To calculate these parameters, Energy Plus uses the Conduction Transfer Function (CTF) el cual se basa en un ca ´lculo de nu ´meros infinitos. This method is efficient to compute surface heat fluxes because they eliminate the need to know temperatures and fluxes within the surface. However, to reduce instability of the calculations, a method that develop CTF series from finite difference approximations to the heat conduction equation (Seem, 1987) were considered to address this problem. To characterize the environment the Simulation tool uses a weather file named as Energy Plus Weather (EPW file). The EPW specifies the outside air temperature, relative humidity, solar radiation, infrared radiation, air velocity and more. Accordingly, to calculate the balance of the outer surface, Eq. (2) is used. qn fsol þqn LWR þqn conv qn koZ0;ð2Þ where qn fsol ZAbsorbed direct and diffuse solar (short wavelength) radiation heat flux; qn LWR ZNet long wavelength (thermal) radiation flux exchange with the air and surroundings; qn conv ZConvective flux exchange with outside air; qn ko ZConduction heat flux (q/A) into the wall. According to this, the conduction heat flux depends on various climatic factors before passing into the interior. Therefore, before validating the simulation model, it has been necessary to configure the climate file and housing models according to the field data, as explained below. 2.2.1. Weather file configuration The configured file was the EPW (Energy Plus Weather) file, which was utilized by Design Builder. Various weather parameters, including air temperature, dew point, relative humidity, atmospheric pressure, global horizontal radiation, wind direction, wind speed, total sky cover, and present weather codes, were directly set based on measurements. However, horizontal infrared radiation intensity, diffuse horizontal radiation, and direct normal radiation were derived through calculations using measurements of other parameters. The calculation methods employed for these parameters are in accordance with those specified in the software (ENERGYPLUS, 2015), and their descriptions are provided below. Regarding Horizontal Infrared Radiation Intensity (HIR), which represents the long-wave radiation emitted by the sky and governs its radiative exchange with the roof (Qin et al., 2017), it was determined using Eq. (3). This equation takes into account the temperature of the sky (T sky ) and incorporates a correction factor based on the emissivity (ε) of the sky. HIRZε$s$Tsky4 ;ð3Þ where εis the emissivity of the sky, T sky is the sky temperature (C) and sis the Stefan-Boltzmann constant (5.67 10 8 W/(m 2 K 4 )). The sky temperature taken for these calculations corresponds to the measurements made in situ. The value of ε has been calculated from Eq. (4). In this equation, T dp represents the dew point temperature (C) and Nis the opaque sky cover in tenths. Both of these factors were acquired through in situ measurements. Regarding the diffuse solar radiation (DR), this parameter was obtained from the horizontal global radiation (HGR) and the sky cover (N) measured in situ, see Eq. (5): DRZHGR$N:ð5Þ Direct normal radiation (NR) was calculated from Eq. (6): NRZHGR DR cos q;ð6Þ εZ0:787 þ0:764 lnTdp273ð1þ0:0224Nþ0:0035 N2þ0:00028 N3Þð4Þ Table 1 Specific features of all samples. State Samples Graphic code Surface Specifications Unpainted and Old MR_old Old and Dusty CR_old Old and moldy With paint coating MR_white Clean and painted white (2 layers of latex Paint) CR_white Clean and painted white (2 layers of latex Paint) MR_cool Clean and painted with cool roof paint (2 layers of a cool roof) J. Torres-Quezada, A. Isalgue ´and H. Coch +MODEL 6
where qis the solar angle at each hour on each day at the established latitude (), which was obtained using the simulation software. According to the measurements, two time periods were configured, one in October and the other in December. The detailed configuration of these two weeks is provided in the reference cited (Torres-Quezada et al., 2021). As mentioned earlier, one specific day (October 10) from these simulations was selected for a detailed analysis, and this chosen day serves as the analysis day for all subsequent simulations. Finally, an average value of 25.8 C for the ground temperature was assigned for all months of the year to define the boundary condition for the floor flux on the ground floor. Additionally, several walls of the two samples adjoining other buildings were considered adiabatic. The specific considerations for these boundary conditions are described in the Department of Energy (2022). 2.2.2. Validation models configuration The thermal configuration of MR and CR buildings for their simulation was determined based on the measured characteristics of each experimental model. The radiative properties of the roofs considered at this stage correspond to the scenario with the roofs in their old conditions. These buildings share similar characteristics like occupancy, thermal characteristics of the envelope, and null direct solar gains since both do not have windows. The thermal properties of the roofs were obtained from the measurements, while the walls and the floor were calculated with the use of the simulation software and based on bibliography. Given that the reflectivity measurements were focused solely on the visible range, their solar reflectivity has been set with the same value. Finally, infiltrations and the occupancy values were determined based on data collected in situ. The simulation parameters of these two experimental models are displayed in Table 2. 2.3. Validation After configuring the climate file and validation models in the simulation software, simulated results for outdoor surface temperature, indoor surface temperature, and indoor air temperature during the two analysis periods were obtained. These results were then compared with the measurements obtained. 2.4. Parametrization Since reflectivity and emissivity can vary significantly due to the use of coatings or natural aging (Torres-Quezada et al., 2019), the thermal behavior of the roof is analyzed considering a wide range of variations in these two parameters under the measured climatic conditions. To achieve this, the inside surface temperature of both roofs was parameterized based on changes in their reflectivity and emissivity, ranging from 0.1 to 1.00. This parameterization involves a graphical representation where the behavior of T si is depicted using a color scale, depending on the values of reflectivity on the x-axis and emissivity on the y-axis. Separate analyses were conducted for the daytime and nighttime periods. Since the analysis is conducted near latitude 0, both periods have approximately 12 h throughout the year. As a result, the temperatures of the daytime and nighttime periods were averaged and presented in separate graphs. This parameterization serves two main objectives. Firstly, it aims to assess the individual effects of radiative properties on both MR and CR. Secondly, it aims to compare the thermal performance of these two roofs under different radiative conditions (old and painted) within the climatic conditions of the study region. 3. Results and discussion 3.1. Measurements 3.1.1. Climate factors measurements The climatic factors for the analyzed day are presented in Fig. 4. On one hand, this figure illustrates the solar radiation (W/m 2 ) and cloud cover (tenths), as depicted in Fig. 4(a). Furthermore, the figure includes the simulated solar radiation under clear sky conditions, obtained using Heliodon (Beckers and Masset, 2003). On the other hand, Fig. 4(b) displays the outdoor air temperature (T a ), relative humidity (RH ), and sky temperature (T sky ). Based on these results, the measured solar radiation (SR_meas) exhibits significant variability and irregularity, with values falling below the simulated values (SR_sim) for most of the day. The daily average of SR_meas (4.4 kWh/ m 2 ) represents only 71% of the SR_sim (6.2 kWh/m 2 ), even on a day characterized by extreme heat conditions in this region. This pattern is closely associated with the extensive cloud cover, which diminishes the amount of solar radiation reaching the surface. In addition, high cloud cover significantly affects the radiative properties of the sky. According to on-site measurements, the sky conditions in this region are characterized by 83% cloudiness and T sky of 15.5 C. This highlights the limited radiative cooling capacity of the sky in this area. These conditions become more pronounced during Table 2 Simulation parameters of the experimental models. MR CR Roof Solar reflectivity 0.52 0.25 Visible reflectivity 0.52 0.25 Emissivity 0.30 0.90 Thermal mass 0.65 kJ/(m 2 $K) 70.51 kJ/(m 2 $K) U-value 7.40 W/(m 2 $K) 2.68 W/(m 2 $K) Walls U-value 3.20 W/(m 2 $K) 3.20 W/(m 2 $K) Floor U-value 1.96 W/(m 2 $K) 2.10 W/(m 2 $K) Occupancy 0.04 people/ m 2 (24 h) 0.035 people/m 2 (24 h) Infiltrations 0.70 ac/h (24 h) 0.60 ac/h (24 h) Ground temperature 25.80 C 25.80 C Frontiers of Architectural Research xxx (xxxx) xxx +MODEL 7
the nighttime, with an average T sky of 19 C at night compared to 11 C during the daytime. Furthermore, the average temperature difference between T a and T sky is 4 C during the night period and 14 C during the diurnal period. Even the highest value of T sky at night (19 C) is only 2 C lower than T a at that moment. This difference is significantly lower than that observed in other climates (Abu Dhabi and New Delhi), where the annual average difference is approximately 12 C(Zingre et al., 2020). Hence, due to the minimal difference between T a and T sky , the longwave radiation heat flux directed towards the sky is restricted in this region, in contrast to other areas with predominantly clear sky conditions. As a result, the average extreme day in this region is typified by moderate radiation levels (4.4 kWh/(m 2 $day)) and a limited sky cooling capacity (T sky Z15.5 C). These values exhibit a notable difference of 20% and 42% compared to the typical solar radiation and sky temperature data observed in other regions (Shittu et al., 2020; Zingre et al., 2015a). 3.1.2. Roof parameters measurements Fig. 5 shows the inside and outside surface temperature of the building roofs. Nevertheless, due to the high thermal transmittance of the metal roof, only the inside surface temperature is displayed which is nearly identical to the outside surface temperature. This similarity is also observed in other studies (Biwole et al., 2008;Zingre et al., 2015a). Additionally, the outdoor air temperature measured (T a ) is provided as reference for the analysis. These data pertain to both roofs in their aged-unpainted condition (MR_old and CR_old). Based on measurements of the radiative properties in this condition, their visible reflectivity is 0.52 for MR and 0.25 for CR, while their emissivity is 0.30 and 0.90, respectively. In regards to the inside surface temperatures, T si _M- R_old shows an inconstant and irregular behavior, which is quite similar to the SR_meas, see Fig. 4(a). By contrast, T si _CR_old exhibits a smoother behavior with lower oscillations and a delay compared to T si _MR_old. The maximum value of T si _MR_old is 66 C, occurring around 12:30, coinciding with the peak of solar radiation. In contrast, the maximum T si _CR_old is 35 C, reached approximately 4 h later than the metal roof. Due to the different thermal mass, thermal resistance, and thickness of these two roof types, the impact of radiation on the metal roof is high and instantaneous, whereas the heavy roof exhibits a much lower response. Furthermore, when solar radiation diminishes, T si _MR_old drops immediately to 26 C, whereas T si _CR_old remains at 35 C, indicating differences of 0.5 C and 10 C above T a , respectively. In fact, T si _MR_old is nearly equal to T a but the T si _CR_old maintains its temperature 4e5C above T a during the whole night. Once again, these results highlight the influence of the varying thermal resistance and thermal mass of these two roofs. On the one hand, the T si _MR_old can reduce its temperature immediately after solar radiation disappears. On the other hand, the inside surface and even the outside surface of the concrete roof do not reduce their Fig. 4 Climatic factors of the analyzed day. (a) Cloud cover, global solar radiation obtained by measurements (SR_meas), and solar radiation obtained by simulations with 0% of cloudiness (SR_sim). (b) Relative humidity (RH ), outdoor temperature (T a ), and sky temperature (T sky ). Fig. 5 Measured values of outdoor air temperature (T a ), outside and inside surface temperature of the building concrete roof (T s _CR_old/T si _CR_old), and inside surface temperature of the building metal roof (T si _MR_old), on the analyzed day. J. Torres-Quezada, A. Isalgue ´and H. Coch +MODEL 8
temperature below T a at any time of the night. Consequently, the T si and T s of the concrete roof are on average 4C and 2 C respectively higher than T a in the night period. In addition to the high thermal mass of the concrete roof, this condition is intensified due to the low cooling capacity of the sky. On the contrary, other studies (Zingre et al., 2015a;2015b) show that the outer surface of concrete roofs can reduce its temperature up to 3 C below the air temperature at night. Furthermore, T si _MR_old is higher than T si _CR_old during the daytime. However, at nighttime, these results are reversed. During the day, the average difference between the inside surface temperatures of MR and CR is 10 C, while at night, this difference is 2.5 C. Despite these opposite behaviors, on a daily average, CR exhibits better thermal behavior than MR in its current conditions (old conditions), with a lower temperature and a smaller oscillation amplitude. With regard to the measurements of the radiative properties, Fig. 6 displays the visible reflectivity and thermal emissivity values for all samples. Additionally, it presents values for a sample of both roofs in a new-unpainted state (MR_new/CR_new) obtained from the literature. These values in the new state serve as a reference for the analysis. Based on these measurements, the aged samples of both roofs (MR_old/CR_old) exhibit reduced reflectivity compared to the samples in their new state (MR_new/ CR_new). However, regarding emissivity, the metal roof shows an increase, while the concrete roof maintains a similar value. From this point onward, all comparisons are made with reference to the values of the two roofs in their new state. MR_old exhibits a reduction in reflectivity of 0.23 (from 0.75 to 0.52). In parallel, CR_old displays a reduction of 0.15, from 0.40 to 0.25. Additionally, the emissivity of the metal roof shows an increase of 0.17 (from 0.13 to 0.30). This change is a result of the accumulation of dust and oxidation over time, transforming the surface of the metal roof from polished to rough and consequently increasing its emissivity (Torres-Quezada et al., 2019). The results for the painted samples demonstrate a significant alteration in the reflectivity and emissivity of both roofs compared to their new state. In all measured samples of both roofs, both radiative properties increase. For the metal roof samples, MR_cool shows a reflectivity increase of 0.11 (from 0.75 to 0.86) and 0.77 increase in emissivity (from 0.13 to 0.90), while MR_white exhibits a reflectivity increase of 0.03 (from 0.75 to 0.78) and 0.82 increase in emissivity (from 0.13 to 0.95). Likewise, CR_white displays an increase in both radiative parameters, with a 0.36 increase in reflectivity (from 0.40 to 0.76) and a 0.05 increase in emissivity (from 0.90 to 0.95). The results imply that the aging effect on MR can have either a negative or positive impact on surface temperature. Aging may diminish its ability to reflect solar radiation while enhancing its capacity to emit thermal radiation (heat). On the other hand, aging in CR only has a negative impact as degradation reduces its ability to reflect solar radiation. In reference to the painted samples, the use of paint on the MR does not have a high influence on the increment of its reflectivity; nevertheless, it has a high impact on the increment of its emissivity. In contrast, the paint’s impact on the concrete roof is significant on its reflectivity but minimal on its emissivity, since the concrete’s emissivity is high in both the painted and non-painted states. The values of these samples have been used in the parameterization section to compare the thermal behavior between the MR and the CR in different states from data taken in situ. 3.2. Validation results Fig. 7 shows the comparison between the simulated and measured results of the outside surface temperature, the inside surface temperature, and the interior air Fig. 6 Visible reflectivity and thermal emissivity measured values of (a) the MR and (b) the CR samples in their aged and painted condition. The values of MR_new and CR_new were obtained by bibliography Bergman et al. (2011) and ASHRAE (2013). Frontiers of Architectural Research xxx (xxxx) xxx +MODEL 9
Qin, Y., Zhang, M., Hiller, J.E., 2017. Theoretical and experimental studies on the daily accumulative heat gain from cool roofs. Energy 129, 138e147. Qiu, T., Wang, G., Xu, Q., Ni, G., 2018. Study on the thermal performance and design method of solar reflectiveethermal insulation hybrid system for wall and roof in Shanghai. Sol. Energy 171, 851e862. Santana, B.O., Torres-Quezada, J., Coch, H., Isalgue, A., 2022. Monitoring and calculation study in mediterranean residential spaces: thermal performance comparison for the winter season. Buildings 12. Seem, J.E., 1987. Modeling of Heat Transfer in Buildings (Ph.D Thesis). University of Wisconsin, Madison. Shittu, E., Stojceska, V., Gratton, P., Kolokotroni, M., 2020. Environmental impact of cool roof paint: case-study of house retrofit in two hot islands. Energy Build. 217, 110007. Synnefa, a., Santamouris, M., Livada, I., 2006. A study of the thermal performance of reflective coatings for the urban environment. Sol. Energy 80, 968e981. Tong, S., Li, H., Zingre, K.T., Wan, M.P., Chang, V.W.C., Wong, S.K., Toh, W.B.T., Lee, I.Y.L., 2014. Thermal performance of concrete-based roofs in tropical climate. Energy Build. 76, 392e401. Torres-Quezada, J., Coch, H., Isalgue ´, A., 2021. Data set of climatic factors measured in a low latitude region with warm and humid climate: solar radiation, cloud cover and sky temperature. Data Brief 38, 107404. Torres-Quezada, J., Coch, H., Isalgue ´, A., 2019. Assessment of the reflectivity and emissivity impact on light metal roofs thermal behaviour, in warm and humid climate. Energy Build. 188e189, 200e208. Torres-Quezada, J., Coch, H., Isalgue ´, A., 2017. The roof thermal behavior in a tropical-equatorial climate. 1st International Congress on Architecture Doctorates. Torres-Quezada, J., Coch, H., Isalgue ´, A., Lo ´pez, J., 2018. The roof impact on the heat balance of low height buildings at low latitudes. Smart and Healthy within the 2-degree Limit. PLEA. Torres-Quezada, J., Pages, A., Coch, H., Isalgue ´, A., 2016. Radiative Performance assessment of two roofs in Meditarranean and Equatorial climates. In: First International Conference on Urban Physics, pp. 337e348. Quito, Ecuador. United Nations, D. of E., 2018. World urbanization prospects. Demogr. Res. Vijaykumar, K.C.K., Srinivasan, P.S.S., Dhandapani, S., 2007. A performance of hollow clay tile (HCT) laid reinforced cement concrete (RCC) roof for tropical summer climates. Energy Build. 39, 886e892. Vollmer, M., Mo ¨llmann, K.P., 2018. Infrared Thermal Imaging: Fundamentals, Reserach and Aplications, second. Wiley, Weinheim-Germany. Wacker, S., Gro ¨bner, J., Zysset, C., Diener, L., Tzoumanikas, P., Kazantzidis, A., Vuilleumier, L., Sto ¨ckli, R., Nyeki, S., Ka ¨mpfer, N., 2015. Cloud observations in Switzerland using hemispherical sky cameras. J. Geophys. Res. 120, 695e707. WeatherCompanyLLC, 2016. Estacio ´n Meteorolo ´gica Ieloroel2 (ElCambio). Wilson, A., Jetz, W., 2016. Remotely Sensed High-Resolution Global Cloud Dynamics for Predicting Ecosystem and Biodiversity Distributions. Ziming, C., Fuqiang, W., Dayang, G., Huaxu, L., Yong, S., 2020. Low-cost radiative cooling blade coating with ultrahigh visible light transmittance and emission within an “atmosphericwindow.”.Sol.EnergyMater.Sol.Cell.213, 110563. Zingre, K., Kumar, K., Pun Wan, M., 2020. Analysing the effect of substrate properties on building envelope thermal performance in various climates. Energies 13 (19), 1e8. Zingre, K.T., Wan, M.P., Tong, S., Li, H., Chang, V., Wong, S.K., Toh, W.B.T., Lee, I.Y.L., 2015a. Modeling of cool roof heat transfer in tropical climate. Renew. Energy 75, 210e223. Zingre, K.T., Wan, M.P., Wong, S.K., Toh, W.B.T., Lee, I.Y.L., 2015b. Modelling of cool roof performance for double-skin roofs in tropical climate. Energy 82, 813e826. J. Torres-Quezada, A. Isalgue ´and H. Coch +MODEL 16