Full text
JOURNAL OF L A T EX CLASS FILES, VOL. 14, NO. 8, AUGUST 2015 1 Enabling Grid-Feeding Converters with a Dissonant-Resonant Controller for Negative-Sequence Voltage Elimination Manel Velasco, Pau Mart´ı, Antonio Camacho, Juan M. Rey, Jaume Miret, Member, IEEE, and Miguel Castilla Abstract—The mitigation of the adverse effects of voltage unbalance in equipment and power quality can be performed by the power electronic converters that interface distributed generators to the grid. Inspired in a resonant controller, this paper presents a dissonant-resonant controller for negative-sequence voltage elimination for a grid-feeding converter connected to the grid. The controller eliminates the negative-sequence voltage at the converter output with a regulable precision, it does not require knowing the grid impedance for successful operation, and it can be a good candidate for parallel operation because it operates not like an integrator, but like an ”untuned” integrator. Using the stationary αβ frame, a closed-loop model is developed in a complex space vector built from the complexification of the stationary components. This allows extracting stability conditions for safe closed-loop operation as well as deriving design guidelines for the controller parameters. Numerical and experimental results show the ability of the proposed controller to meet its design goals, thus corroborating the theoretical approach. Index Terms—Grid-feeding converter, αβ components, negative-sequence, resonant controller I. INTRODUCTION One of the most common phenomena in power systems is voltage unbalance. Its elimination is motivated by the adverse effects on equipment and power quality, such as electrical machine overheating, transformer overloading, capacity limitation of power electronics, more losses and less stability of power system, and negative impacts on induction motors and adjustable speed drives [1], [2]. The voltage unbalanced concerns trigger also new regulations in grid codes. Although the definition and regulation of voltage unbalance differs among standardization organizations and local regulators, for example, the standard EN 50160 indicates that the voltage unbalance factor must be less than 2% for low and medium voltage systems [3]. Therefore, control techniques to compensate the unbalance must be developed. Electronic converters interfacing dis- M. Velasco, P. Mart´ı and A. Camacho are with the Automatic Control Department, Technical University of Catalonia, Pau Gargallo 5, 08028 Barcelona, Spain, email: {manel.velasco,pau.marti,antonio.camacho.santiago}@upc.edu J.M. Rey is with Escuela de Ingenier´ıas El´ectrica, Electr´onica y de Telecomunicaciones (E3T), Universidad Industrial de Santander (UIS), 680002 Bucaramanga, Colombia, and with the Electronic Engineering Department, Technical University of Catalonia, Av. Victor Balaguer s/n, 08800 Vilanova i la Geltr´u, Spain, email:juanmre[email protected] J. Miret and M. Castilla are with the Electronic Engineering Department, Technical University of Catalonia, Av. Victor Balaguer s/n, 08800 Vilanova i la Geltr´u, Spain, email:{jaume.miret,miquel.castilla}@upc.edu This work was supported by the Ministry of Science, Innovation and Universities of Spain and by the European Regional Development Fund under project RTI2018-100732-B-C22. tributed generation units (DGs) in grid-feeding, grid-forming, or grid-supporting configurations [4] can be considered a promising solution in front of other strategies that require installing additional equipments such as series or shunt active power filter, series-parallel compensators, static synchronous compensators, and energy storage units [5]–[7]. Research regarding grid-connected converters under unbalanced grid voltage has been largely treated, see e.g. [8]–[28]. Most of the control proposals serve diverse control objectives (mitigation of the unbalance, voltage-ride through, mitigation of voltage fluctuations, elimination of harmonics, elimination of dc link current ripples, etc) while considering different type of grid impedances. However none of them is devoted only at eliminating the negative-sequence voltage that the grid unbalance generates with independence of the specific grid impedance. Limiting the scope to grid-feeding converters, this paper presents a control strategy that targets negative-sequence voltage elimination at the inverter output where a local load is connected. The voltage unbalance is assumed to be generated by the main grid. This assumption permits focusing only on the negative-sequence controller because both the negativesequence controller and the positive-sequence controller (in charge of delivering the active power to the grid, among other tasks) are decoupled in terms of steady-state dynamics. The development of an appropriate control algorithm is challenging since existing control algorithms may not be directly applicable if parallelization is desired. Note that these power converters already operate in parallel with other grid-feeding power converters in grid-connected mode. While the proportional-integral (PI) controller guarantees zero steady-state error for DC references, for AC references unavoidable steady-state amplitude and phase errors occur because it does not comply with the internal model principle [29]. Complementary, resonant (R) controllers [30] become a promising alternative because they have been developed upon the internal model principle [31], and they have been applied in many forms and scenarios in power generation systems [32]–[34]. Motivated by these advantages, R controllers are chosen as a baseline control approach to eliminate the negative-sequence voltage. Moreover, they are generalized into a new form called dissonant-resonant (DR) controllers in order to provide a richer set of performance features. The DR controller is defined in the αβ stationary reference frame, which implies that grid voltages are transformed to the αβ components and then, by
JOURNAL OF L A T EX CLASS FILES, VOL. 14, NO. 8, AUGUST 2015 2 ia v1 RLLLvga ib v2 RLLLvgb ic v3 RLLLvgc RR R Fig. 1. Scheme of the grid-feeding converter (modeled as a three-phase current source) with a local load and connected to the grid through an RL line. means of a sequence extractor, into symmetric sequences for negative-sequence voltage elimination. See [35]–[38] for the foundations, review and implemetation details of sequence extractors. This paper uses the second order generalized integrator (SOGI) [36], [37] as a sequence extractor. The constructive idea behind the DR controller is to obtain an untuned integrator through a generalization of a R controller. The untuned feature is included to avoid undesirable properties that otherwise may appear when multiple integrators are operated in parallel, such as destabilizing effects or reaching undesirable equilibria [39], [40]. Intuitively, in the Laplace domain, an untuned integral controller for DC references could be understood as a low-pass filter with an adjustable pole that can be made as close to zero as desired. For AC references, the generalization of the R controller is achieved by adding an additional frequency to the natural frequency to alter the rotation frequency, creating a dissonant effect. The design of the additional frequency permits increasing the set of desired transient dynamics for the closed-loop system with respect to those that can be achieved by a standard R controller. The paper also presents the stability analysis and controller design guidelines for the DR controller. A closedloop model is presented in the αβ frame using a complex space vector built from the complexification [41] of the αβ negative-sequence components. The presented DR controller has been experimentally tested in a laboratory set-up and its performance results corroborate its effectiveness. The rest of this paper is structured as follows. Section II presents the problem to be solved. Section III presents the controller. Section IV presents the stability analysis and provides controller design guidelines. Section V summarizes the experimental results and Section VI concludes the paper. II. PROBLEM DEFINITION A. Plant Model The considered three-phase plant is illustrated in Fig. 1. Without loss of generality, it is assumed that the unbalance occurs at the grid side, and Ris a sensitive local load that requires balanced voltages. Therefore, the output voltages v1, v2and v3of the grid-feeding converter must be balanced. By using the modified nodal analysis, the plant can be compactly described by #» v1,2,3=G(s)#» ia,b,c +W(s)# » vga,b,c (1) whose detail is given by v1(s) v2(s) v3(s) = G11(s)G12(s)G13(s) G21(s)G22(s)G23(s) G31(s)G32(s)G33(s) ia(s) ib(s) ic(s) + W11(s)W12(s)W13(s) W21(s)W22(s)W23(s) W31(s)W32(s)W33(s) vga(s) vgb(s) vgc(s) . (2) Matrices G(s)and W(s)in (1), where sis the Laplace operator, are symmetric with diagonal and off-diagonal transfer functions, Gii(s)and Gij (s)or Wii(s)and Wij(s), given by Gii(s) = LL2s2+ (2LLRL+ 3RLL)s+RL2+ 3RRL 3LLs+ 3R+ 3RL (3) Gij (s) = LL2s2+ 2LLRLs+RL2 3LLs+ 3R+ 3RL (4) Wii(s) = LLs+RL+ 3R 3LLs+ 3R+ 3RL (5) Wij (s) = LLs+RL 3LLs+ 3R+ 3RL .(6) The grid voltages and currents are transformed into the αβ frame. This is done by applying the αβ tranformation #» xa,b,c = xa xb xc = 1 0 1 −1 2 √3 21 −1 2−√3 21 xα xβ xγ =T#» xα,β,γ (7) where xistands for either current or voltage in the given frame. By applying the transformation (7) to the model given in (1), the following plant expression is obtained #» vα,β,γ =T−1G(s)T#» iα,β,γ +T−1W(s)T# » vgα,β,γ =Gα,β,γ(s)#» iα,β,γ +Wα,β,γ(s)# » vgα,β,γ (8) whose detail is given by vα(s) vβ(s) vγ(s) = Gαα(s) 0 0 0Gββ(s) 0 0 0 Gγγ(s) iα(s) iβ(s) iγ(s) + Wαα(s) 0 0 0Wββ(s) 0 0 0 Wγγ(s) vgα(s) vgβ(s) vgγ(s) (9) where Gαα(s) = Gββ(s) = RLLs+RRL LLs+R+RL , Gγγ(s) = RL+LLs Wαα(s) = Wββ(s) = R LLs+R+RL , Wγγ(s) = 1. (10) It is interesting to observe that the αβ plant model (8)-(10) is decoupled (diagonal) and each voltage can be controlled individually. At this point, the modeling effort makes use of the property that complex numbers Ccan be represented by particular real matrices in R2x2[41] as follows a+jb ↔a−b b a (11) where a, b ∈Rand j=√−1, and under which addition and multiplication of complex numbers and matrices correspond to
JOURNAL OF L A T EX CLASS FILES, VOL. 14, NO. 8, AUGUST 2015 3 Fig. 2. Open-loop system. each other. Then, looking at the plant model (8)-(10), it can be observed that the first two diagonal elements of Gα,β,γ, Gαα(s)and Gββ(s), are equal, and that the corresponding offdiagonal elements Gαβ and Gβα are equal and with opposite sign. Hence, the αβ 2×2subsystem of Gα,β,γ satisfies the complexification property (11). A similar observation can be made for the αβ 2×2subsystem of Wα,β,γ in (8)-(10). Therefore, after application of (11) to the αβ 2×2subsystems, the plant model (8)-(10) can be written as vα+jβ =RLLs+RRL LLs+R+RL iα+jβ +R LLs+R+RL vgα+jβ . (12) It is important to note that since the load Ris balanced, the plant model given in (12) also holds for both the symmetric components of the currents and voltages. Hence, the negativesequence of (12) can be written as v− α+jβ =RLLs+RRL LLs+R+RL i− α+jβ +R LLs+R+RL vg− α+jβ =G−(s)i− α+jβ +W−(s)vg− α+jβ (13) that provides a compact representation of the open-loop plant model, which can be represented in terms of block diagrams as in Fig. 2. The plant model (13) is a linear model with complex input and output variables. The plant input is the negativesequence current i− α+jβ , the plant output is the negativesequence voltage v− α+jβ , and the unbalance grid negativesequence voltage vg− α+jβ is viewed as a perturbation. B. Problem Formulation Given the plant model (13), the problem to be solved is to find the appropriate negative-sequence current i− α+jβ that eliminates the negative-sequence voltage, that is, such that v− α+jβ = 0. It is important to note that v− α+jβ ∈C, which means that it has a modulus |·|and a phase θ(·). Hence, to achieve v− α+jβ = 0 means to have |v− α+jβ |= 0 while θ(v− α+jβ ) in this particular case is not defined. C. Problem Feasibility By taking (13), making v− α+jβ = 0, and isolating i− α+jβ , the following expression is obtained i− α+jβ =1 LLs+RL vg− α+jβ (14) which is a differential equation whose solution indicates that it does exist a current that eliminates the negative-sequence Fig. 3. Closed-loop system. voltage. Therefore, the problem can be solved, but it would require a measure of the grid impedance (RLand LL), and a measure of the unbalanced voltage vg− α+jβ . However, none of these measures is available. Instead, the converter output voltages v1,2,3will be measured, then transformed into the αβ stationary frame components, and then further transformed into the symmetric components via a SOGI. And only the complexificated negative-sequence component v− α+jβ will be used for the control purposes. Schematically, the closed-loop configuration is given in Fig. 3, where the goal is to design the control C(s)where the reference input is the negative-sequence voltage that is zero, (v− α+jβ )∗= 0, and the sensor transfer function H(s) corresponds to the SOGI. III. CONTROL PROPOSAL This section presents the new dissonant-resonant (DR) controller and establishes a comprehensive relation between the DR controller and a ”untuned” standard resonant (R) controller in the αβ frame. In addition, the stability analysis of the closed-loop system is provided, together with the controller design guidelines. A. Dissonant-Resonant (DR) Controller In order to solve the problem formulated in sub-section II-B, the following dissonant-resonant (DR) controller is proposed i− α+jβ =ke−jω0tZejωdt|(v− α+jβ )∗|−|v− α+jβ |dt(15) where ω0is the grid frequency given by the SOGI-FLL (frequency locked loop) [37], and the integral gain k∈C and the dissonant frequency ωdare the control parameters. B. From a R Controller to a DR Controller A standard R controller in the stationary reference frame for the negative-sequence is given by [32] i− α(s) i− β(s)= Ks s2+ω2 0 Kω0 s2+ω2 0 −Kω0 s2+ω2 0 Ks s2+ω2 0!ε− α(s) ε− β(s)(16) where K∈Ris the integral gain, and ε− α(s)and ε− β(s)are the voltage errors given by ε− α(s) = (v− α(s))∗−v− α(s), ε− β(s) = (v− β(s))∗−v− β(s).(17)
JOURNAL OF L A T EX CLASS FILES, VOL. 14, NO. 8, AUGUST 2015 4 By noting that the complexification property (11) can be applied to (16), the R controller can also be written as i− α+jβ =Ks s2+ω2 0−jKω0 s2+ω2 0ε− α+jβ (18) which can be further rearranged as follows i− α+jβ =Ks −jKω0 s2+ω2 0 ε− α+jβ =K s+jω0 ε− α+jβ .(19) Note that the transfer function in (19) is a synchronous integrator in negative-sequence [42] in the αβ frame. By applying the Laplace transform and related properties to (19), the following differential equation is obtained di− α+jβ dt+jω0i− α+jβ =Kε− α+jβ.(20) By assuming zero initial conditions, the solution of (20) is i− α+jβ =Ke−jω0tZejω0tε− α+jβ dt(21) which is a complexificated R controller in the αβ frame. In order to avoid a ”pure” integrator, controller (21) is modified adding a dissonant frequency ωdto the system frequency ω0 of the exponential inside of the integral (future work will study the effect of this modification in the frequency of the exponential outside of the integral), which leads to i− α+jβ =Ke−jω0tZej(ω0+ωd)tε− α+jβ dt. (22) The modification included in (22) can be explained as follows. Looking at (21), the negative-sequence voltage error ε− α+jβ rotates at frequency −ω0(for being the negative component). Hence, by multiplying it inside the integral by ejω0thas the effect of cancelling the rotation. Then integration takes places, and the multiplication by the outside term e−jω0t makes the obtained negative-sequence current to rotate again at frequency −ω0. The inclusion of the dissonant frequency ωd in (22) does not permit a perfect cancellation of the frequency rotation of the negative-sequence voltage error ε− α+jβ , thus leading to a dissonant integrator. By using the polar notation of the αβ negative-sequence errors given in (17), the complexificated voltage error negativesequence ε− α+jβ can be written as ε− α+jβ = (v− α+jβ )∗−v− α+jβ =|(v− α+jβ )∗|e−j(ω0t−ϕ)−|v− α+jβ |e−j(ω0t−ϕ′)(23) where ϕand ϕ′are initial phases. Then, substituting (23) into (22), simplifying ω0wherever possible, and removing the common factor ejϕ′ , the following expression is obtained i− α+jβ =ke−jω0tZejωdt|(v− α+jβ )∗|ej(ϕ−ϕ′)−|v− α+jβ |dt (24) with k=ejϕ′K. (25) Note that the term |(v− α+jβ )∗|ej(ϕ−ϕ′)in (24) can be considered as a new negative-sequence voltage reference. Hence, making an abuse of notation, it could be re-defined as |(v− α+jβ )∗|,|(v− α+jβ )∗|ej(ϕ−ϕ′).(26) Using (26) and (25) in (24), the DR controller (15) is obtained. C. DR Controller Properties From the definition of the DR controller (15) and its relation to a standard R controller given in the previous subsection, the following properties can be highlighted. First, the gain (25) depends on the initial condition because of its dependency on the initial phase ϕ′in ejϕ′. In fact, this term has a modulus equal to 1, that is, it does not change the value of K, but points towards an undetermined direction, which creates uncertainty that may impact the closed-loop dynamic behavior. To overcome the problem that may arise for achieving repetitive experiments, the controller is activated when ϕ′= 0. Second, when the dissonant frequency is ωd= 0, the DR controller (15) operates like a standard R controller, as it can be observed in (22). Therefore it can be considered a generalization of the R controller which is an integral controller of the negative-sequence voltage error in modulus, rotated at frequency −ω0. Third, looking at the control parameters of the DR controller, the integral gain kcan be used to boost performance and it is related to the final error. And the dissonant frequency ωdaffects the rotation frequency, thus providing a smooth transition from a proportional to an integral controller in terms of logical operation. IV. STABILITY ANALYSIS The plant transfer functions G−(s)and W−(s)in Fig. 3 are given in (13), the controller C(s)is the DR controller (15), and the sensor H(s)is the SOGI whose model characterized by a damping factor ξin complexificated form is [43] H(s) = ξω0s−jξω2 0 s2+ξω0s+ω2 0 .(27) Therefore, the stability analysis of the closed loop model illustrated in Fig. 3 can be performed using the closed-loop transfer function given by GCL(s) = G(s)C(s) [1 + H(s)G(s)C(s)]−1(28) where the minus subscript of G−(s)has been removed, the input and output are (v− α+jβ )∗and v− α+jβ , respectively, and the controller transfer function C(s)is computed next. A. Controller Transfer Function The transfer function is obtained as follows. First, by using again the polar notation, the modulus of the negative-sequence voltage v− α+jβ can be written as |v− α+jβ |=ej(ω0t+ϕ)v− α+jβ (29) By using (29), the DR controller (15) can be expressed as i− α+jβ =ke−jω0tZejωdth|(v− α+jβ )∗|−ej(ω0t+ϕ)v− α+jβ idt (30) By removing the common factor ejϕ in (30) and performing some calculations, the DR controller is written as i− α+jβ =kejϕe−jω0tZejωdtejω0th¯v∗−v− α+jβ idt (31)
JOURNAL OF L A T EX CLASS FILES, VOL. 14, NO. 8, AUGUST 2015 5 where ¯v∗=e−jω0t−jϕ |(v− α+jβ )∗|(32) becomes the new reference input but it does not affect the stability analysis. Note also that similar than the gain given in (25), the gain kin (31) is multiplied by ejϕ. Hence, for each given kvalue, the initial direction ϕwill determine performance and the shape of the stability region. In order to obtain the Laplace transform of (31), the derivative of (31) is performed to obtain di− α+jβ dt=−jω0kejϕe−jω0tZejωdtejω0th¯v∗−v− α+jβ idt |{z } i− α+jβ +kejϕejωdth¯v∗−v− α+jβ i =−jω0i− α+jβ +kejϕejωdth¯v∗−v− α+jβ i(33) which can then be easily transformed into sI− α+jβ (s) = −jω0I− α+jβ (s) + kejϕE(s−jωd)(34) where the error E(s−jωd)has been obtained using the frequency shifting property of the Laplace transform given by L{eatx(t)}=X(s−a).(35) The controller transfer function can not be still obtained from (34) because the input E(·)and the output I− α+jβ (·)have different arguments, s−jωdand s, respectively. This problem is solved applying the shift operator [44] given by x(t+a) = ead dt x(t)(36) Therefore, the application of (36) to the controller equation (34) leads to sI− α+jβ (s) = −jω0I− α+jβ (s) + kejϕe−jωdd ds E(s)(37) which can be further written as C(s) = I− α+jβ (s) E(s)= (s+jω0)−1kejϕe−jωdd ds =¯ C(s)e−jωdd ds (38) B. Stability Condition and Controller Design Guidelines At this point the closed loop transfer function in (28) can be constructed because transfer functions of the plant (13), SOGI (27) and controller (38) are available, while reminding that the new reference input is ¯v∗(s)defined in the time domain in (32) and the output is V− α+jβ (s). By applying the push through rule to (28) it is obtained GCL(s) = [1 + G(s)C(s)H(s)]−1G(s)C(s)(39) which is nonlinear due to the non-linear expression of the controller C(s)(38) caused by the presence of the d ds operator. By applying the small gain theorem [45], the closed loop system (39) will be stable if G(s)¯ C(s)H(s−jωd)e−jωdd ds ∞ <1(40) 0 200 400 600 800 d (rad/s) 1000 2000 3000 4000 5000 6000 kmax Fig. 4. Values of kmax as a function of ωd. holds, where k·k∞denotes the infinite norm and the controller C(s)has been replaced by he expression given in (38). By using the sub-multiplicative property of the norm, condition (40) can be written as G(s)¯ C(s)H(s−jωd)e−jωdd ds ∞ ≤ G(s)¯ C(s)H(s−jωd) ∞ e−jωdd ds ∞ <1 (41) By noting that the norm of the shift operator is 1, the stability condition (41) simplifies to G(s)¯ C(s)H(s−jωd) ∞<1(42) By replacing in the stability condition (42) the transfer functions of the plant (13), SOGI (27) and controller (38), a relation is stablished between the dissonant frequency and the controller gain in terms of stability. In particular, for a given dissonant frequency ωdand by solving the inequality (42), an upper bound for the modulus of the controller gain k, namely kmax, is obtained. For example, by taking one of the values for the dissonant frequency that is used in the experiments presented in next section, ωd= 174 rad/s, the inequality (42) becomes the expression given in (43), whose solution for kprovides a value kmax ≃3000. Fig. 4 shows the kmax/ωddependency by varying the dissonant frequency from ωd= 0 to ωd= 2ω0, being ω0= 2π60. It is important to note that stability is determined by the modulus of k. However, the shape of the system response is determined by its angle, which is given by the relation of its real and imaginary part. V. EXPERIMENTAL RESULTS The proposed control strategy has been tested in the laboratory set-up given in Fig. 5 where six grid-feeding converters operate in a grid-connected AC microgrid. Two scenarios are considered. First, the basic scenario that mimics the scheme shown in Fig. 1 where a single grid-feeding converter, G1 in Fig. 5, enabled with the DR controller is connected to an unbalanced grid while supplies the local load L1. In this basic scenario, the rest of converters (G2to G6) of Fig. 5 are disabled. And second, the parallel scenario where the six grid-feeding converters connected to an unbalanced grid are also enabled with DR controllers. Each grid-feeding converter is implemented using a Guasch three-phase inverter with a damped LC-filter and a DY transformer. The input of the
JOURNAL OF L A T EX CLASS FILES, VOL. 14, NO. 8, AUGUST 2015 6 G(s)¯ C(s)H(s−jωd) ∞= −k(LLRs +R RL)ξω2 0j−ξω0(s−ωdj) (LLs+ (R+RL)) (s+ωdj)(s−ωdj)2+ω2 0+ξω0(s−ωdj) ∞ <1(43) Fig. 5. Plant scheme for parallel operation. TABLE I NOMINAL VALUES OF THE SYSTEM SET-UP. Description symbol nominal value nominal power Sn3.5kVA DC-link voltage 400 V grid voltage vg 155 V(l-n, peak) grid frequency ω02π60 rad/s grid inductance LL4.6mH grid resistance RL0.5 Ω LC filter inductances 5mH LC filter capacitances 1.5µF LC filter damping resistors 68 Ω T1and T2power rating 10 kVA T3,T4and T5power rating 5kVA T6power rating 3kVA T1and T2equivalent impedance 0.5 + 3.7jΩ T3,T4and T5equivalent impedance 1.13 + 2.2jΩ T6equivalent impedance 1.95 + 6.77jΩ nominal local load R24 Ω switching frequency 10 kHz SOGI damping factor ξ0.707 converter is supplied by an Amrel DC power source. The grid is emulated by a Pacific Power AC power source with a grid impedance emulated using discrete RL impedances. For the basic scenario, the setup is configured to have the single converter G1injecting 600 W of active power. The main setup parameters are listed in Table I such as the components of the six LC filters, which are all equal, and the characteristics of the six DY transformers that interface each converter in Fig. 5. In Table I transformers are named as Ti,i= 1,...,6, and they are not all equal, which permits configuring different types of connections. It is important to note that for both basic and parallel scenarios being analyzed, the impedance value is abnormally high. This unrealistic weak characterization has been chosen on purpose to maximize the problem to be solved, which also permits observing the performance of the DR controller in a more accurate way. The operation of the proposal has been also successfully verified in more conventional grid conditions. Note also that although the grid impedance has a given value, the DR controller does not need to know it for successfully achieving the control goal. The DR controller is implemented on a Texas Instruments F28M36 digital signal processor. The sequence extractor and the internal controllers for the current loop are based on SOGI-FLLs. The current loop also includes a space vector modulator to compute the switching times of each converter branch. Phase voltages and currents are measured and exported to Matlab. In the experiments, at time t= 0 s the grid is unbalanced, and the amplitude of the G1negative-sequence voltage is 5V, which gives an unbalance factor of 3.2%, thus being above of the recommended limit of 2% given by the EN 50160 standard. Then, for the basic scenario, the DR controller is activated at time t= 0.2s. A. Main Result Fig. 6 shows the performance and main actors of the proposed controller for negative-sequence voltage elimination for the basic scenario. Sub-fig. 6a shows the modulus of negative-sequence voltage |v− α+jβ |that starts with an initial value near 5V, and after applying the DR controller at time t= 0.2s, it starts to decrease towards zero, meeting the control goal that motivated its development. In this experiment, the control parameters are specified to be the gain kwith Im{k}= 0 and Re{k}= 1400 (and therefore initial phase ϕ′= 0) with a dissonant frequency ωd= 174 rad/s, which are appropriate settings according to the design guidelines given in the previous section because the stability limit for this frequency was with kmax ≃3000. In addition, the real and imaginary part of the controller gain kare illustrated using an arrow representing a vector in a real-imaginary circle also plotted in the Sub-fig. Fig. 6 shows also other signals of interest. Voltages va,b,c are not shown because the unbalance is difficult to be observed. Instead, αβ negative-sequence voltage v− αand v− β(Subfig. 6b), and currents ia,b,c (Sub-fig. 6c) are displayed. To better illustrate the results, two zoom-in views of the currents ia,b,c are also presented in Sub-fig. 6d and 6e that correspond to the initial and final part of the experiment, respectively plotted with different x-axis. Sub-fig. 6d shows the currents ia,b,c when the voltage unbalance is present and not action is taken to remove it (from time t= 0.1s to t= 0.16 s), which implies currents perfectly balanced. Alternatively, Sub-fig. 6e shows the currents ia,b,c after 1s when voltages have already been balanced by the unbalance of the currents achieved by the action of the controller (from time t= 1.1s to t= 1.16 s). The unbalanced currents achieve balance in voltages by eliminating the negative-sequence voltage. Fig. 7 complements Fig. 6 by illustrating the existing decoupling in steady-state dynamics for both positive and negative-sequence controllers while showing their coupling in the transient. In particular, Fig. 7 shows the performance
JOURNAL OF L A T EX CLASS FILES, VOL. 14, NO. 8, AUGUST 2015 7 0 0.2 0.4 0.6 0.8 1 1.2 Time (s) 0 2 4 6 8 V- (V) Re{K} Im{K} (a) 0 0.2 0.4 0.6 0.8 1 1.2 Time (s) -6 -3 0 3 6 Voltage (V) V- V- (b) 0 0.2 0.4 0.6 0.8 1 1.2 Time (s) -6 -3 0 3 6 Current (A) ia ib ic (c) 0.1 0.11 0.12 0.13 0.14 0.15 0.16 Time (s) -6 -3 0 3 6 Current (A) ia ib ic (d) 1.1 1.11 1.12 1.13 1.14 1.15 1.16 Time (s) -6 -3 0 3 6 Current (A) ia ib ic (e) Fig. 6. Performance of the DR controller using gain kwith Im{k}= 0 and Re{K}= 1400, with ωd= 174 rad/s: (a) modulus of negative-sequence voltage, (b) αβ negative-sequence voltages, (c) currents ia,b,c, (d) currents ia,b,c zoom-in before applying the controller and (e) currents ia,b,c zoom-in after applying the controller. of the same DR controller when the converter is subject to a change in active power injection. A load change at time t= 0.8s occurs and requires doubling the active power injection, increasing from 600 W to 1200 W. As it can be observed, the increase in the power injection leads to an increase in the injected currents (Sub-fig. 7b) while the negativesequence voltage (Sub-fig. 7a) reaches the expected steadystate equilibrium although a small overshoot can be observed when the load change occurs due to the coupling introduced by the SOGI. This experiment permits corroborating that the DR controller operates as desired without altering or being altered by the positive-sequence controller whose main task is to inject the active power generated by the source. 0 0.2 0.4 0.6 0.8 1 1.2 Time (s) 0 2 4 6 8 V- (V) Re{K} Im{K} (a) 0 0.2 0.4 0.6 0.8 1 1.2 Time (s) -6 -3 0 3 6 Current (A) ia ib ic (b) Fig. 7. Performance of the DR controller subject to a change in active power injection from 600 W to 1200 W at time t= 0.8s, using gain kwith Im{k}= 0 and Re{K}= 1400, with ωd= 174 rad/s: (a) modulus of negative-sequence voltage and (b) currents ia,b,c. B. Real and Complex Part of the DR Controller Gain Similar to Sub-fig. 6a, Fig. 8 shows the performance of the DR controller for different initial phases of the controller gain. As before, the different settings of the real and imaginary part of the controller parameters are illustrated by the vector arrow plotted in each Sub-fig. As it can be observed, the phase of the gain khas an effect on the transient dynamics. Nevertheless, for any phase, the DR controller is able to eliminate the negative-sequence voltage. Fig. 9 shows the performance of the DR controller for different settings of the modulus of the controller gain k. The real and imaginary part of the controller gain keep the same angle but its modulus increase in each Sub-fig., from left to right. As it can be seen, the greater the gain, the faster the response. However, from |k|= 2800 the system is no longer stable, as it can be seen for |k|= 3000 in Sub-fig. 9d, thus corroborating the numerical study given in sub-section IV-B. C. Enriching the Closed-Loop Dynamics The dissonant frequency ωdis the parameter of the DR controller (15) that permits generalizing the operation of a standard R controller in such a way that a richer set of closed-loop dynamics can be obtained. Fig. 10 shows the performance of the DR controller for different settings of the dissonant frequency in such a way that different pairs of (ωd,|k|) apply. In the experiments, the variation of ωdgoes together with a variation of the modulus of the controller gain in order to achieve in all the experiments the same settling time with different dynamics. In particular, from left to right, Sub-figures 10a, 10b and 10c are characterized by (ωd,|k|) = {(17.4,140),(174,1400),(1740,14000)}, respectively, where ωdis in rad/s. This rich set of dynamics could not be achieved by a standard R controller. In addition, Fig. 11 provides a comparison of the DR controller with a given particular setting, |k|= 1400 and ωd= 174 rad/s, with respect to a R controller with the same gain. As it can be observed, the R controller also
JOURNAL OF L A T EX CLASS FILES, VOL. 14, NO. 8, AUGUST 2015 8 0 0.2 0.4 0.6 0.8 1 Time (s) 0 2 4 6 8 V- (V) Re{k} Im{k} (a) 0 0.2 0.4 0.6 0.8 1 Time (s) 0 2 4 6 8 V- (V) Re{k} Im{k} (b) 0 0.2 0.4 0.6 0.8 1 Time (s) 0 2 4 6 8 V- (V) Re{k} Im{k} (c) 0 0.2 0.4 0.6 0.8 1 Time (s) 0 2 4 6 8 V- (V) Re{k} Im{k} (d) 0 0.2 0.4 0.6 0.8 1 Time (s) 0 2 4 6 8 V- (V) Re{k} Im{k} (e) 0 0.5 1 Time (s) 0 2 4 6 8 V- (V) Re{k} Im{k} (f) 0 0.2 0.4 0.6 0.8 1 Time (s) 0 2 4 6 8 V- (V) Re{k} Im{k} (g) 0 0.2 0.4 0.6 0.8 1 Time (s) 0 2 4 6 8 V- (V) Re{k} Im{k} (h) Fig. 8. Modulus of the negative-sequence voltage for different settings of the controller gain ksubject to |k|= 1400, with ωd= 174 rad/s: (a) ϕ′= 0◦, (b) ϕ′= 45◦, (c) ϕ′= 90◦, (d) ϕ′= 135◦, (e) ϕ′= 180◦, (f) ϕ′= 225◦, (g) ϕ′= 270◦, and (h) ϕ′= 315◦. 0 0.2 0.4 0.6 0.8 1 Time (s) 0 2 4 6 8 V- (V) Re{k} Im{k} (a) 0 0.2 0.4 0.6 0.8 1 Time (s) 0 2 4 6 8 V- (V) Re{k} Im{k} (b) 0 0.2 0.4 0.6 0.8 1 Time (s) 0 2 4 6 8 V- (V) Re{k} Im{k} (c) 0 0.2 0.4 0.6 0.8 1 Time (s) 0 2 4 6 8 V- (V) Re{k} Im{k} (d) Fig. 9. Modulus of the negative-sequence voltage for different settings of the controller gain k, with ωd= 174 rad/s, Im{k}= 0 and (a) Re{k}= 700, (b) Re{k}= 1400, (a) Re{K}= 2000, (a) Re{K}= 3000. 0 0.2 0.4 0.6 0.8 1 Time (s) 0 2 4 6 8 V- (V) Re{k} Im{k} (a) 0 0.2 0.4 0.6 0.8 1 Time (s) 0 2 4 6 8 V- (V) Re{k} Im{k} (b) 0 0.2 0.4 0.6 0.8 1 Time (s) 0 2 4 6 8 V- (V) Re{k} Im{k} (c) Fig. 10. Modulus of the negative-sequence voltage for different settings of the controller rotation speed ωd, that leads to different pairs of (ωd,|k|) : (a) (17.4,140), (b) (174,1400), and (c)(1740,14000) (where ωdis in rad/s). 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 Time (s) 0 2 4 6 8 V- (V) DR controller Resonant controller Re{K} Im{K} Fig. 11. Modulus of negative-sequence voltage of the DR controller using gain kwith Im{k}= 0 and Re{k}= 1400, with ωd= 174 rad/s compared to the standard resonant controller with |k|= 1400. eliminates the negative-sequence voltage. But the transient dynamics of the R controller are slower that the DR controller. Specifically, looking at the settling time where the negativesequence voltage remains within 5%of zero, the DR controller reaches this point at time t= 0.6s while the R controller does it at time t= 1.1s, suggesting that the DR controller is almost two times faster than the R controller when both controllers are characterized by the same integral gain. 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 Time (s) 0 2 4 6 V- (V) G1 G2 G3 G4 G5 G6 (a) 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 Time (s) 0 2 4 6 V- (V) G1 G2 G3 G4 G5 G6 (b) Fig. 12. Negative-sequence voltage elimination for parallel DR controllers: synchronized (a) and serial (b) activation. D. Parallel Operation Fig. 12 completes the experimental validation of the DR controller analyzing its performance in parallel operation when six grid-feeding converters operate in a grid-connected AC
JOURNAL OF L A T EX CLASS FILES, VOL. 14, NO. 8, AUGUST 2015 9 microgrid, as illustrated in Fig. 5. In this scenario, the voltage of the main grid is unbalanced and the converters are supplying the load L1with 100 W each. For each converter, the damped LC filter and the DY transformer specifications are given in Table I. The goal of each local DR controller is to eliminate the negative-sequence voltage seen in each converter output. Two experiments are performed. The first one, Sub-figure 12a, covers the synchronized activation of the six DR controllers of the six converters, meaning that all of them are activated at the same time, at t= 0.2s. The second one, Sub-figure 12b, covers the serial activation of the six DR controllers. In this case, starting at t= 0.2s, and every 0.2s approximately, every DR controller is activated, starting from G1to G6. Both subfigures in Fig. 12 shows that all DR controllers eliminate the negative-sequence voltage. It is worth noting that the serial activation covers the wort case scenario in terms of coupling effects among the controllers. In particular, it illustrates the coupling effect that each activation of each converter DR controller has in the negative-sequence voltage seen by the other converters. The performance of each controller after the activation of a new one highly depends on the initial phase that it has to deal with, which determines the closed-loop dynamic behavior delivered by each controller, as discussed in the description of the properties of the DR controller given in Sub-section III-C. VI. CONCLUSION The elimination of voltage unbalance leads to higher power quality. Motivated by this fact, this paper has presented a novel controller strategy for a grid-feeding converter capable of suppressing the negative-sequence voltage at the converter output. The control strategy, based on the application of a resonant controller, defines a generalized structure, called dissonant-resonant controller, that is characterized by two control parameters whose adjustment permits the controller to act almost like a pure integral controller. As a consequence, it has the ability of completely remove the error, that is, to remove the negative-sequence voltage without incurring in the problems that integral controllers may have in parallel operation. In addition, the control goal is achieved regardless of the impedance value of the grid. The presented stability analysis permits a safe design while indicating design guidelines for the control parameters. Future work will focus on the extension of this control algorithm to grid-forming converters. REFERENCES [1] F Woll, ”Effect of unbalanced voltage on the operation of polyphase induction motors,” IEEE Trans. Ind. Applicat., vol 11, pp 3842, Jan. 1975. [2] K. Lee, G. Venkataramanan and T. M. Jahns, ”Modeling effects of voltage unbalances in industrial distribution systems with adjustablespeed drives,” IEEE Trans Ind. Applicat., vol. 44, no. 5, pp. 1322-1332, Sept.-Oct. 2008. [3] ”EN 50160, Voltage characteristics of electricity supplied by public electricity networks”, 1999 [4] J. Rocabert, A. Luna, F. Blaabjerg and P. Rodr´ıguez, ”Control of power converters in AC microgrids,” IEEE Trans. Power Electron., vol. 27, no. 11, pp. 4734-4749, Nov. 2012. [5] D. Graovac, V. A. Kati, and A. Rufer, ”Power quality problems compenation with universal power quality conditioning system,” IEEE Trans. Power Del., vol. 22, no. 2, pp. 968-976, Apr. 2007. [6] J. Miret, A. Camacho, M. Castilla, L. G. Vicuna, and J. Matas, ”Voltage support control strategies for static synchronous compensators under unbalanced voltage sags,” IEEE Trans. Ind. Electron., vol. 61, no. 2, pp. 808-820, Apr. 2013. [7] J. M. Guerrero, P. C. Loh, T. L. Lee, and M. Chandorkar, ”Advanced control architectures for intelligent microgrids. Part II: Power quality, energy storage, and AC/DC microgrids,” IEEE Trans. Ind. Electron., vol. 60, no. 4, pp. 1263-1270, Apr. 2013. [8] A. Camacho, M. Castilla, J. Miret, J. C. Vasquez, and E. Alarcon-Gallo, ”Flexible voltage support control for three-phase distributed generation inverters under grid fault,” IEEE Trans. Ind. Electron. , vol. 60, no. 4, pp. 1429-1441, April 2013. [9] F. Gonzalez-Espin, I. Patrao, E. Figueres and G. Garcera, ”An adaptive digital control technique for improved performance of grid connected inverters,” IEEE Trans. Ind. Inf., vol. 9, no. 2, pp. 708-718, May 2013. [10] M. Castilla, J. Miret, A. Camacho, J. Matas and L. Garc´ıa de Vicu˜na, ”Voltage support control strategies for static synchronous compensators under unbalanced voltage sags,” IEEE Trans. Ind. Electron. vol. 61, no. 2, pp. 808-820, Feb. 2014. [11] X. Guo, X. Zhang, B. Wang, W. Wu, and J. M. Guerrero, ”Asymmetrical grid fault ride-through strategy of three-phase grid-connected inverter considering network impedance impact in low-voltage grid,” IEEE Trans. Power Electron., vol. 29, no. 3, pp. 1064-1068, Mar. 2014. [12] A. Camacho, M. Castilla, J. Miret, R. Guzman, and A. Borrell, ”Reactive power control for distributed generation power plants to comply with voltage limits during grid faults,” IEEE Trans. Power Electron., vol. 29, no. 11, pp. 6224-6234, Nov. 2014. [13] X. Shi, Z. Wang, B. Liu, Y. Liu, L. M. Tolbert and F. Wang, ”Characteristic investigation and control of a modular multilevel converter-based HVDC system under single-line-to-ground fault conditions,” IEEE Trans. Power Electron., vol. 30, no. 1, pp. 408-421, Jan. 2015. [14] S. Li, X. Wang, Z. Yao, T. Li and Z. Peng, ”Circulating current suppressing strategy for MMC-HVDC based on nonideal proportional resonant controllers under unbalanced grid conditions,” IEEE Trans. Power Electron., vol. 30, no. 1, pp. 387-397, Jan. 2015. [15] M. Mirhosseini, J. Pou, and V. G. Agelidis, ”Individual phase current control with the capability to avoid overvoltage in grid-connected photovoltaic power plants under unbalanced voltage sags,” IEEE Trans. Power Electron., vol. 30, no. 10, pp. 5346-5351, Oct 2015. [16] J. L. Sosa, M. Castilla, J. Miret, J. Matas, and Y. A. Al-Turki, ”Control strategy to maximize the power capability of PV three-phase inverters during voltage sags,” IEEE Trans. Power Electron., vol. 31, no. 4, pp. 3314-3323, April 2016. [17] H. Nian, T. Wang, and Z. Q. Zhu, ”Voltage imbalance compensation for doubly fed induction generator using direct resonant feedback regulator,” IEEE Trans. Energy Convers., vol. 31, no. 2, pp. 614-626, Jun. 2016. [18] F. Nejabatkhah, Y. W. Li and B. Wu, ”Control strategies of three-phase distributed generation inverters for grid unbalanced voltage compensation,” IEEE Trans. Power Electron., vol. 31, no. 7, pp. 5228-5241, July 2016. [19] Z. Wang, B. Wu, D. Xu, M. Cheng, L. Xu, ”DC-link current ripple mitigation for current-source grid-connected converters under unbalanced grid conditions”, IEEE Trans. Ind. Electron., vol. 63, no. 8, pp. 4967- 4977, Aug. 2016. [20] V. Vekhande, K. V. K. and B. G. Fernandes, ”Control of three-phase bidirectional current-source converter to inject Balanced three-phase currents under unbalanced grid voltage condition,” IEEE Trans. Power Electron., vol. 31, no. 9, pp. 6719-6737, Sept. 2016. [21] Y. Hu, Z. Q. Zhu and M. Odavic, ”Instantaneous power control for suppressing the second-harmonic DC-bus voltage under generic unbalanced operating conditions,” IEEE Trans. Power Electron., vol. 32, no. 5, pp. 3998-4006, May 2017. [22] X. Shi, Z. Wang, B. Liu, Y. Li, L. M. Tolbert and F. Wang, ”Steadystate modeling of modular multilevel converter under unbalanced grid conditions,” IEEE Trans. Power Electron., vol. 32, no. 9, pp. 7306-7324, Sept. 2017. [23] H. Chen and X. Xing, ”Circulating current analysis and suppression for module grid-connected inverters under unbalanced conditions,” IEEE Access, vol. 6, pp. 69120-69129, Oct. 2018. [24] M. A. G. L´opez, J. L. G. de Vicu˜na, J. Miret, M. Castilla, and R. Guzm´an, ”Control strategy for grid-connected three-phase inverters during voltage sags to meet grid codes and to maximize power delivery capability,” IEEE Trans. Power Electron., vol. 33, no. 11, pp. 9360-9374, Nov. 2018. [25] X. Guo, Y. Yang and X. Zhang, ”Advanced control of grid-connected current source converter under unbalanced grid voltage conditions,” IEEE Trans. Ind. Electron., vol. 65, no. 12, pp. 9225-9233, Dec. 2018.