scieee AI-readable full text Open interactive document viewer

On-line core losses determination in ACSR conductors for DLR applications

Riba Ruiz, Jordi-Roger,Liu, Yuming,Moreno Eguilaz, Juan Manuel,Sanllehí Muñoz, Josep

Abstract

Dynamic line rating (DLR) is a method that focuses on dynamically determining the maximum allowable current of power lines, while ensuring they operate within safe limits. DLR needs to monitor the temperature and current of the line in real-time, as well as the weather variables in the surroundings of the power line. DLR approaches also require determining the AC resistance of the power line conductors, which is a key parameter that enables it to determine Joule and core losses. This paper presents an approach for an on-line alternating current (AC) resistance estimation of aluminum conductor steel-reinforced (ACSR) conductors to determine the DLR capability of such conductors from real-time conductor and meteorological parameter measurements. For this purpose, conductors with one, two and three layers of aluminum strands are analyzed in detail. Based on the experimental results presented in this paper, two possible approaches are proposed.

Full text

Citation: Riba, J.-R.; Liu, Y.; Moreno-Eguilaz, M.; Sanllehí, J. On-Line Core Losses Determination in ACSR Conductors for DLR Applications. Materials 2022,15, 6143. https://doi.org/10.3390/ ma15176143 Academic Editor: Federico Mazzucato Received: 17 July 2022 Accepted: 2 September 2022 Published: 4 September 2022 Publisher’s Note: MDPI stays neutral with regard to jurisdictional claims in published maps and institutional affiliations. Copyright: © 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https:// creativecommons.org/licenses/by/ 4.0/). materials Article On-Line Core Losses Determination in ACSR Conductors for DLR Applications Jordi-Roger Riba 1,* , Yuming Liu 1,2 , Manuel Moreno-Eguilaz 1and Josep Sanllehí2 1Electrical Engineering Department, Universitat Politècnica de Catalunya, Rambla Sant Nebridi 22, 08222 Terrassa, Spain 2SBI Connectors, Albert Einstein, 5, 08635 Sant Esteve Sesrovires, Spain *Correspondence: jor[email protected]; Tel.: +34-937398365 Abstract: Dynamic line rating (DLR) is a method that focuses on dynamically determining the maximum allowable current of power lines, while ensuring they operate within safe limits. DLR needs to monitor the temperature and current of the line in real-time, as well as the weather variables in the surroundings of the power line. DLR approaches also require determining the AC resistance of the power line conductors, which is a key parameter that enables it to determine Joule and core losses. This paper presents an approach for an on-line alternating current (AC) resistance estimation of aluminum conductor steel-reinforced (ACSR) conductors to determine the DLR capability of such conductors from real-time conductor and meteorological parameter measurements. For this purpose, conductors with one, two and three layers of aluminum strands are analyzed in detail. Based on the experimental results presented in this paper, two possible approaches are proposed. Keywords: core losses; aluminum conductor steel-reinforced; ac resistance; dynamic line rating 1. Introduction Today, renewable power generation sources are reinforcing distribution networks. The growing demand for electricity is forcing system operators to take full advantage of the maximum capacity of existing power lines [ 1 ]. However, the maximum allowable temperature of the conductor must not be exceeded, as it defines the current carrying capacity of the conductor [ 2 ]. The ampacity or maximum allowable loading current is established by the maximum permissible temperature of the conductor [ 3 ]. Temperature has a great influence on the mechanical sag of overhead transmission lines [ 4 , 5 ], which is a key parameter for power system operation [ 6 ]. Overhead power transmission lines are generally operated below their static line rating (SLR). The SLR is calculated when the conductor operates at the maximum allowable temperature in conservative weather conditions. Contrarily, dynamic line rating (DLR) determines the actual ampacity when conductors are operating at the maximum allowable temperature under actual weather conditions [ 7 ]. DLR can be useful for the integration of intermittent renewable energy sources into existing power networks [ 8 ]. Intermittent renewable energy sources (IRES) cannot provide constant additional power, making it difficult for system operators to justify the investment required to expand current transmission lines [ 9 ]. Dynamic line rating (DLR) allows for the maximum utilization of the conductor, that is, to operate at the maximum ampacity or current that it can withstand without exceeding the upper allowed temperature of the conductor [ 10 ]. Although there are different approaches to DLR, the most common approach is to measure weather variables, line current and temperature using dedicated sensors [ 11 ]. These measured variables are used to feed mathematical models of conductors, such as the CigréTB207 [ 12 ] and IEEE [ 13 ] models, from which the maximum conductor rating is dynamically obtained. Results obtained are significantly dependent on weather conditions, including ambient temperature, wind speed and direction, or solar radiation, although wind speed significantly affects the resulting ampacity [14,15]. Materials 2022,15, 6143. https://doi.org/10.3390/ma15176143 https://www.mdpi.com/journal/materials Materials 2022,15, 6143 2 of 14 The alternating current resistance (R ac ) of the conductor is a key parameter which allows the ampacity or maximum current capacity of power conductors to be accurately estimated. This can increase their effective capability [ 16 ], since Joule and core losses represent the main heat source of the conductor, and can be determined from the alternating current (AC) resistance R ac [ 17 , 18 ]. Line current, along with ac resistance, are used in some DLR approaches to estimate the effective wind speed [ 18 ]. Therefore, DLR enables the development of more accurate power flow analysis approaches if the ac resistance, which changes with temperature, is measured in real time [19]. Stranded aluminum conductor steel-reinforced (ACSR) conductors have been applied for over 100 years in overhead power lines to transmit electrical power at high voltage [ 20 ]. ACSR conductors have multiple layers of aluminum [ 21 ] and galvanized steel strands. The aluminum wires are wound helically around the core formed by the galvanized steel strands. Adjacent aluminum layers are wound in opposite directions around the steel core [ 22 ]. Whereas the steel core provides the mechanical strength, high-conductivity aluminum strands provide the current path [ 23 ], carrying approximately 98% of the electric current [ 24 ]. Electric current tends to spiral along the aluminum strands because the contact resistance between adjacent strands is much greater than the internal resistance of the strands, producing an axial component of the magnetic field. The axial AC magnetic flux causes eddy currents and hysteresis losses in the core, and forces the current density in the aluminum layers to redistribute to a greater or lesser extent, depending on the strength of the magnetic field in the core, and thus, on the intensity of the electric current and the lay length of the aluminum layers [ 25 ]. The lay length is the distance the wire requires to make a complete revolution around the diameter of the conductor, as shown in Figure 1. Therefore, due to magnetic induction, the steel core increases the AC resistance of the conductor [23]. Materials 2022, 15, x FOR PEER REVIEW 2 of 15 on weather conditions, including ambient temperature, wind speed and direction, or solar radiation, although wind speed significantly affects the resulting ampacity [14,15]. The alternating current resistance (Rac) of the conductor is a key parameter which allows the ampacity or maximum current capacity of power conductors to be accurately estimated. This can increase their effective capability [16], since Joule and core losses represent the main heat source of the conductor, and can be determined from the alternating current (AC) resistance Rac [17,18]. Line current, along with ac resistance, are used in some DLR approaches to estimate the effective wind speed [18]. Therefore, DLR enables the development of more accurate power flow analysis approaches if the ac resistance, which changes with temperature, is measured in real time [19]. Stranded aluminum conductor steel-reinforced (ACSR) conductors have been applied for over 100 years in overhead power lines to transmit electrical power at high voltage [20]. ACSR conductors have multiple layers of aluminum [21] and galvanized steel strands. The aluminum wires are wound helically around the core formed by the galvanized steel strands. Adjacent aluminum layers are wound in opposite directions around the steel core [22]. Whereas the steel core provides the mechanical strength, high-conduc- tivity aluminum strands provide the current path [23], carrying approximately 98% of the electric current [24]. Electric current tends to spiral along the aluminum strands because the contact resistance between adjacent strands is much greater than the internal resistance of the strands, producing an axial component of the magnetic field. The axial AC magnetic flux causes eddy currents and hysteresis losses in the core, and forces the current density in the aluminum layers to redistribute to a greater or lesser extent, depending on the strength of the magnetic field in the core, and thus, on the intensity of the electric current and the lay length of the aluminum layers [25]. The lay length is the distance the wire requires to make a complete revolution around the diameter of the conductor, as shown in Figure 1. Therefore, due to magnetic induction, the steel core increases the AC resistance of the conductor [23]. La y len g th / 2 Figure 1. Stranded conductor and lay length. Due to the opposite stranding directions of adjacent aluminum layers, the axial components of the magnetic field generated by the currents from adjacent layers are in opposite directions, which reduces the total magnetic field. The greatest cancellation of the magnetic field occurs in conductors with two aluminum layers, this effect being less marked in conductors with an odd number of aluminum layers than in conductors with an even number of layers [23,25,26]. Therefore, ACSR conductors with an even number of aluminum layers have lower magnetic core losses [22]. Under AC supply, the axial component of the magnetic field generates eddy currents and hysteresis losses, and modifies the current distribution between the layers. This effect, due to the magnetic coupling of the current in the aluminum layers through the steel core [3], is known as the transformer effect. The magnitude of the axial magnetic flux largely determines the intensity of the transformer effect, so it varies with the intensity of the electric current and the magnetic permeability of the steel core, which in turn depends on the tensile stress of the core and the temperature [27]. The non-uniformity of the current density in the different layers of aluminum due to the transformer effect is greatest for three-layer ACSR conductors [3]. Experimental results performed on a three-layer ACSR conductor show that the current density in the central layer is higher than in the other layers, resulting in a higher Rac/Rdc ratio [28], Rdc being the direct current (DC) resistance. This is mainly due to the transformer effect [26,27] Figure 1. Stranded conductor and lay length. Due to the opposite stranding directions of adjacent aluminum layers, the axial components of the magnetic field generated by the currents from adjacent layers are in opposite directions, which reduces the total magnetic field. The greatest cancellation of the magnetic field occurs in conductors with two aluminum layers, this effect being less marked in conductors with an odd number of aluminum layers than in conductors with an even number of layers [ 23 , 25 , 26 ]. Therefore, ACSR conductors with an even number of aluminum layers have lower magnetic core losses [ 22 ]. Under AC supply, the axial component of the magnetic field generates eddy currents and hysteresis losses, and modifies the current distribution between the layers. This effect, due to the magnetic coupling of the current in the aluminum layers through the steel core [ 3 ], is known as the transformer effect. The magnitude of the axial magnetic flux largely determines the intensity of the transformer effect, so it varies with the intensity of the electric current and the magnetic permeability of the steel core, which in turn depends on the tensile stress of the core and the temperature [ 27 ]. The non-uniformity of the current density in the different layers of aluminum due to the transformer effect is greatest for three-layer ACSR conductors [ 3 ]. Experimental results performed on a three-layer ACSR conductor show that the current density in the central layer is higher than in the other layers, resulting in a higher R ac /R dc ratio [ 28 ], R dc being the direct current (DC) resistance. This is mainly due to the transformer effect [ 26 , 27 ] or current redistribution among the aluminum layers, and only partially due (to a lesser extent) to the eddy currents and hysteresis losses that occur in the steel core [28]. This paper presents an approach for an on-line estimation of the AC resistance of ACSR conductors to determine their DLR capacity from real-time conductor measurements Materials 2022,15, 6143 3 of 14 and weather parameters, thus presenting several novel findings and making unique contributions in this area. Joule and core losses are determined from an on-line measurement of the AC resistance, which, due to its low value, makes its on-line measurement under AC supply a challenging task. The approach proposed here to estimate the AC resistance can be applied to ACSR conductors with any number of aluminum layers, while considering its dependence on the line current. This is a novelty in this work, since most of the current DLR approaches do not take into account the change in the AC resistance of ACSR conductors with the current level, so they can lead to inaccurate estimates of the AC resistance, and thus of the DLR ampacity. To this end, two new methods are proposed to determine the AC resistance. The first one, which is more accurate, is based on measuring temperature, current, voltage drop and the phase shift between voltage drop and current over a short length of conductor. The second method only requires measuring the temperature and current through the conductor, thus avoiding measuring the voltage drop and simplifying installation and measurement requirements. The proposal presented here is in line with the current trend of operating power lines at their maximum instantaneous capacity, since it allows the current rating to be adapted to existing weather conditions in real-time. In addition, it is simple to apply, requires a low computational burden, and is compatible with the Internet of Things (IoT), one of the crucial technologies that improves smartness in many industrial, power line and smart grid applications [ 29 – 31 ], whose basic function is to connect objects [ 32 ], including intercommunicating sensors [ 33 ], actuators and other smart technologies [34]. The experimental results presented in this paper show that the two proposed approaches are suitable for an on-line determination of the AC resistance of ACSR conductors to apply DLR strategies, so that it is possible to take advantage of the full transmission capacity of ACSR-based power lines. The accuracy of the proposed approaches has been evaluated by analyzing different ACSR conductors, including single-, two- and three-layer conductors in different working conditions, covering a wide range of operations in different weather conditions. This paper is structured as follows: Section 2describes the theoretical background, including how to experimentally determine the AC resistance of ACSR conductors, the equations required to estimate power losses in ACSR conductors, the transient thermal balance equation for ACSR conductors and the calculation of the DLR ampacity; Section 3 describes the experimental setup used in this paper, including the electrical loop, the analyzed conductors, the high-current power transformer, the sensors used and the measuring devices; Section 4shows the experimental results obtained with the different conductors and discusses the results attained; and finally, Section 5concludes the paper. 2. Theoretical Background 2.1. AC Resistance and Reactance of ACSR Conductors The AC resistance of a conductor is affected by the current density distribution, the internal temperature and the magnetic properties of the steel core, with the two last parameters being affected by the intensity of the electric current. According to [ 35 ], the AC resistance of ACSR conductors can be expressed as the sum of three terms, i.e., the DC resistance, the resistance term due to eddy currents, and the term due to hysteresis losses. Core losses (hysteresis and eddy current losses) as well as any temperature rises also increase the effective AC resistance of the conductor [ 3 , 20 , 36 ]. The combined action of eddy currents, hysteresis and the transformer effect raises the AC resistance R ac of the conductor above the DC value R dc at the same temperature. Higher values of the R ac /R dc ratio increase the energy losses in the conductor [20]. Since the cancellation of the axial component of the magnetic field is less effective in conductors with an odd number of aluminum layers, these conductors will exhibit higher resistance ratios R ac /R dc . The highest resistance ratio is expected in conductors with a single layer of aluminum, whereas the lowest corresponds to conductors with two layers [ 3 ]. The internal inductance of ACSR conductors increases with current up to a maximum value, Materials 2022,15, 6143 4 of 14 where the steel core becomes magnetically saturated [ 36 ], and then any further increase in current reduces the internal inductance [ 3 ] due to the decrease of the magnetic permeability. According to the international standard IEC 60287-1-1 [ 37 ], the AC resistance can be obtained from the DC resistance as: Rac =Rdc1+ys+yp[Ω/m](1) where y s and y p are, respectively, the skin and proximity effect factors. The effect of temperature is considered as: Rdc =R0[1+α20(T−20)] [Ω/m](2) where Tis the operating conductor temperature, R 0 the DC resistance measured at 20 ◦ C and α20 is the temperature coefficient at 20 ◦C. In most ACSR applications, the skin effect is negligible compared to the transformer effect, but in applications requiring low currents, large diameter conductors or high frequencies, this difference is reduced. The proximity effect is also negligible when distances between adjacent conductors greater than ten diameters are assumed [ 20 ]. Although (1) is simple to apply, it only applies to nonferromagnetic conductors up to 5 kV [ 37 ], and it does not consider important parameters such as those related to the stranding, including the direction and lay length, as it considers the stranded conductor to be a solid conductor [16,38]. The DC resistance of the conductor only depends on the temperature of the conductor, but the AC resistance also depends on the current [ 3 ]. According to [ 25 ], the AC resistance of an isothermal ACSR conductor increases with current following a sigmoidal change due to the change in magnetic field strength and the consequent increase in core losses. There is no explicit equation to determine the internal inductance of an ACSR conductor under DC supply. Several authors have proposed formulas for AC supply, although they are not exact, since it is difficult to model the complex behavior of the magnetic flux in the steel core. It is known that the per-unit length of the internal AC inductance of ACSR conductors also increases with current following a sigmoidal curve up to a maximum value corresponding to the magnetic saturation of the steel core, and then, any further current increases reduce the inductance [ 25 ]. The goodness of the electrical contacts between aluminum wires in the same layer and between wires in adjacent layers changes with the tension and degree of oxidation in the conductor. Also, conductors are not isothermal because they exhibit both radial and sometimes axial temperature gradients [ 3 ]. Therefore, due to the nonlinearity and complexity of these effects, the most effective way to determine the AC resistance and the internal reactance or inductance of stranded ACSR conductors is from experimental measurements. By measuring the instantaneous values of the voltage drop per unit length ∆ V, the electric current Iand the phase shift ϕ between them, it is possible to determine the per unit length values of the impedance [ 39 ], AC resistance R ac and reactance Xof the conductor expressed in Ω/m as [3,40]: Z=∆V I[Ω/m](3) Rac =∆V I·cos ϕ[Ω/m](4) X=∆V I·sin ϕ[Ω/m](5) The next equation describes the dependence of Rac with temperature: Rac,T=Rac,0[1+αac(T−T0)] [Ω/m](6) Materials 2022,15, 6143 5 of 14 where R ac,0 is the AC value of the resistance at a given temperature T 0 , usually 20 ◦ C, and αac is the temperature coefficient of the AC resistance. Note that R ac,0 is a measured value, which already includes the saturation effect, as proved in [19]. 2.2. Power Losses in ACSR Conductors Core losses take into account the effect of eddy currents and hysteresis in the steel core [ 3 ]. These losses, along with current redistribution and the effect of temperature, are key factors determining the AC resistance of ACSR conductors [ 41 ]. Eddy current and hysteresis losses increase with the square of the strength of the magnetic flux density and with increasing values of temperature for a constant strength of the magnetic field H. However, they tend to decrease as the resistivity of the steel core material increases, and thus, as the temperature rises [20]. According to [ 17 , 18 , 42 ], the losses due to Joule (P J ), core (P M ) and redistribution (P redis , transformer effect) effects can be expressed as follows: PJ+PM+Predis =I2Rac (7) Note that (7) is in agreement with the method for measuring power losses detailed in IEEE Std. 2772 [ 43 ] to measure the power loss of overhead conductors under real simulated laboratory conditions: Ploss =PJ+PM+Predis =∆VIcosϕ(8) 2.3. Transient Thermal Balance Equation for DLR Calculation The heat balance equation, which must always be satisfied, is the basis for implementing DLR approaches for ACSR conductors [ 18 ]. It states that the sum of the ohmic ( PJ+PM+Predis ) and solar heat gain must equal the heat loss by convection and radiation [44]. According to [ 12 ], the unsteady-state equation that describes the transient thermal balance of an ACSR conductor can be expressed as: PJ+PM+Predis +PS−PC−PR=mc dT dt [W/m](9) P J ,P M ,P redis and P S being the per unit length heat gain terms of the conductor (Joule, magnetic/core, transformer effect and solar heating terms, respectively, in W/m). P C and P R are the per unit length heat loss terms (convective and radiative loss terms, respectively, in W/m), mis the per unit length mass of the conductor in kg/m, cis the specific heat capacity of the conductor expressed in J/(kg ◦ C), Tis the average conductor temperature expressed in ◦ C, and tis the time in s. The heat capacity cof the ACSR conductor is calculated as the weighted average of the iron strands in the core and the aluminum strands, and can be expressed as: c(T) = mAlcAl,20◦C[1+βAl(T−20)] + msteelcsteel,20◦C[1+βsteel(T−20)] mAl,20◦C+msteel,20◦C [J/(kg◦C)] (10) where c x is the specific heat capacity of element x(Al = aluminum or steel), m x is its mass per unit length, and β is the temperature coefficient of the heat capacity, whose values can be found in [10]. According to [10,18], convective heat losses are calculated as: PC=π[0.042 +3.6·10−5(Ta+T)](T−Ta)Nu [W/m](11) where Nu is the Nusselt number, which can be calculated as detailed in [ 18 ] once the conductor diameter, surface roughness, local wind speed, local temperature, relative density and kinematic viscosity of the air are known. Materials 2022,15, 6143 6 of 14 The heat gain by solar radiation is obtained from the global solar radiation S(W/m 2 ) as [12]: PS=αsSD [W/m] (12) where D[m] is the outer conductor diameter and αs is the dimensionless solar absorptivity of the conductor surface, where its value is often assumed to be 0.5 [45]. Heat losses due to radiation are calculated as [12]: PR=πεDσB[(T+ 273)4−(Ta+ 273)4] [W/m] (13) where ε is the emissivity factor of the surface of the conductor (its value is often assumed to be 0.5 [2,45]) and σBis the Stefan-Boltzmann constant. The DLR ampacity I max is calculated at the maximum allowable temperature of the conductor, assuming that the temperature of the conductor is in thermal equilibrium, resulting in [10,46]: Imax =PC(Tmax) + PR(Tmax)−PS Rac(Tmax)1/2 [A](14) From (14), it is seen that the AC resistance plays a key role in determining the DLR ampacity, so an accurate estimate is required for this purpose. 3. Experimental Setup This section describes the experimental devices and materials used in the laboratory experiments, including the ACSR conductors, sensors and measuring devices required to determine the AC resistance of the studied conductors. 3.1. The Analyzed Single-, Two- and Three-Layer ACSR Conductors As explained in the introduction, ACSR conductors with one, two or three layers have different behaviors due to the interaction of the axial magnetic flux generated by the different layers of aluminum strands with the steel core, thus increasing the AC resistance of the conductor. Since the adjacent aluminum layers are stranded in opposite directions, the axial component of the resulting magnetic field is reduced. Therefore, this cancellation effect is greatest in two-layer ACSR conductors, while it is the least impactful in threelayer conductors, and not present at all in single-layer conductors. Due to the effect of the steel core, the AC resistance of the conductor is expected to depend not only on the temperature of the conductor but also on the intensity of the current flowing through the conductor. However, due to the partial cancellation of the axial component of the magnetic flux generated by layers of aluminum strands wound in opposite directions, the AC resistance of two-layer ACSR conductors should be almost independent of current intensity, while in the case of three-layer ACSR conductors, this dependency should be very low. It should be at the maximum in single-layer ACSR conductors. This work analyzes the behavior of the three-layer 550-AL1/71-ST1A ACSR conductor (HAASE Gesellschaft mbh, Graaz, Austria), and the two-layer 135-AL1/22-ST1A conductor (EMTA Kablo, Istanbul, Turkey), whose main parameters are summarized in Table 1. Next, a single-layer ACSR conductor was made from the 135-AL1/22-ST1A two-layer conductor by carefully removing the outer layer of aluminum strands. The three-layer conductor includes 7 steel strands that form the core, and three successive layers with 12, 18 and 24 aluminum strands, respectively, thus being 7/54. The two-layer conductor includes 7 steel strands in the core and two layers with 10 and 16 aluminum strands, respectively, being 7/26. The single-layer conductor is 7/10. Figure 2shows the geometry of the analyzed three-, two- and single-layer ACSR conductors. Materials 2022,15, 6143 7 of 14 Table 1. Main parameters of the three-layer 550-AL1/71-ST1A ACSR conductor from HAASE Gesellschaft and the two-layer 135-AL1/22-ST1A ACSR conductor from EMTA Kablo. Symbol Description Three-Layer Two-Layer Unit AAl Area of aluminum 549.7 134.9 mm2 Asteel Area of steel 71.3 22 mm2 NAl Number of aluminum wires 54 (12/18/24) 26 (10/16) - NSteel Number of steel wires 7 7 - DAl Aluminum wire diameter 3.6 2.57 mm Dsteel Steel wire diameter 3.6 2.0 mm DConductor diameter 32.4 16.3 mm mAL Mass per unit length of aluminum 1.5183 - kg/m msteel Mass per unit length of steel 0.5583 - kg/m R20◦CDC resistance of the conductor 0.0526 0.2038 Ω/km Imax Current carrying capacity 1020 430 A Materials 2022, 15, x FOR PEER REVIEW 7 of 15 Table 1. Main parameters of the three-layer 550-AL1/71-ST1A ACSR conductor from HAASE Gesellschaft and the two-layer 135-AL1/22-ST1A ACSR conductor from EMTA Kablo. Symbol Description Three-Layer Two-Layer Unit 𝐴  Area of aluminum 549.7 134.9 mm2 𝐴  Area of steel 71.3 22 mm2 𝑁 Number of aluminum wires 54 (12/18/24) 26 (10/16) - 𝑁 Number of steel wires 7 7 - 𝐷 Aluminum wire diameter 3.6 2.57 mm 𝐷 Steel wire diameter 3.6 2.0 mm D Conductor diameter 32.4 16.3 mm 𝑚 Mass per unit length of aluminum 1.5183 - kg/m 𝑚 Mass per unit length of steel 0.5583 - kg/m 𝑅 ° DC resistance of the conductor 0.0526 0.2038 Ω/km 𝐼 Current carrying capacity 1020 430 A Next, a single-layer ACSR conductor was made from the 135-AL1/22-ST1A two-layer conductor by carefully removing the outer layer of aluminum strands. The three-layer conductor includes 7 steel strands that form the core, and three successive layers with 12, 18 and 24 aluminum strands, respectively, thus being 7/54. The two-layer conductor includes 7 steel strands in the core and two layers with 10 and 16 aluminum strands, respectively, being 7/26. The single-layer conductor is 7/10. Figure 2 shows the geometry of the analyzed three-, two- and single-layer ACSR conductors. (a) (b) (c) Figure 2. Cross section of the analyzed ACSR conductors. (a) Single-layer 7/10 conductor. (b) Twolayers 7/26 conductor. (c) Three-layer 7/54 conductor. 3.2. The High-Current Transformer Used to Test the Conductors To determine the AC resistance of the conductors, they were tested in the laboratory under different operating conditions. For this end, a variable high-current transformer (10 kVA, 380 V/4 V, output current 0–2.5 kA, Transcir, Montcada i Reixac, Spain) was used to generate the current required to test the conductors. The analyzed ACSR conductors were connected to the high-current transformer forming a low impedance circular loop, as shown in Figure 3. To meet the requirements of the Cigré TB345 [3], the length of the conductor was 5.5 m. Figure 2. Cross section of the analyzed ACSR conductors. ( a ) Single-layer 7/10 conductor. ( b ) Twolayers 7/26 conductor. (c) Three-layer 7/54 conductor. 3.2. The High-Current Transformer Used to Test the Conductors To determine the AC resistance of the conductors, they were tested in the laboratory under different operating conditions. For this end, a variable high-current transformer (10 kVA, 380 V/4 V, output current 0–2.5 kA, Transcir, Montcada i Reixac, Spain) was used to generate the current required to test the conductors. The analyzed ACSR conductors were connected to the high-current transformer forming a low impedance circular loop, as shown in Figure 3. To meet the requirements of the CigréTB345 [ 3 ], the length of the conductor was 5.5 m. Materials 2022, 15, x FOR PEER REVIEW 8 of 15 Fan Conductor loop Rogowski coil High-current transformer Fan Thermocouple Figure 3. Experimental loop for testing the different ACSR conductors. It is known that wind speed has a stronger impact in terms of DLR rating than ambient temperature or solar radiation [9], so the effect of wind speed was studied in this paper. As shown in Figure 3, two SF 0147 fans (variable speed, 50 W, Orbegozo, Murcia, Spain) were used to simulate variable wind speed conditions. It should be noted that in the experiments, a constant wind flow of 5 m/s was applied, which was measured with a Pen 850021 anemometer (0.4–30 m/s measuring range, resolution of 0.1 m/s, accuracy of 3% full scale, Sper Scientific, Scottsdale, AZ, USA) during the entirety of the experiment under wind conditions. 3.3. Measuring Devices In experimental tests involving the loops of ACSR conductors, the current flowing in the loop, the voltage drop over one meter length of the conductor and the phase shift between the voltage drop and current was measured. The current flowing through the test loop was measured by means of a CWT500LFxB Rogowski coil (sensitivity = 0.06 mV/A, PEM, Nottingham, UK), which was connected to an NI USB-6210 data acquisition system (National Instruments, Dallas, TX, USA), with a current accuracy of ±1%. A T-type thermocouple was used to measure the surface temperature of the conductor. It was connected to a NI-9211 thermocouple input module (±1 °C, National Instruments, Dallas, TX, USA). Acquisitions made with the NI-9211 thermocouple input module and the NI USB- 6210 data acquisition system were synchronized using Python code programmed by the authors of this work. An 850021 RH Pen anemometer was used to measure the wind speed (measuring range 0.4–30 m/s, 0.1 m/s resolution, 3% full scale accuracy, Sper Scientific, Scottsdale, AZ, USA). 4. Experimental Results This section presents the experimental tests carried out with the three ACSR conductors described in Section 3, which were performed in the AMBER high-current laboratory facilities of the of the Universitat Politècnica de Catalunya. 4.1. Results Obtained with a Single-Layer ACSR Conductor The first test was conducted with a single-layer conductor, whose rated current was about 220 A. The conductor was heated from room temperature by applying the rated current until reaching the equilibrium temperature, which was about 77 °C. Conventional Figure 3. Experimental loop for testing the different ACSR conductors. It is known that wind speed has a stronger impact in terms of DLR rating than ambient temperature or solar radiation [ 9 ], so the effect of wind speed was studied in this paper. As shown in Figure 3, two SF 0147 fans (variable speed, 50 W, Orbegozo, Murcia, Spain) were used to simulate variable wind speed conditions. It should be noted that in the Materials 2022,15, 6143 8 of 14 experiments, a constant wind flow of 5 m/s was applied, which was measured with a Pen 850021 anemometer (0.4–30 m/s measuring range, resolution of 0.1 m/s, accuracy of 3% full scale, Sper Scientific, Scottsdale, AZ, USA) during the entirety of the experiment under wind conditions. 3.3. Measuring Devices In experimental tests involving the loops of ACSR conductors, the current flowing in the loop, the voltage drop over one meter length of the conductor and the phase shift between the voltage drop and current was measured. The current flowing through the test loop was measured by means of a CWT500LFxB Rogowski coil (sensitivity = 0.06 mV/A, PEM, Nottingham, UK), which was connected to an NI USB-6210 data acquisition system (National Instruments, Dallas, TX, USA), with a current accuracy of ±1%. A T-type thermocouple was used to measure the surface temperature of the conductor. It was connected to a NI-9211 thermocouple input module ( ± 1 ◦ C, National Instruments, Dallas, TX, USA). Acquisitions made with the NI-9211 thermocouple input module and the NI USB-6210 data acquisition system were synchronized using Python code programmed by the authors of this work. An 850021 RH Pen anemometer was used to measure the wind speed (measuring range 0.4–30 m/s, 0.1 m/s resolution, 3% full scale accuracy, Sper Scientific, Scottsdale, AZ, USA). 4. Experimental Results This section presents the experimental tests carried out with the three ACSR conductors described in Section 3, which were performed in the AMBER high-current laboratory facilities of the of the Universitat Politècnica de Catalunya. 4.1. Results Obtained with a Single-Layer ACSR Conductor The first test was conducted with a single-layer conductor, whose rated current was about 220 A. The conductor was heated from room temperature by applying the rated current until reaching the equilibrium temperature, which was about 77 ◦ C. Conventional ACSR conductors usually operate below 90 ◦ C [ 24 ] except when operating under emergency contingency conditions [19]. Then, by forcing it to pass the same amount of current, the conductor was cooled with the help of fans. During both parts of this cycle, the temperature of the conductor, the voltage drop and the current through the conductor were measured. From these measurements, the phase shift between the voltage drop and the current was calculated, and the AC resistance was obtained from (4). This test was repeated with currents of 145 A and 75 A. Figure 4shows the results of the AC resistance as a function of the conductor temperature. Results presented in Figure 4clearly show the effect of the core on the AC resistance of the single-layer ACSR conductor. These results proved that the AC resistance of a singlelayer ACSR conductor depended not only on temperature but also on the current flowing through the conductor. Results in Figure 4also show that, in the case of strong wind, the measured surface temperature differs more from that of the interior. Therefore, for a given conductor surface temperature, the apparent AC resistance measured in strong wind is higher than when measured in no wind because of the higher temperature difference between the interior and the surface of the conductor in strong wind conditions (increased radial temperature gradient). However, this difference is always below 5%. 4.2. Results Obtained with a Two-Layer ACSR Conductor The second test was carried out with a two-layer conductor, whose rated current was about 430 A. Due to the opposite stranding directions of the two layers, the axial Materials 2022,15, 6143 9 of 14 component of the magnetic flux is almost cancelled. Therefore, the AC resistance must be almost independent of the current intensity because the ferrous core is almost unaffected by the magnetic flux generated by the aluminum layers. Materials 2022, 15, x FOR PEER REVIEW 9 of 15 ACSR conductors usually operate below 90 °C [24] except when operating under emergency contingency conditions [19]. Then, by forcing it to pass the same amount of current, the conductor was cooled with the help of fans. During both parts of this cycle, the temperature of the conductor, the voltage drop and the current through the conductor were measured. From these measurements, the phase shift between the voltage drop and the current was calculated, and the AC resistance was obtained from (4). This test was repeated with currents of 145 A and 75 A. Figure 4 shows the results of the AC resistance as a function of the conductor temperature. Results presented in Figure 4 clearly show the effect of the core on the AC resistance of the single-layer ACSR conductor. These results proved that the AC resistance of a single-layer ACSR conductor depended not only on temperature but also on the current flowing through the conductor. Results in Figure 4 also show that, in the case of strong wind, the measured surface temperature differs more from that of the interior. Therefore, for a given conductor surface temperature, the apparent AC resistance measured in strong wind is higher than when measured in no wind because of the higher temperature difference between the interior and the surface of the conductor in strong wind conditions (increased radial temperature gradient). However, this difference is always below 5%. Single-layer ACSR conductor Temperature (ºC) 20 30 40 50 60 70 80 Resistance (micro-Ohm) 500 550 600 650 700 750 800 220 A no fan 220 A with fan 145 A no fan 145 A with fan 75 A no fan 75 A with fan 220 A 145 A 75 A Heat i ng at 220 A wi t h no fan appl i ed Cool i ng at 220 A due to the fan Figure 4. Single-layer ACSR conductor. Rac versus temperature measured for heating-cooling cycles at 220 A, 145 A and 75 A. 4.2. Results Obtained with a Two-Layer ACSR Conductor The second test was carried out with a two-layer conductor, whose rated current was about 430 A. Due to the opposite stranding directions of the two layers, the axial component of the magnetic flux is almost cancelled. Therefore, the AC resistance must be almost independent of the current intensity because the ferrous core is almost unaffected by the magnetic flux generated by the aluminum layers. As in the previous case, the conductor was heated by applying the rated current until reaching the equilibrium temperature, which was about 77 °C. Then, once again, by forcing it to pass the same amount of current, the conductor was cooled using fans. During the course of the experiment, the conductor temperature, voltage drop and current were measured, so that the AC resistance was calculated from (4). This test was repeated with currents of 280 A and 130 A, where the results of the AC resistance versus the temperature of the conductor are displayed in Figure 5. Figure 4. Single-layer ACSR conductor. R ac versus temperature measured for heating-cooling cycles at 220 A, 145 A and 75 A. As in the previous case, the conductor was heated by applying the rated current until reaching the equilibrium temperature, which was about 77 ◦ C. Then, once again, by forcing it to pass the same amount of current, the conductor was cooled using fans. During the course of the experiment, the conductor temperature, voltage drop and current were measured, so that the AC resistance was calculated from (4). This test was repeated with currents of 280 A and 130 A, where the results of the AC resistance versus the temperature of the conductor are displayed in Figure 5. Materials 2022, 15, x FOR PEER REVIEW 10 of 15 Two-layer ACSR conductor Temperature (ºC) 20 30 40 50 60 70 80 Resistance (micro-Ohm) 200 210 220 230 240 250 260 430 A no fan 430 A with fan 280 A no fan 280 A with fan 130 A no fan 130 A with fan 430 A 280 A 130 A Heat i ng at 430 A wi t h no fan appl i ed Cool i ng at 430 A due t o t he fan Figure 5. Two-layer ACSR conductor. Rac versus temperature measured for heating-cooling cycles at 430 A, 280 A and 130 A. From Figure 5, it can be seen that, as expected, the AC resistance of the two-layer ACSR conductor depended on its temperature, but it was almost independent of the current level. The effect of a strong wind increased the Rac value below 5%. 4.3. Results Obtained with a Three-Layer ACSR Conductor The third test was carried out with a three-layer conductor, whose rated current was around 1080 A. Due to the odd number of layers, the axial component of the magnetic flux does not completely cancel. Therefore, the AC resistance must depend slightly on the current intensity because the iron core is somewhat influenced by the axial component of the magnetic flux generated by the aluminum layers. The three-layer ACSR conductor was heated by applying the rated current until the equilibrium temperature was reached, which was about 85 °C. Next, by forcing the flow of the same amount of current, the conductor was cooled using fans. During the experiment, the temperature of the conductor, the voltage drop and the current were measured, so that the AC resistance was obtained from (4). The test was repeated twice with current intensities of 650 A and 310 A, respectively. Figure 6 shows the results of the AC resistance versus conductor temperature. Figure 5. Two-layer ACSR conductor. R ac versus temperature measured for heating-cooling cycles at 430 A, 280 A and 130 A.