On the Feasibility of Collaborative Green Data Center Ecosystems Anna Agust´ ı-Torraa, Frederic Raspalla, David Remondoa, David Rinc´ ona,1, Giovanni Giulianib aDept. of Telematics Engineering, Universitat Politecnica de Catalunya (UPC), Barcelona, Spain bHP Italy Innovation Center, Milan, Italy Abstract The increasing awareness of the impact of the IT sector on the environment, together with economic factors, have fueled many research efforts to reduce the energy expenditure of data centers. Recent work proposes to achieve additional energy savings by exploiting, in concert with customers, services’ workloads and to reduce data centers’ carbon footprints by adopting demandresponse mechanisms between data centers and their energy providers. In this paper, we debate about the incentives that customers and data centers should have to adopt such measures and propose a new service type and pricing scheme that is economically attractive and technically realizable. Simulation results based on real measurements confirm that our scheme can achieve additional energy savings while preserving service performance. Keywords: energy-efficient computing and networking, energy-aware data centers 1. Introduction The advances in virtualization technology of the last years have shaped the evolution of the IT sector towards a model where organizations no longer sustain their IT infrastructure but rent it from third parties. This ”cloud” paradigm is attractive for companies and providers as it allows for a quicker deployment of new services, relieves companies from their maintenance, and can significantly cut down companies’ and providers’ costs. As a result, we are witnessing a rapid deployment of new data centers (DCs) of increasing size, complexity and heterogeneity in service offerings. In parallel, several studies have estimated that the IT sector is responsible for about 1 – 2% of the greenhouse gas (GHG) emissions worldwide [1]; DCs accounting for 1.3% of the overall energy consumed [2]. The impact of CO2emissions on climate change and the rapid concentration of IT services in DCs have raised the concern about their energy sustainability. Moreover, energy consumption accounts for a significant share of DCs’ operational costs. Thus, rather than a concern, energy saving has become a necessity for DCs’ economic viability. Many regulations are also being established worldwide to limit corporate emissions, increasing the pressure to cap carbon footprint, to promote the procurement of power with source mixes with a larger portion of renewable energy [3]. Within a DC, energy consumption reduction is tackled at various levels. At the component level, for example, by employing more efficient power supplies, multiple spin rate drives, and memories or CPUs with several energy states or clock gating. At the system level, by employing Dynamic Frequency and Voltage Scaling (DFVS) techniques to adapt CPU parameters according to load, adjusting performance not to exceed ∗Corresponding author. Tel.: +34 934137056. Fax: +34 934137007. Email address: [email protected] (David Rinc´ on) some power limit (capping), introducing power profiles, or supporting variable-speed fans. At an architectural level, by carefully locating racks, server clusters or network interconnects to optimize the effectiveness of cooling and ventilation. Last, at the operations level, by trying to adapt IT component utilization to workloads. These techniques seek to exploit components’ power attributes by tuning them according to utilization (or even shutting down components). Examples include consolidation of workloads and virtual servers into fewer, more energy-efficient physical servers (so that some servers and network elements can be switched off), or migrating/re-locating these to other DCs with more advantageous conditions due to the weather or the cost of energy [4]. While DC-holistic approaches can significantly cut down power consumption, further savings and lower environmental impact may be achieved by widening the scope of the solution to span the entire energy consumption chain. In this direction, [5] proposes a concerted strategy toward both energy and CO2 emission reduction where the three parties in the DC ecosystem interact; namely, the DC, its customers, and the DC’s energy provider (EP). The approach relies on two ideas: first, a higher flexibility in the service agreements between the parties; second, their dynamic collaboration.Flexibility is supported by the inclusion of energy-related (green) clauses in the Service Level Agreements (SLAs), established between the DC and its customers, and the power Supply-Demand Agreements (SDAs), established between DCs and EPs. Collaboration allows a party to request the other to adjust its behaviour so that some energy/power consumption objective is met, and is implemented by the exchange of messages between a DC and its EP or the DC and its customers. Thus, for the EP to avoid resorting to fossil energy sources (e.g. diesel engines) due to a peak in the total energy demanded, the EP can instead request one or more of its customer DCs to temporarily reduce their power consump- Preprint submitted to Ad-hoc networks September 29, 2014 *Manuscript
tion; if a DC accepts the request, it will adjust the performance of the hosted IT applications to reduce its energy consumption (e.g. by consolidating virtual machines (VM) in fewer physical servers, delaying the execution of tasks, etc.). In case of energy surplus, the performance of the IT services provided by the DC can be upgraded (by increasing the physical resources allocated to them, advancing the execution of scheduled jobs, or accepting workloads from other DCs). The idea of reducing power usage in a demand-response (DR) fashion when supply is scarce is not new. [6] describes a use case where a company reduces its power demand by automatically adjusting lighting, thermal settings or rack power distribution units (PDUs) upon an EP’s request. While this form of collaboration or those in [5] and [7] can effectively lead to an environment friendly DC ecosystem, all the different parties must have an incentive to adopt them –aside from environmental stewardship–, as this may critically impact their businesses. [5], [6] and [7] suggest the incentives to be financial, based on rewards or discounts. EPs will make discounts to DCs that diminish their power demands. As this may require changing the operating conditions of applications, DCs’ customers should agree in advance to reductions in performance and be compensated with lower tariffsaccordingly. Otherwise, DCs would have little interest in collaborating with EPs: the economic loss that resulted from compensating customers for SLA violations could outweigh EP’s rewards and cause customers to choose other providers. Still, even if DC customers adhered to flexibilize the committed performance levels, finding a suitable reward/pricing scheme is hard given the multiraterality of the DC ecosystem: customers’ discounts might not pay offthe performance degradation experienced; on the other hand, while a DC would see its energy expenditures reduced, it could still see its profit diminished (due to lower revenues resulting from the use of lower tariffs during energy saving episodes). We conclude that, for any energy saving collaborative framework as those described to succeed, it must permit reaching some equilibrium point where customers are satisfied with the service received (relative to its price), and where DCs and EPs do not see their profits depressed. A second condition is that the technical requirements to implement it must be simple enough for DCs to adopt it. In this regard, we note that, while [5] establishes a framework and methods to deploy such a paradigm in a technically realizable manner, these do not warrant the above requirement by themselves. This paper seeks to contribute in this direction by proposing a service model and pricing scheme that is attractive for users, profitable for DCs and EPs and technically feasible, while promoting energy savings in a collaborative manner. We discuss benefits that its adoption would bring to all the parties and assess its advantages and disadvantages with results obtained with a simulator (contrasted with measurements from real DCs), fed with real and synthetic service demands and load patterns, real server parameters and typical energy costs. This paper is organized as follows. Section 2 briefly describes the components of the DC ecosystem. Section 3 summarizes related work, including ideas in [5] that contextualize and motivate this work. In Section 4 we discuss potential barriers that may preclude the adoption of collaborative measures as the ones discussed. Section 5 presents the motivation, assumptions and idea behind our proposal, expected advantages. Section 6 identifies the major variables that need to be considered to measure such advantages and presents how we study their evaluation. Sections 7 and 8 discuss our experimental work: the tool employed, how it works, how we parameterized it and the results obtained. Section 9 presents general conclusions of this research, recommendations concerning the feasibility of the proposal and future directions. 2. Background and terminology 2.1. Data Centers (DCs) A data center is an infrastructure built to provide IT services such as massive data storage, CDN, web, e-mail, server hosting, enterprise-class applications, or on-demand computing. Such services often consist of several components like databases, front-ends, application servers or middleware, increasingly being deployed as virtual machines. The business model varies, but typically a DC is either a service within a large corporation, or a business by itself that resells some of its infrastructure to third parties or ”tenants”. While varying in size, purpose and structure, DCs typically consist of large farms of servers executing services for end users. Connectivity is provided by high-speed network equipment. Servers execute application software related to the offered services (e.g. web, e-mail, social network or video) as well as management software (e.g. backup or antivirus). Servers may host several VMs, controlled by a hypervisor software and managed either by the DC or, in a in cloud computing scenarios, indirectly by the users themselves. Apart from IT systems, DCs have facilities such as components used to deliver power (PDUs) and cooling to IT equipment. Most DCs use uninterruptible power supply (UPS) systems to protect the equipment and guarantee the supply in case of outages. In case of emergency, servers hosting secondary services can be switched off, and migration can be used to consolidate services. Hence, UPS systems must maintain power supply to keep the critical machines running while providing enough time to relocate critical services and orderly switch offthe hosted machines. DCs use cooling systems and air flow strategies to keep hardware temperature below a critical value beyond which it may malfunction or damage. Lastly, some large DCs also have on-site renewable power sources. Energy costs are becoming the major expense in DCs and this trend is increasing as hardware and software drop in price. Several studies show that most of the power consumed by a conventional DC is due to its servers (up to 50%), while, approximately, the other half of the power is due to cooling [8]. Many benchmark studies (e.g. [9]) have empirically found that the power consumed by servers increases quasi-linearly with the utilization of their cores, as depicted in Figure 1. Thus, the power consumed by a server can be accurately modeled as W(u)=Wmin +(WMax −Wmin)u(1) 2
Figure 1: Typical power-utilization curve of a physical server. Wmin refers to the active-idle power consumption, where server is in non-dormant state but with zero CPU utilization; while Widle is the power usage in some dormant state. where urefers to the % utilization of all its cores, WMax is the peak power, Wmin that at 0% utilization and (WMax −Wmin) is the dynamic power range. The fact that servers consume even if idle –i.e. their lack of proportionality– is what precisely motivates the consolidation of workloads in other servers to turn some off, and has driven vendors to manufacture more efficient processors. In this regard, note that W0(u),W(u)/WMax = b+(1 −b)u, with b=Wmin Wmax , where bcan be understood as a measure of proportionality (the lower the better). In the literature, other indices similar to bare used to quantify energy proportionality, such as b(1−u 2) or u W0(u). Similarly, several metrics are used to quantify the energy efficiency of DCs. A common one is the PUE (Power Usage Effectiveness), defined as the ratio between the total energy consumed over that spent solely by IT equipment. A lower PUE means higher efficiency. The PUE, which typically ranges in (1,3) [10], does not account for carbon emissions. Another metric is the Carbon Usage Effectiveness (CUE) defined as the product of PUE and CEF; where the CEF or carbon emission factor is the amount of CO2grams released per kWh. CEF can be non-zero for renewable sources if the emissions due to manufacturing, transport, installation or recycling of their equipment are considered. 2.2. IT Customers, users and IT Services We call IT Customer (ITC) the entity that contracts the provision, execution and maintenance of some application –IT service (ITS)– in a DC, as opposed to users, which are those employing the service. DCs provide a wide array of services, from consumer-oriented to enterprise-class offerings. Thus, ITCs can be single users, but also companies offering services to other individual users, businesses, or departments within themselves. An IT service is understood as a collection of servers (physical or virtual, hereafter called virtual machines, VMs) and software entities that jointly execute a task. IT services have a wide range of complexity: from single VMs started and controlled at the customers will, to complex cloud computing applications involving several physical servers, many VMs, and auxiliary subservices such as antivirus or backup procedures. This model where customers pay to build a virtual infrastructure on top of a DC’s physical one is called Infrastructure-as-a-Service (IaaS). SLAs specify the conditions under which a certain type of IT service is to be provided, the tariffto be paid, and the penalties (usually discounts) in case the DC fails to deliver the service under the agreed conditions. The key performance indicators (KPIs) most often found in SLAs relate to availability (service uptime) and performance. Cloud computing services consisting of VMs can also include as KPI detailed parameters such as start-up delay, computing power1, memory, OS image, I/O performance or disk size (refer to [11] for examples). One way of quantifying the resources available to a virtual server (and thus its performance) is by a consolidation ratio CR, defined as the number of virtual CPUs (vCPUs) of VM instances running per server or CPU core. DC automation frameworks take care of provisioning the necessary resources (and monitoring them) for each IT Service, by mapping the high-level clauses and KPIs found in SLAs into low-level operational parameters. For instance, a web-hosting service may include a ”high-performance” SLA clause that translates into 12 load balanced VMs (running in 3 servers) able to handle 1000 requests/sec; while a ”medium performance” may refer to the same service running 6 VMs on 2 servers of lower capacity able to process 300 requests/s. In cloud/IaaS environments, service instances typically belong to a certain class (e.g. small,medium or large) with some predefined attributes (e.g. 1, 2 or 4 vCPUs, and 2, 4 or 8GB of RAM). 2.3. Energy Providers (EPs) An EP is a company that produces and sells energy. Supplydemand agreements (SDAs) state the conditions under which power is delivered to customers. These include the price per kWh, a peak power demand and availability. Energy costs vary by region. According to [12], the average industrial rate per kWh is $0.0677 in the US and e0.0836 in Europe. Typically, EPs manage several power generator facilities like coal generation plants or gas turbines to satisfy the demands. It is very important to EPs that the power they produce matches the power that is being demanded and not feed the grid with more or less energy than needed (otherwise the grid could collapse). Therefore, it is crucial for EPs to correctly plan energy production ahead, and to rapidly react to unforeseen changes in demand. Prediction of power generation capabilities and power demands is critical for the EP to be able to plan economically (and also ecologically) which power sources it schedules. The reaction time of power sources varies significantly: for instance, coal power plants need several hours to shut down, while diesel generators can be turned on/offrapidly. And the availability of renewable energy can highly vary depending on wind speeds or solar irradiance. EPs make use of customer load profiles and categorize them. For major customers (e.g. DCs), power consumption is measured directly to precisely tune prediction methods. To plan power generation, EPs take into account weather forecasts to predict the amount of renewable energy that will be available. 1Measured in abstract units such as Amazons Compute Unit, equivalent to a 1.0-1.2 GHz 2007 Opteron/Xeon processor (see [11]). 3
To quantify the extent to which production conforms to demand, EPs consider the ratio Rbetween generated and demanded power. Energy shortage occurs when Rdeviates to values <1; while surplus when R>1. Both types of episodes are critical for an EP if it is not able to timely compensate them with its own power sources. This is the reason to tighten the collaboration of DCs and EPs on a demand-response fashion. The energy consumed by a DC typically accounts for a relatively small percentage of the energy produced by its EP. Nevertheless, the ability to quickly reduce the power demand even if in a small percentage can help an EP to avoid resorting to expensive and highly contaminating power sources. Thus, for an EP, a DR scheme constitutes an effective, practical means to dynamically influence the power demanded by customers. On the other hand, an EP may supply energy to multiple DCs, their joint demand constituting a larger fraction. Thus, the larger the number of DCs served and their share of the demand, the easier it can be for an EP to influence the demand (and mitigate peaks quicker) as this offers higher degrees of freedom. 3. Related work There are diverse solutions to reduce DCs’ energy consumption, such as techniques where servers’ processor states are aligned with job demands (e.g. DVFS), system-wide approaches that reduce servers’ idle powers [13], per-core power gating [14], consolidation of servers during low workload periods (e.g. [15]), virtualization techniques to obtain energy savings [16], [17] or the use of low-latency power state changes in servers to improve the impact of virtualization [18]. To complement these, there are many contributions that focus on the characterization of workloads in DCs, such as [19]. [20] considers the adaption of DC’s power demand to fluctuations in electricity pricing considering the DC as a whole, disregarding the discrete elements inside, while [21] contemplates the use of on-site energy storage to avoid peak power costs. [3] studies the reduction of DCs’ carbon footprints by using on-site renewable energy production. By managing resources across multiple DCs, [22] achieves power savings. Similarly, [23] contemplates the dynamic exchange of workloads among different sites, where services are moved to DCs with higher efficiency –both in terms of performance versus power consumption ratio and also depending on the carbon footprints of the energy generation at their EPs–. As mentioned, the co-operation paradigm recently proposed in [5] is based on leveraging flexibility and dynamic collaboration among all the DC ecosystem players: the EP, the IT customers and the DC itself. Flexibility is enhanced by adding energy-aware extensions to SLAs –stating the conditions (QoS parameters, guarantee terms and associated tariffs) under which IT services are provided– which then become GreenSLAs. These extensions establish the degree of change in running conditions (e.g. performance or availability) that the DC and its customer agree to accept as a function of the energy context of the ecosystem, together with specific tariffs and guarantee terms. Energy context refers to the state of the ecosystem regarding energy, and it can be either calendar related or dependent on the actual situation of the EP. Calendar-based clauses relate running conditions with the time-of-the-day. An example of a calendar related clause could be that a service enjoys a 99.95% availability for weekdays during working hours and a 95% – 99% availability for the rest of the time. On the other hand, the collaboration paradigm, illustrated in Figure 2, contemplates interactions between EPs and DCs related to the current balance between the energy demand and production of the EP, according to extensions in the SDAs (called GreenSDAs), such that an EP can issue requests to a DC to reduce or increase the consumed power for a certain time period. If the DC accepts to serve the request, there will be clauses in the GreenSLA that allow the DC to modify its power consumption by changing running conditions of some IT services. An example of such a clause could be that, if a request from an EP to reduce power consumption for a time period Thas been accepted by the DC, then a Web hosting service that is running in a high performance condition (say, 12 load-balanced VMs able to handle 1000 requests/s) can be set to run in medium performance (6 load-balanced VMs) during T. The collaboration between the three DC ecosystem parties will also follow the rules established in the GreenSLAs (between the DC and the IT customers), and the GreenSDAs (between the DC and the EP), together with the associated economic impact for every change in running conditions of the IT services or the consumed power of the DC, respectively. An example of such rules could be that the EP may request the DC to reduce its power consumption for periods no longer than one hour, during which a certain discount in the electricity price will be applied. Figure 2: Interaction among the three DC ecosystem parties. 4. Current DC service models and barriers potentially hindering collaboration in the DC ecosystem As discussed in §1, at least two conditions should be met for energy saving collaborative models to be adopted. First, the measures to save energy should not conflict or impair IT customers interests (e.g. businesses), who should still perceive adequate service levels relative to their cost. Second, energy-saving measures and their consequences (e.g. on pricing) should not affect DCs’ economic viability (i.e., they should not cause DCs’ profits to be reduced). To understand the motivation behind our proposal and its advantages, next we briefly discuss existing service models, pricing schemes, and the effect of energy costs in DC’s economies through a simple model. 4
4.1. Current service and pricing schemes The service models and pricing schemes offered by public DCs (e.g. [11][24][25][26][27][28]) are diverse and rapidly evolve nowadays (particularly in cloud providers) as a result of the technology quickly advancing and competition. Generically, however, providers employ a billing scheme that depends on three dimensions: performance (committed resources), uptime and resource utilization. Customers can contract one or more instances of a certain class (specifying OS, amount of RAM, disk capacity, CPU power or network bandwidth) and pay accordingly; a monthly fee in traditional services (e.g. managed hosting), or only during the time that the service is active (in cloud/IaaS, typically on a hourly basis). Some providers also charge when the service is off, but at a lower tariff(e.g. 50% less) to cover the cost of storing customers’ data. In others, pricing depends on the number of I/O operations performed, the amount of RAM available to VMs, or the network bandwidth used. To cope with increasing service’s demands, some DCs have elastic offerings where the resources allocated to IT services can be scaled (and billed accordingly) depending on their loads, either automatically or by the customers themselves via a Web dashboard or some API. 4.2. Data center economics and the effects of energy costs To determine adequate tariffs (e.g. prices per unit time in pay-as-you-go schemes as the above), DCs need to find an equilibrium between two competing factors: their profit and their competitiveness. In a simple model, the profit P can be defined as the difference between the DC’s revenues R (what customers pay) and running costs C, over some period of time (e.g. monthly). Costs include recurring costs (personnel salaries, licences, taxes, insurances, maintenance, leasing of buildings, etc.) and the amortization of facility or IT equipment and building costs. Part of these running costs are strictly due to energy consumption and the rest are independent of this factor. The costs due to energy consumption, Ce, are due to the energy consumed by servers and interconnects, lighting and cooling, and can be written as Er, with Ethe amount of energy consumed in a time period and rthe price per kWh. We refer to the running costs that are independent of energy consumption as fixed costs. Thus, in a simple economic model, we can express DC costs as C=Cf+Ce–with Cfthe fixed costs and Ce=Er the energy related expenditure– and its profit as P=R−C=R−(Cf+Ce), where, to be economically viable in the long term, R>C. While well established cloud providers have reported significant profits in the past, new players continue to appear, offering services at tariffs often 40% lower [29]. In an increasingly competitive market as this, revenues Rare expected to progressively approach costs Cfrom above, as new providers emerge and DCs strive to capture/retain market share. Indeed, big providers have announced price reductions over time. Thus, in our model, we can assume that PR(or R P1). Since energy consumption represents a significant fraction of the total costs and it varies depending on IT workloads, finding the right tariffscheme is hard for a DC. A conservative approach (e.g. billing under the assumption that servers or network devices consume peak powers WMax even if they do not) would maximize profit; however, profit maximizing schemes are not always the optimal strategy as could be, for instance, capturing market share. Conversely, setting tariffs below the worst-case cost of energy can attract users, but also lead to lower profit or even economic loss. The point is that, if energy costs account for a large fraction of the OPEX, their variation can have a high impact on DCs total costs and profits. To illustrate this, let us see how a certain variation ∆E in the energy spent by a DC may affect its overall costs. As C=Cf+Ce, if we assume that Ce=αCfor some α < 1, and the fixed costs Cfto be independent of the E, we have ∆C C=∆Ce C=∆E Cr=∆Er Er Ce C=∆E Eα, which says that a 20% variation in the energy consumption translates into a 20α% variation in the total costs. Similarly, by definition, profit is P=R−C. Assuming that revenues Rdo not depend on E(as occurs in XaaS-services where customers pay fixed fees), ∆P P=−∆C P=−∆C C C P=−α∆E E R−P P=−α∆E ER P−1 which, under the assumption that RP, is ∆P P≈ −α∆E E R P, and says that a DC’s profit can significantly vary depending on its energy consumption. For instance, for α=0.5 and R P=6, a 10% increase in the energy bill will cut profit by 25%. If finding a suitable pricing scheme is hard with conventional service offerings, the use of ”green” SLAs will complicate the matter further, which may discourage their adoption. Suppose that a DC (employing a conservative billing approach) were to offer, according to some ”greened” SLAs, two service performance levels abiding some calendar: a high one (for business hours), and a low, energy-saving one for the rest of time. During non-busy hours, the DC would save energy and see its energetic costs reduced. However, depending on how the price per unit time were set for those periods, it could see its interests impaired: too low of a price could cause the DC to see its revenue (and thus profit) reduced, while higher prices may not be accepted by customers if the price reduction did not pay offthe performance one; causing the DC to loose market share (and again profit), compared to the case where no performance and price adjustments were made to save energy. Hence, given the expected increase in pricing sensitivity (due to higher competition), providers may be reluctant to adopt such measures. 5. Proposed service and pricing scheme 5.1. Motivating observations and assumptions As per the previous discussion, performance-centric pricing schemes can make it difficult for DCs to predict profits and establish competitive tariffs, given that fees do not necessarily match the costs incurred to run services, like those related to power consumption. Moreover, customers have no stimulus to promote or claim for energy efficiency, but performance. Studies on DC’s workloads have shown that servers are seldom idle but rarely operate at maximum CPU utilization [30]. Moreover, the load of many IT services may fluctuate and be, in several periods, far below the peak, for which resources are 5
provisioned (and customers billed irrespective of their usage). Under these circumstances, many customers could prefer a service whose tariffdepended on the real utilization of their services, more than on the resources the DC provisions to them. Further, some could accept some performance degradation for the purposes of energy saving if this translated into a lower bill; particularly if they were given the assurance that, at peak or busy hours –when their services are mostly demanded– some prescribed performance metrics or resources are guaranteed. 5.2. Proposed pricing model The pricing scheme that we propose is conceptually fairly simple. Instead of setting prices according only to performance, utilization or allocated resources, let service fees include a fixed part plus a variable one that equals the monetary cost of the energy consumed by an IT service. To exemplify how this scheme could work, consider a service consisting of a single VM charged only when the instance is running on a time slot basis, such as 10 minutes. The fee at the kth slot could be pk=f+ekrk, with ekthe energy spent by the instance and rkthe price per kWh. The value of fwould depend on the instance properties (e.g. OS image) and be derived to apportion for DC’s fixed costs Cf, including some quantity to achieve a certain target profit. If the IT service consisted of Icomponents or instances, the fee for each would be pi,k=fi+ei,krkand the overall service fee in a slot equal Pk=PI ipi.k=PI ifi+PI iei,krk. Thus, the bill after running the service over Sslots would amount to B= S X k=1 Pk=S I X i fi+ S X k=1 rk I X i=1 ei,k where the second term corresponds to the energy spent by the service throughout, weighted, at each slot, by the kWh rate. Note that if the fiare identical (some f) and the rate of energy constant r, the above is simply S I(f+¯ Er), with ¯ Ethe average energy consumed per instance over Sslots. Note that the above model is kept purposely open. For instance, the energy figures (ei) can include or not (part of) the costs of cooling or those of the network interconnects, which could, otherwise, be apportioned to the fixed terms f. The important fact is that a direct inclusion of energetic costs into fees can solve the issue with respect to the incentives that a DC has to offer variable-performance schemes to save energy; be these on a calendar basis or in response to explicit requests from EPs: if users pay proportionally to their energy consumption, DCs’ profits can remain the same even when resorting to lower tariffs during energy-saving episodes, because this is as if customers paid themselves the watts they consume directly to the EP. In other words, during energy-saving periods, the DC’s turnover can be reduced exactly by the same amount that its energy costs, hence keeping its profit roughly the same. Moreover, DC profits can be much less sensitive to energy expenditures. Explicitly including energy expenditures in fees can increase customers’ awareness of the environmental impact of their businesses, be fairer –not only environmentally, but also economically–, and makes particular sense given that energy proportionality is becoming a primary design goal. Still, would such a pricing scheme be positively perceived by customers? Next we propose a service model which, subject to the above pricing scheme, can be attractive for customers and DCs. 5.3. Elastic Energy-Aware Calendar-driven Services (EEACD) As DCs may host IT services that are mission-critical for the tenants’ businesses, these may demand stringent performance requirements. As argued, however, many would adhere to relaxing their performance indicators during low utilization periods –as long as certain levels (and the availability and uptime of their services) were guaranteed– in exchange for a cost reduction. One type of service allowing for this while promoting energy savings and letting DCs adjust power demand upon energy providers’ requests can be as follows. 1. IT customers specify (in a green SLA) the minimum performance level (min) that the DC should grant on a calendar basis (e.g. at each time slot in a week), as well as a maximum one (max), for each parameter and component of its service. Thus min,max may be thought of as vectors, whose dimensions refer to measurable metrics as computing power, RAM, or network bandwidth, etc. 2. The customer is billed as described, depending on an estimate of the energy spent and the energy rate r. 3. The DC commits to offer elasticity: if service loads surpass their capacity, additional resources (e.g. CPU power) are allocated, within the min/max bounds. 4. For a DC to (further) cut its energy demand when requested by its EP, a second calendar specifies another set of min/max values for each IT service. We refer to the first calendar as the regular calendar (RC), and call the second, the energy-saving calendar (ESC). The DC commits to apply the ESC no more than a certain fraction of the time, e.g. 3.3% (1 day in a month, or 8h a week). During the time the ESC is obeyed, a lower energy rate r0applies. Thus, EP’s rewards can come in the form of a rate reduction from which both a DC and its customers can benefit. 5.4. Can such a service suit customers, DCs and EPs? The attentive reader may wonder about the purpose of a calendar if a DC can dynamically adapt services’ resources to their demands. The role of the calendar is severalfold. First, while DCs employ monitoring tools to efficiently provision resources, migrating or consolidating VMs takes time and resources. The use of a calendar can ease the task of planning ahead and later rearrange computational resources. Second, it can be the basis against which SLA conformance is verified. Most importantly, the min values guarantee customers some minimum performance for their services on one side. On the other hand, these indicate energy-saving opportunities which, if exploited by a DC (e.g. if service loads follow the calendar), can reduce not only the overall power consumption, but also customers’ bills. The role of the max values is that of bounding from above the cost per slot, by preventing the DC from allocating resources in excess. Lastly, busy hours can vary from service to 6
service, each of which can have distinct performance requirements. Specifying a calendar on a per service basis can help to optimize overall service performance and energy consumption. Arguably, one possible downside of this kind of service could be that customers do not know the service fee in advance, as the price per unit time depends on the usage of the service, the DC decisions regarding consolidation and the activation of energy saving measures in response to requests from its EP. While slot prices are unknown, these are bounded from above (due to the max values) by a known quantity (probably close to the fee had the service been provisioned inflexibly for peak utilization). Thus, customers pay no more (and often less) than in case they were charged by allocation, while being granted a relatively high performance due to elasticity. Moreover, slot fees can be reported by the DC in nearly real time in services’ dashboards. Thus, depending on the service, customers can modulate their computational loads. Lastly, in case of commercial customers, the more utilized a service is, the higher its bill, but also the higher their tenants’ revenues, and vice-versa. Companies may positively perceive this service as a safe way to mitigate financial bleeding in case of business failure. How about DCs? By including energy costs into service prices, data centers can keep their profits independent of the fluctuations in services activity and not be economically affected by energy-saving measures. It can also reduce their financial risk and ensure a predictable and measurable ROI. In addition, for reasons of environmental awareness, a growing number of conscious customers may choose green data centers in front of other options, even if at higher tariffs, altruistically. Thus, a DC adopting the above services may even see its customer base enlarged. On the other hand, if customers defrayed their energy costs, what would be the incentives of DCs to save energy? First, in the proposed scheme, not all energy costs of a DC need to be charged to customers (e.g. lighting and part of cooling). Most importantly, customer bills will depend on the cost of the energy spent by their services, which depend on their load, but also on how energy-efficient a DC is and the cost of energy. Thus, DCs adopting the proposed service may still strive to be as energy-efficient as possible to offer competitive prices. Hence, the scheme is such that all the participants of the DC ecosystem are induced to save energy. IT customers, to lower their costs (and widen their profit); DCs to stay as competitive as possible by purchasing efficient equipment, keeping up with eco-friendly technological advances and collaborating with EPs to get discounts and offer more economic tariffs to customers; and EPs by avoiding peak demands and thus maintaining the stability of the electricity distribution grid. In the sequel, we aim at understanding the extent to which this scheme can be attractive for DCs and their customers and the energy be reduced. Next, we discuss additional benefits and the requirements from a technical perspective. 5.5. Additional benefits There is an increasing environmental awareness of business activities, and the IT sector is not an exception. Corporate social responsibility, codes of conduct, and other forms of self-regulation currently include energy consumption and CO2 emissions. The ISO 14000 standards define the methodology for accounting the environmental impact of companies and help businesses comply with regulations or self-imposed goals. ISO 14604 [31], in particular, provides tools for quantifying GHG emissions, and is used by public or independent entities (e.g. the Carbon Trust in the UK [32]) to certify carbon footprints. EMAS (Eco-Management and Audit Scheme) [33], developed by the EU, is another example of greenness certification, and includes the ISO 14001 recommendations. Finally, international treaties such as the Kyoto Protocol have established limits on CO2emission volumes, whose rights can be traded; which establishes market-based incentives to reduce GHG. The proposed paradigm permits and incentivizes energy savings and cleanness. As all the participants could be required to meet such regulations, they all may benefit from it. The main benefit for EPs may be the possibility of reducing peak demands at times when the energy production structure is under stress, due to a shortage or because the energy mix is biased towards fossil-based sources. This can result in a more reliable, stable and safer energy grid, and less penalties for an EP, which will then reach its environmental goals more easily. 5.6. Technical requirements Deploying the service type proposed requires: a) measuring the amount of resources utilized by services 2) scaling physical resources to load (e.g. by migrating/consolidating VMs), and 3) measuring/estimating the energy consumed by services. The first two requirements are readily covered in today’s DCs. Many tools exist to monitor CPU loads, memory usage or network traffic. The time scales at which the monitoring should be performed in the above services (several seconds or minutes) are compatible with the performance of such tools, whose overhead is within acceptable levels at those timescales [34]. On the other hand, to consolidate and perform live VM migrations, cloud providers already employ open source and commercial products2, most of which come with monitoring functions built in. Typically, migration and consolidation times are on the order of a minute or less [35] [36], which may be acceptable for the above services. Also, VM migration: 1) may cause an interruption in the service or lengthen the execution time of jobs, and 2) causes extra load (and thus energy consumption) at the origin and destination servers. However, modern techniques minimize service interruption, and the increase of CPU load and power consumption of the destination server may be in the order of 20% according to [35][36]3. Measuring the power and energy consumed by servers (and network equipment) can be performed directly with dedicated hardware, or indirectly from analytical models. Racks usually include PDUs able to report (via SNMP) the power consumed of each server at a second resolution [37]. Indirect methods use 2E.g. IBM’s System Planing tool, VMware’s Distributed Resource Scheduler (DRS), Rackwise’s DCiM, or the OpenStack suite 3The figures refer to servers with Intel Xeon E5620 4-core CPUs at 2.40GHz, but the relative increase can be extrapolated to other models/vendors. 7
properly parameterized and trained models to estimate the consumption of servers from a measured figure of CPU utilization [38]. Thus, the power and energy spent by services can be estimated from such figures and models in conjunction with the measures of the resources they spent. For instance, in case of servers, if a certain VM has utilized ¯u% of a CPU core on the average during a time slot of Tseconds, the energy consumed can be estimated by ˆe=T(Wmax −Wmin)¯u Ncores +ξ(Wmin), where the first term corresponds to the fraction of the server’s dynamic power range apportionable to the VM (as per (1)) and ξ(Wmin) the share of the server’s active-idle power attributed to the VM, which may be derived in several ways. The logic we employed in our simulations was to split Wmin among all the VMs hosted in a server proportionally to their minimum share of CPU reserved, which is the inverse of the consolidation ratio. The above only accounts for server energy. Regarding other important energy sinks (network components and specially cooling), similar estimates can be derived. For instance, router and switches figures can be weighted by traffic volumes, readily measured. For simplicity, in our simulations we consider these to be proportional to that of servers. 6. Studying the feasibility and advantages of the approach To assess the benefits and downsides of the proposed scheme, we need to understand the extent to which energy expenditure at the DC may be reduced due to calendaring and a DR collaboration with EPs, the impact on service performance and if the resulting prices may be worthwhile and competitive. To that end, we consider three factors (energy, power and performance indicators) to compute prices according to our scheme. Then, we compare the outcome against those obtained in case SLAs were inflexible, prices independent of energy expenses and the power demand not adapted. Of the above, experienced performance is the hardest to quantify, given the distinct nature and purpose of services, their variety, and the number of factors potentially influencing. Moreover, aspects like user satisfaction and perception come into play, which entail the use of utility functions to be assessed. For modeling purposes, services can be categorized depending on whether they are up on a continuous basis or sporadically. Thus, a DC may host always-on services or time-scoped ones. Examples of the first kind abound and are those offered by traditional computing, such as e-mail, web or database, which, deployed in bare-metal or as VMs (i.e. as IaaS), are typically offered to a large set of users, have a direct or indirect revenue and require 24x7x365 uptimes. Services of the second kind may last for a limited period and could include from the execution of high-demanding simulations, batch processes, management tools (backup or antivirus), user-oriented remote desktops, to VMs instantiated to dynamically scale services, as computing platforms like MapReduce/Hadoop permit for data mining purposes, or Cassandra and alike for distributed databases. Services can also be classified, depending on how load is serviced, into workload-conservative and non-conservative. In the former, demands cannot be lost but delayed, as occurs with simulations, backups or an antivirus scans. In the latter, unsatisfied loads are lost. These include streaming, web, real-time collaboration systems. As a first approximation, our simulation study considers always-on and time-scoped services but only of the workload non-conservative type. 6.1. Measuring service performance IT services may consist of several components, each conducting a distinct task. Deriving a generic metric that quantifies the performance exhibited by one such component is hard, and so is one that reflects that by a service as a whole. Indeed, the assessment performance in virtualized environments is an active area of research [39]. Several functions Pmay be used as performance scores. Next, we discuss the rationale behind the one we chose, which is suitable for workload non-conservative services and balances generality and simplicity. Recall that the purpose is not quantifying application performance in absolute terms but rather comparatively, to see the effect of adjusting service resources according to calendars or EP requests. When a DC provisions some component (of some class), it allocates a certain amount of resources (e.g. disk space, memory, and a certain share of a CPU/core in VMs) which, apart from enabling the service, guarantee that some performance indicators fulfill those dictated by SLAs (e.g. the min vectors of calendars). For simplicity, suppose that a service is composed of a single VM. The performance experienced by a service P can be modeled as a function of three variables at each point in time: 1) the amount of resources (of some kind) allocated to a service an, 2) the amount of such resources demanded dn, and 3) the quantity of such resources utilized un. In these terms, and irrespective of the performance score P employed, it is reasonable to accept that: I. un≤dn, i.e. utilization cannot exceed demand. II. If a service exactly utilizes what it requires, un=dn, then performance Pmust be highest (e.g.1 or 100%) and monotonically decrease as undeviates from dn. III. In case the system provides resource allocation guarantees: 1. If the demand does not exceed the allocation (dn≤ an), all the demanded resources are granted (un= dn), implying P=1. 2. If it does, at least the resources allocated are granted; and more in case spare resources exist and the system allows them to be borrowed (un≥an). The above considerations mean that, under resource guarantees, in the worst case, un=min an,dnand P|dn≤an=1, regardless of how P is defined. A familiy of functions satisfying the above conditions is P∗ n(un,dn)=un dnα,∀α≥1, as P∗ n(un,dn)=min(an,dn) dnα =min 1,an dnα is 1 for dn≤anand, otherwise, decreases as an dnα, with α governing the rate of decay as demands surpass guaranteed resources (or undeviate from dn). In our simulation study we take 8
α=1, as then P∗represents a measure of relative throughput. We also compute the average performance of a service running over Sslots as ¯ P∗=1 SPS n=1P∗ n. In this regard, note that we can write ¯ P∗=1 SP dn≤an 1+P dn>an (an/dn)α≥1 SP dn≤an 1=β. where βis the fraction of time where dn≤an. This has an important implication in our context. Whether services are sensitive or not to resource exhaustion (value of α), if calendars accurately reflect service loads (i.e. dn) or the DC can quickly scale resources (an), service degradation may be small on the average, while achieving energy savings and lowering prices. 7. Simulation environment Several DC/cloud simulators exist in the literature, which focus on distinct aspects of DC scenarios. CloudSim [40] is oriented to the dimensioning and modelling of cloud environments (and federations) and the evaluation of resource provisioning algorithms. DCWorms [41] is a recent tool able to compute the performance and energy consumption of DCs using diverse consumption models and workloads. It can be used also for the thermal optimization of the physical location of the equipment in the DC room. GreenCloud [42] is an extension to the ns-2 simulator and models accurately the DC’s network traffic patterns. Although all of the aforementioned tools are able to calculate the power consumption of a DC, none of them fitted our needs (or were difficult to extend) regarding the key aspects of our approach: the calendars, the treatment of EP requests, elasticity in the resource allocation, and the economic costs involved. Thus, to evaluate the feasibility of our proposal, we developed our own simulator of the DC-EP ecosystem. 7.1. Our simulator: inputs, outputs and internal behaviour Our simulator represents a DC by a collection of physical servers and simulates the execution of IT services placing some workload on them. Workload varies in two dimensions. First, the number of VM instances changes over time: there is a substrate of some number of always-on VMs (which may represent IaaS-type services or entire physical servers), plus a variable number of time-scoped ones, of distinct durations arriving spread in time. Second, the CPU demand placed by each at every time slot (i.e. our dnin §6.1) varies according to some pattern. Slot durations are configurable. To emulate GreenSLAs and calendars, a file specifies, for each IT service, the min/max performance levels required at every slot, in regular regime (RC calendar) or energy-saving (ESC calendar), to apply for some time when a DC accepts to cut its consumption on an EP request. When that occurs, the tool can also simulate the effect of delaying tasks (e.g. the execution of backups or antiviruses) or the start of VMs, as additional measures. Calendars’ min/max values correspond to consolidation ratios CR. Thus, a minCR=4 (of a certain server type) means that a VM should get 1 4th of a core; i.e. it should be granted an=25% of its capacity. The simulator employs these values to assign services to servers (as discussed next) and thus determine: the overall number of servers required, a performance score for each service at each slot (considering dnand the utilization unactually observed after the allocation), the overall CPU load of each server, its energy expenditure, and the energy apportioned to each service. To that end, the simulator models servers’ power-utilization curves as per (1), and computes servers’ power/energy expenditures per slot, Wnfrom their overall utilizations (equal to the sum of the unof the services hosted). Similarly, the energy spent by a service is derived from the unas discussed in §5.6. To be as realistic as possible, server’s parameters (Wmin, WMax and Widle, and number of cores) were chosen from data in [9] for several platforms. In particular, the three types of servers used in the simulations were IBM x3250 M3, HP ProLiant DL360, and Dell PowerEdge R720. To account for other energy expenditures (e.g. cooling, network) we assumed that these spent power proportionally to servers, according to PUE=2. Note that this has no effect for comparison purposes. The simulator underwent an extensive validation and tuning phase where its output was contrasted against the power/energy consumption measured in two DC testbeds with real servers and realistic load patterns. This revealed that the simulator can accurately reproduce the results found in real equipment. 7.2. Simulating service-to-server assignment The simulator implements several strategies regarding VM placement for comparison purposes. As said, calendars’ min/max values refer to consolidation ratios, CR. From the CR values of each VM, the simulator assigns VMs to servers by ordering CRin ascending order and assigning them to the first server they fit in. This first-fit approximation to the bin-packing problem is not optimal and may require more servers than those strictly needed. However, it is easily implemented and known to require a number of servers below twice the number of the optimal case [43]. As the same method is used with and without our proposal, we expect this to hardly influence the comparison. 7.3. Simulating elasticity To simulate elasticity (i.e. the ability of a DC to adapt resources according to services’ demands), the simulator proceeds as follows. Note that, while in our discussion in §6.1, we spoke of demands dn(e.g. CPU cycles), these may not be measurable metrics, particularly in workload non-conservative services. Instead, a DC may be able to monitor only the extent to which resources are utilized (un) at each slot. Thus, our simulator tries to scale VM’s CRaccording to their observed CPU utilization levels un. However, since the burstiness of unsamples may exhibit high variations from slot to slot, we compute a moving average of each service utilization as ˆun=ˆun−1W+un W+1 to filter out high frequency components. The smoothness (and reactivity) of this average is controlled by W, which defaults to 10 slots. Moreover, in practice, migrating/consolidating VMs very frequently may impose high penalties and is thus unrealistic. To account for this, the simulator is forbidden to adapt a VM’s CRmore frequently than every Kslots (e.g. 30 minutes). Given these considerations, elasticity is implemented by comparing services’ ˆunas follows. Recall that there is a 1-to- 1 correspondence between consolidation factors CRand shares 9
Ramón y Cajal fellowship holder at UPC. David Remondo has published 12 full papers in international research journals and has participated in more than fifteen evaluations of research projects co-funded by the European Commission. His research interests lay in the area of communication networks, mainly in heterogeneous networks, energy saving issues and performance evaluation. Giovanni Giuliani graduated in Electronics Engineering with honors in 1982, and has over 30 years of working experience in R&D, IT Consulting and System Integration in major Computer Companies (Olivetti, Digital, Compaq, HP). He has covered various positions in SW Engineering until 1997, working on Operating System development and Manufacturing Framework products; he has been nominated Consulting Engineer by Digital Corporate Engineering Board in 1992. In parallel to his job in the industry, Giovanni performed university teaching and research activities from 1988 to 1993 at Engineering and Computer Science universities in Italy (Milan and Como). Starting from 1998 - as Solution Architect in Consulting and System Integration organization in Digital, and then, due to the mergers, Compaq and finally HP – he delivered several complex projects in Manufacturing, Government, Finance market, then exploring the area of Mobility for various sectors. Back in 2005 he joined the HP Italy Innovation Center, where he's been leading the Cloud Computing Initiative since 2009. Starting from 2013 he serves as Lead Architect of the HP LIFE platform (HP worldwide program offering a cloud based e-learning initiative for entrepreneurs). During the last decade, he has been involved in several research projects funded by European Commission in the area of Mobility, e-Collaboration, Cloud Computing and more recently he is technical coordinator in a sequence of 3 Green-IT research projects (FIT4Green, All4Green and now DC4Cities).