Improvement of an old villa’s energy efficiency in Sweden: case study

Alay Ferrarons, Carles

Abstract

Energy prices are of great concern for homeowners and companies, and the implementation of energy efficiency measures has gained importance in recent years as means of mitigating these costs. Energy surveys are useful to analyze and tackle energy inefficiencies, with a focus on the primary issues and the identification of solutions. The objective of this project was to conduct an energy survey of a 1971 villa in Älvkarleby with the aim of identifying the main contributors to energy losses and proposing measures through a quantitative approach. This involved collecting data from the rooms, manual calculations, and the use of a simulation model of the dwelling. Results show that the primary sources of energy loss in the dwelling are the envelope components, particularly the basement walls and windows. While these issues should be addressed, both options are not economically viable in a 15-year period. However, the installation of a ground source heat pump (GSHP) and photovoltaic (PV) panels yielded a net profit over a 15-year period. The implementation of these systems resulted in an annual saving of 13 005 SEK. Moreover, the final use of electricity from the grid for heating purposes is 6.2 MWh/year, which represents a reduction of almost 76 % compared to the previous purchased energy.

Full text

FACULTY OF ENGINEERING AND SUSTAINABLE DEVELOPMENT Department of Building Engineering, Energy Systems and Sustainability Science Carles Alay Ferrarons 2024 Student thesis, Advanced level (Master degree, one year), 15 HE Energy Systems Master Program in Energy Systems Supervisor: Arman Ameen Assistant supervisor: Roland Forsberg Examiner: Mathias Cehlin Assistant examiner: First name Last name Improvement of an old villa’s energy efficiency in Sweden: case study. Subtitle of your thesis, if any i Cover picture: Aerial photo of the northern façade and roof of the study house in Älvkarleby: Carles Alay Ferrarons, 2024. ii Preface As an industrial engineer specializing in energy systems, I was looking forward to applying the concepts I have learned in my master’s program to increase the energy efficiency of a dwelling, thus contributing to a greener future. I would like to express my gratitude to Roland Forsberg, who has helped me with his experience in both theoretical concepts and data collection, as well as access to the necessary equipment. Also, his willingness to meet regularly to discuss the project. I would also like to use these lines to thank Arman Ameen for his tutoring and guidance for this project. Furthermore, I would like to acknowledge his feedback and tips, which were highly valuable for the project. I am most grateful to Karl-Otto for his hospitality and for providing the dwelling for the project. Finally, I wish to express my gratitude to my family for their invaluable support in enabling me to live in Sweden and pursue this project, their support and comprehension in every step of the project. iii Nomenclauture Abreviations and acronyms GSHP Ground source heat pump NPV Net Present Value PV Photovoltaic SMHI Swedish Meteorological and Hydrological Institute SVEBY Swedish Agency for Standarization and Verification of Energy Performance in Buildings BBR Swedish Building Regulation (Swedish: Boverkets byggregler) iv Abstract Energy prices are of great concern for homeowners and companies, and the implementation of energy efficiency measures has gained importance in recent years as means of mitigating these costs. Energy surveys are useful to analyze and tackle energy inefficiencies, with a focus on the primary issues and the identification of solutions. The objective of this project was to conduct an energy survey of a 1971 villa in Älvkarleby with the aim of identifying the main contributors to energy losses and proposing measures through a quantitative approach. This involved collecting data from the rooms, manual calculations, and the use of a simulation model of the dwelling. Results show that the primary sources of energy loss in the dwelling are the envelope components, particularly the basement walls and windows. While these issues should be addressed, both options are not economically viable in a 15-year period. However, the installation of a ground source heat pump (GSHP) and photovoltaic (PV) panels yielded a net profit over a 15-year period. The implementation of these systems resulted in an annual saving of 13 005 SEK. Moreover, the final use of electricity from the grid for heating purposes is 6.2 MWh/year, which represents a reduction of almost 76 % compared to the previous purchased energy. Keywords: “energy survey”, “dwelling”, “Sweden”, “cold climate”, “heat transmission”, “PV panels”, “ground source heat pump”. v vi Table of contents 1 Introduction ............................................................................................... 10 1.1 Background.......................................................................................... 10 1.2 Literature review ................................................................................... 11 1.3 Aims .................................................................................................. 14 1.4 Approach ............................................................................................ 14 2 Theory ..................................................................................................... 15 2.1 Heat losses........................................................................................... 15 2.1.1 Power .......................................................................................... 15 2.1.2 Energy ......................................................................................... 15 2.1.3 Thermal bridges .............................................................................. 16 2.2 λ-method ............................................................................................ 16 2.3 Internal generation of heat ........................................................................ 16 2.4 Ventilation losses ................................................................................... 17 2.4.1 Effect ........................................................................................... 17 2.4.2 Energy ......................................................................................... 17 2.5 Hot tap water ....................................................................................... 17 2.6 Solar radiation ...................................................................................... 18 2.7 Heat balance of the building ...................................................................... 18 2.8 Duration diagrams ................................................................................. 19 2.9 Normal year correction ........................................................................... 20 2.10 Investments: NPV .................................................................................. 20 3 Method .................................................................................................... 22 3.1 Study object ......................................................................................... 22 3.2 Measurements ...................................................................................... 22 3.3 Numerical simulation: IDA ICE .................................................................. 23 3.4 Retrofit measures .................................................................................. 25 3.4.1 Ground Source Heat Pump (GSHP)....................................................... 25 3.4.2 PV panels ...................................................................................... 25 3.4.3 Add insulation on the basement’s surfaces................................................ 26 3.4.4 Windows ...................................................................................... 27 4 Results and discussion ................................................................................... 29 4.1 Measurements with the meters ................................................................... 29 4.1.1 Indoor climate conditions (temperature, humidity, and CO2) ........................ 29 4.1.2 Mechanical flow .............................................................................. 30 4.1.3 Thermal bridges .............................................................................. 30 4.2 Energy gains ......................................................................................... 31 4.3 Energy losses ........................................................................................ 33 4.4 IDA ICE simulation ................................................................................ 36 4.5 Energy measures.................................................................................... 40 4.5.1 Ground Source Heat Pump (GSHP)....................................................... 40 vii 4.5.2 PV panels ...................................................................................... 41 4.5.3 Add insulation on the basement’s surfaces................................................ 43 4.5.4 Windows ...................................................................................... 44 4.6 CO2 emissions reduction .......................................................................... 45 5 Conclusions ............................................................................................... 47 5.1 Study results ........................................................................................ 47 5.2 Outlook .............................................................................................. 47 5.3 Perspectives ......................................................................................... 48 References ....................................................................................................... 49 Appendix A: Floor plans of the dwelling ................................................................... A1 Appendix B: U-value calculations ............................................................................ B1 Appendix C: Energy balance calculations .................................................................. C1 Transmission losses ......................................................................................... C1 Power ..................................................................................................... C1 Energy .................................................................................................... C3 Ventilation losses ........................................................................................... C4 Power ..................................................................................................... C4 Hot tap water ............................................................................................... C6 Solar radiation............................................................................................... C7 Internal heat generation ................................................................................... C7 Normal year correction .................................................................................... C8 Heat balance ................................................................................................. C8 Appendix D: Meters information ........................................................................... D1 viii List of figures Figure 1: Sweden energy use per sector in 2022 (Swedish Energy Agency, 2023). .......... 10 Figure 2: Duration diagram (DUT) representation for different outdoor mean temperatures (Nilsson and Commtech Group, 2003). ............................................................. 19 Figure 3: DUT diagram with ICH (Nilsson and Commtech Group, 2003). ................... 19 Figure 4: PV energy generation throughout the year with constant energy demand for the current situation and with the inclusion of a GSHP. ............................................... 26 Figure 5: Living room results for indoor climate conditions. .................................... 30 Figure 6: Bedroom results for indoor climate conditions. ........................................ 30 Figure 7: Normal and thermal picture of the southern living room in the main floor. ....... 31 Figure 8: Normal and thermal picture of the basement living room. ........................... 31 Figure 9: Heat energy input of the dwelling broken down by source. .......................... 32 Figure 10: Solar radiation heat coming through the two-glaze windows surrounding the dwelling in Wh........................................................................................... 32 Figure 11: Monthly solar energy provided to the dwelling, excluding summer months (mid- May to mid-September). ............................................................................... 33 Figure 12: Losses contribution to power needs of the dwelling, in kW. ....................... 34 Figure 13: Heat power losses [MWh] of the dwelling for its various sources and their contribution in percentage for the year 2023. ...................................................... 34 Figure 14: Area and u-value times area for each surface of the envelope of the dwelling.... 35 Figure 15: Heat loss contribution [MWh] for the various ventilation categories. ............. 36 Figure 16: Bought energy to heat the dwelling throughout a year (IDA ICE model). ........ 36 Figure 17: Representation of the temperatures in the main bedroom throughout the year. 37 Figure 18: Representation of the temperatures in the living room throughout the year. .... 37 Figure 19: Representation of the temperatures in the kitchen and dining room throughout the year. ................................................................................................... 37 Figure 20: Total heating demand of the dwelling throughout the year. ........................ 38 Figure 21: Energy losses through the different parts of the dwelling. .......................... 38 Figure 22: Representation of energy gains and losses throughout the year,with the same legend as in Figure 21. .................................................................................. 39 Figure 23: Energy losses through the envelope by surface area. ................................. 39 Figure 24: Payback period for the GSHP with a 4 % interest rate and 15 year use. .......... 41 Figure 25: Energy obtained from solar radiation with a 6 kW system throughout a year. .. 41 Figure 26: Payback period for the PV panels investment during the 20 years of use. ........ 42 Figure 27: Payback period for the insulation with a 4 % interest rate and 15 year use....... 43 Figure 28: Payback period for the windows’ replacement investment during the 15 years of use.......................................................................................................... 44 15 2 Theory Heat can be transferred between bodies through conduction, convection, and radiation (Moshfegh, 1992). Buildings provide protection to occupants from the exterior through various layers, which may vary depending on the climate conditions. In colder climates, these layers prevent heat from escaping from the rooms, helping reduce the amount of supplied heat required to keep the rooms warm. These layers can be of various types, but all have a certain thermal resistance that prevents heat from escaping. Light insulation materials have a lower thermal resistance, while heavy insulation have a higher thermal resistance. The thermal resistance of a material is typically defined by its U-value, measured in W/m2·°C (Kim et al., 2023). Boverket provides building regulations in Sweden. Their document contains mandatory provisions as well as some general recommendations in different areas, such as accessibility, dwelling design, mechanical resistance safety in case of fire and energy management (Borveket, 2019). In this part of the work, some equations and concepts are clarified for their relevance in the energy audit. 2.1 Heat losses 2.1.1 Power As previously stated, a temperature difference between the exterior and the interior of the dwelling result on a heat flux in which heat losses occur. The materials of the walls, roof, doors, windows, etc. form the envelope, which prevents heat from escaping. Transmission losses can be calculated with the following equation: 𝑄𝑡=∑ (𝑈𝑖·𝐴𝑖)·(𝑇𝑖𝑛 −𝑇𝑜𝑢𝑡) 𝑛 𝑖=0 [W] Eq. 1 In Eq. 1, U stands for the thermal transmittance [W/ m2·°C], A is the area of the surface [m2], Tin is the indoor temperature [°C] and Tout is the outdoor temperature [°C] (ASHRAE, 2017b). 2.1.2 Energy While power is related to how fast energy is used or transmitted, energy is the ability to create a change or movement, and it considers the time needed to do so. Since outdoor conditions are not constant throughout the year, degree-hours are used in the calculation of the energy that escapes through a surface (ASHRAE, 2017a): 16 𝐸 =∑ (𝑈𝑖·𝐴𝑖)·°ℎ 𝑛 𝑖=0 [Wh] Eq. 2 Here, °ℎ stand for the degree hours [h], which is obtained by the DVUT diagram and takes into consideration the average temperature in Älvkarleby. According to the Swedish Meteorological and Hydrological Institute (SMHI), the average outdoor temperature in this regions has a value of 6.22 °C for the year 2023 (SMHI, 2023). 2.1.3 Thermal bridges Transmission losses through the building’s envelope occur not only through the walls, but sometimes in junctions and corners. These heat losses are called thermal bridges and are contemplated in Eq. 3: 𝐸𝑡ℎ_𝑏 =(∑𝛹𝑇𝐵 ·𝐿𝑖+∑𝑋𝑗 𝑚 𝑗=0 𝑛 𝑖=0 )·°ℎ [Wh] Eq. 3 These transmission losses can be punctual (𝑋𝑗 factor) or one dimensional (𝛹𝑇𝐵 factor). However, thermal bridges can be taken into consideration when outside areas of the building are used to calculate the envelope transmissions instead of the internal areas, which is the applied method in this project. 2.2 λ-method U-values are usually calculated by adding the thermal resistance of the materials in each layer, the values of which can be found in the SVEBY collection files (SVEBY, 2024). Occasionally, materials are combined within the same layer, and their total thermal conductivity differs from the theoretical one. There are two methods to calculate the new conductivity value: the U-value method and the λ-method. For this project the λ-method will be used. This method involves calculating the total λ by weighing the λ of each material with its representative share: λtotal =λ1·α+λ2·β [W/m·K] Eq. 4 In Eq. 4, λ represents the thermal conductivity of each material, while α and β stand for the share of that material in the insulation layer (where α + β = 1). 2.3 Internal generation of heat In the interior of the building there is also internal heat generation, mainly generated by human activity, electric equipment (lighting, stove…) and solar radiation during daytime (Nilsson and Commtech Group, 2003). According to SVEBY, a person emits about 80 W of heat, and electric equipment has thermal losses of about 70 % of their energy use (SVEBY, 2024). 17 A study that analyses different households in Sweden and their energy use, estimates that single-family dwelling use about 30 kWh/m2 of energy annually (Mata, Sasic Kalagasidis and Johnsson, 2013). 2.4 Ventilation losses Ventilation is necessary to introduce fresh air to the interior of the building. Usually, households are not airtight, and air enters and exits through leaks. This is known as natural ventilation since no energy is required to ventilate a space. However, in some buildings, ventilation is achieved mechanically, using a fan to regulate the amount of air that enters and/or exits (Nilsson and Commtech Group, 2003). 2.4.1 Effect 𝑃 =𝑞·𝜌·𝐶𝑝·∆𝑇 [kW] Eq. 5 Here, 𝑃 stands for the effect or power [kW], 𝑞 is the airflow in [m3/s], 𝜌 is the air density [1.2 kg/m3], 𝐶𝑝 is the heat capacity [1.005 kJ/kg·K], and ∆𝑇 is the temperature difference [K] (ASHRAE, 2017a). 2.4.2 Energy 𝐸 =𝑞·𝜌·𝐶𝑝·°ℎ [kW] Eq. 6 In Eq. 6, 𝐸 stands for the energy [kWh] and °ℎ is the degree hours. This equation is useful when a certain period is studied (ASHRAE, 2017a). 2.5 Hot tap water Some of the generated heat is used to warm water for consumption, which is considered a thermal loss, since part of the heat is dedicated for another purpose rather than heating the household. For approximation purposes and based on Roland Forsberg’s experience in the energy audit field, a third of the total volume of cold water used in a year is used to heat water. 𝑞ℎ𝑜𝑡_𝑤𝑎𝑡𝑒𝑟 ≈𝑞𝑐𝑜𝑙𝑑_𝑤𝑎𝑡𝑒𝑟 3 [m3/s] Eq. 7 𝑞ℎ𝑜𝑡_𝑤𝑎𝑡𝑒𝑟 is the water flow of hot water and 𝑞𝑐𝑜𝑙𝑑_𝑤𝑎𝑡𝑒𝑟 is the water flow of cold water, both expressed in the same units. The energy used to heat cold water can be obtained with Eq. 8: 18 𝐸ℎ𝑜𝑡_𝑤𝑎𝑡𝑒𝑟 =𝑞ℎ𝑜𝑡_𝑤𝑎𝑡𝑒𝑟·𝜌·𝐶𝑝·∆𝑇 3600 [kWh] Eq. 8 𝐸ℎ𝑜𝑡_𝑤𝑎𝑡𝑒𝑟, is the amount of energy required to heat 𝑞ℎ𝑜𝑡_𝑤𝑎𝑡𝑒𝑟, obtained from the previous equation (Eq. 7). 𝐶𝑝 is the heat capacity, with a value of 4.184 kJ/(kg·K), 𝜌 is the density of the fluid (1 000 kg/m3), and ∆𝑇 the difference between the inlet temperature and the supply temperature. 2.6 Solar radiation Solar radiation contributes to heating the household. Irradiation can enter the building through the windows. Although solar radiation peaks at approximately noon when the sun is at its highest position, the building has some temperature inertia that causes the heat peak load to occur some hours later (Nilsson and Commtech Group, 2003). Solar radiation is taken into consideration during the months when heating is needed, which is from mid-September to mid-May. In the remaining months, heat does not contribute to reaching 20 ˚C, but rather results in a heat excess. 𝐸𝑠𝑜𝑙𝑎𝑟 =𝐴·𝐼·𝑟·𝑐·𝑑 [Wh/month] Eq. 9 Eq. 9 represents the solar energy obtained each month. It is necessary to calculate this equation for each independent month, as values may vary. 𝐸𝑠𝑜𝑙𝑎𝑟, expressed in [Wh/month], represents the solar energy obtained for a certain month. 𝐴 stands for the windows area, 𝐼 is the average solar radiation energy per day of the month [Wh/m2·month], 𝑟 represents the sun radiation factor, 𝑐 stands for the cloud factor, and 𝑑 is the number of days for that specific month. 2.7 Heat balance of the building The temperature in a room is directly related to the heat generated, supplied or extracted from that space. In order to maintain a certain temperature and create comfort, the supplied heat must vary. 𝐸𝑖𝑛 =𝐸𝑜𝑢𝑡 [MWh] Eq. 10 𝐸𝑖𝑛 =𝐸ℎ𝑒𝑎𝑡𝑖𝑛𝑔 +𝐸𝑠𝑜𝑙𝑎𝑟 +𝐸𝑝𝑒𝑜𝑝𝑙𝑒 +𝐸𝑒𝑞𝑢𝑖𝑝𝑚𝑒𝑛𝑡 [MWh] Eq. 11 𝐸𝑜𝑢𝑡 =𝐸𝑡𝑟𝑎𝑛𝑠 +𝐸𝑣𝑒𝑛𝑡 +𝐸ℎ𝑜𝑡_𝑤𝑎𝑡𝑒𝑟 +𝐸𝑢𝑛𝑐_𝑣𝑒𝑛𝑡 [MWh] Eq. 12 Supplied energy (𝐸𝑖𝑛) is the sum of energy introduced by the heating system (𝐸ℎ𝑒𝑎𝑡𝑖𝑛𝑔), the solar radiation (𝐸𝑠𝑜𝑙𝑎𝑟), energy produced by the occupants of the household (𝐸𝑝𝑒𝑜𝑝𝑙𝑒), and the waste energy from the electric equipment (𝐸𝑒𝑞𝑢𝑖𝑝𝑚𝑒𝑛𝑡). 19 Losses of heat (𝐸𝑜𝑢𝑡) are the sum of the losses through the building’s envelope surfaces (𝐸𝑡𝑟𝑎𝑛𝑠), losses from natural ventilation (𝐸𝑣𝑒𝑛𝑡), energy used to heat water for consumption (𝐸ℎ𝑜𝑡_𝑤𝑎𝑡𝑒𝑟) and uncontrolled losses that escape the envelope (𝐸𝑢𝑛𝑐_𝑣𝑒𝑛𝑡). 2.8 Duration diagrams These diagrams represent the exterior temperatures of a specific location, taken every hour and arranged in ascending order (Figure 2). They can be used to determine the amount of heat required for a house based on its internal heat generation. This is calculated using the heat balance equation (Eq. 10), which considers both the heat supplied and lost to bring the internal temperature of the building to 20 ˚C (Nilsson and Commtech Group, 2003). FIGURE 2: DURATION DIAGRAM (DUT) REPRESENTATION FOR DIFFERENT OUTDOOR MEAN TEMPERATURES (Nilsson and Commtech Group, 2003). In the case of buildings in cold climates, there are usually no specific requirements for upper limits on room temperature, and temperature control systems only provide heat. When high temperatures are reached, occupants can ventilate the rooms by opening the windows to achieve comfort. In Figure 3, for instance, ventilation would be needed above the Internal Heat Characteristic (IHC) line, whereas heating would be supplied under it (Nilsson and Commtech Group, 2003). FIGURE 3: DUT DIAGRAM WITH ICH (Nilsson and Commtech Group, 2003). 20 The internal heat generation is represented by the distance between ICH and the 20 ˚C line, and the junction between the ICH and the outdoor temperature is the balance temperature. Heat us supplied below this temperature. 𝑇𝑏=𝑇𝑖−𝑄∗ 𝐻𝑣+𝐻𝑡 [ºC] Eq. 13 𝑇𝑖 is the indoor temperature (20 ºC), 𝑄∗ stands for the internal generation power, and 𝐻𝑣 and 𝐻𝑡 are the heat losses due to ventilation and air leakages, and transmission, respectively. 𝐻𝑣 and 𝐻𝑡 can be calculated with the following equations: 𝐻𝑣=[(1−𝜂)·𝐹]·𝜌·𝐶𝑝 Eq. 14 𝐻𝑡=∑(𝑈𝑖·𝐴𝑖) 𝑛 𝑖=0 +∑𝛹𝑇𝐵 ·𝐿𝑖+∑𝑋𝑗 𝑚 𝑗=0 𝑛 𝑖=0 Eq. 15 In Eq. 14, 𝜂 is the thermal efficiency of the ventilation system (only in mechanical ventilation with heat recovery). In this case, efficiency is 0. 𝐹 stands for the ventilation rate in m3/s. The meaning of 𝜌 and 𝐶𝑝 are the same as in Eq. 6. The meaning of the variables in Eq. 15 are the same as previously stated in Eq. 2 and Eq. 3. To simplify calculations, 𝑋𝑗 is considered to be 0. 2.9 Normal year correction The outdoor temperature varies from one year to another. Therefore, energy use is used to correct the outdoor temperature differences: 𝑄𝑐𝑜𝑟𝑟𝑒𝑐𝑡𝑒𝑑 =𝑄𝑎𝑐𝑡𝑢𝑎𝑙_ℎ𝑒𝑎𝑡 ·𝑆𝑛𝑜𝑟𝑚𝑎𝑙_𝑦𝑒𝑎𝑟 𝑆𝑎𝑐𝑡𝑢𝑎𝑙_𝑦𝑒𝑎𝑟 [MWh] Eq. 16 𝑄𝑎𝑐𝑡𝑢𝑎𝑙_ℎ𝑒𝑎𝑡 stands for the calculated heat. 𝑆𝑛𝑜𝑟𝑚𝑎𝑙_𝑦𝑒𝑎𝑟 is the degree days of a normal year, whereas 𝑆𝑎𝑐𝑡𝑢𝑎𝑙_𝑦𝑒𝑎𝑟 stands for the degree days of the year of study (2022) (Borveket, 2019). 2.10 Investments: NPV The Net Present Value (NPV [SEK]) is a selection method for investments. This method considers the investment and the expected future cash inflows (or savings) over a period to determine whether an investment is worthwhile (positive result) or not (negative). 21 𝑁𝑃𝑉 =∑𝐴𝑖 (1+𝑟)𝑖−𝐼 𝑛 𝑖=0 Eq. 17 𝐴𝑖 are each month’s savings [SEK], 𝑟 is the discount rate [%], 𝑖 is the number of years, and 𝐼 stands for the investment [SEK]. 22 3 Method 3.1 Study object The studied household is an old villa from 1971 located in Älvkarleby, Sweden. The villa –constructed from brick– comprises two floors: the main floor, which is approximately 1 meter above ground level, and the basement underneath. Attached to the main floor there is a wooden-wall garage, which is separated from the living space with a door. The length of the house is oriented east-west, with the main entrance facing north at a slight inclination of 5º. A copy of the original plans of the house can be found in Appendix A. The electric heating system consists of an electric coil that heats water in a tank. This hot water is then distributed through pipes to radiators –placed underneath each window– via the building’s internal heating system. The total heated floor surface area is 205.5 m2. In the attached garage, there is an electric heating system which sets the room temperature to 5 ˚C. The household has a natural ventilation system, but there is mechanical ventilation in the kitchen and adjacent bathroom. The kitchen extractor has three speeds, while the bathroom extractor has only one speed. The dwelling’s annual electricity bill is 9.8 MWh. Additionally, the owner of the house uses 10 m3 of a wood mixture to heat the house during peak energy periods. The owner of the property resides there alone and consumes approximately 47 m3 of water annually, a third of which is heated. 3.2 Measurements During the visits to the house, thermal bridge measurements were taken. This analysis provides insight into their location in the building. The Flir E75 IR-camera is used to identify thermal bridges in various locations within the villa. Thermal bridges are expected to be found in wall and floor junctions, where usually more exterior air infiltrates. This procedure was carried out while extractor fans were at their maximum level, creating an under pressure in the building. This IR-camera is known for its versatility across a wide range of temperatures depending on its use. In its different modes, it can measure in the following ranges of temperatures (˚C): [-20, 120], [0, 650], [300, 1000]. The first mode was used to measure thermal bridges. The camera is renowned for its excellent resolution and sensitivity, and for having an accuracy of ± 2 % of reading for ambient temperature between 15 ºC and 35 ºC and object temperature above 23 0 ºC (see Appendix D). The measurement was conducted on a semi-cold day (11th of April 2024 at 18:30) to facilitate the observation of thermal bridges. Additionally, a mechanical air flow meter (SwemaFlow 233) was used to determine the flow rate at which the mechanical extractors operate by enclosing them within a hood. This meter was calibrated, and the certificate is attached in Appendix D. The extractor in the kitchen is expected to operate at a higher rate than that in the bathroom, given that it is expected to cope with more contamination in a shorter period. To determine the indoor characteristics of the rooms, two CO2 meters were placed in the bedroom and main living room for an 8-day period. During this period, data was measured and stored every 10 minutes. The meters were placed at a distance of one meter from the sofa and bed, with the former at a height of 50 cm and the latter at a height of 1.5 meters. The model Rotronic CL11, which is capable to measure multiple variables simultaneously, including temperature, humidity, and CO2 and store it for later analysis, was selected for the experiment. The device has a measuring range of 0 to 5000 ppm, and an accuracy of ± 30 ppm ± 5% of the measured value at 23 ± 5 ºC 1 . 3.3 Numerical simulation: IDA ICE The IDA ICE software was used to conduct the energy analysis, in addition to manual calculations. This software is a simulation tool used to model various rooms and assess the indoor climate and thermal comfort, as well as the energy use of a building with variable time steps (Xue et al., 2022). Furthermore, it is a valuable tool for conducting sensitivity analysis and comparing energy usage before and after the implementation of the measures. As stated in a project using IDA ICE 4.8: “the software has been validated against the EN 15265-2007 and the EN 13791 standards” (Suhonen et al., 2020). Moreover, it has been used and certified to be able to properly showcase a building’s behavior in recent years (Steen Englund et al., 2020). These reasons resulted in the use of the program for the assessment of the energy audit of the villa. To proceed with the calculations, the base model of the villa was created using the plans the plans of the house and the properties of the floors, walls, roof, windows, and doors (Appendix A). Indoor temperature was set to match that of the house, which is 20 ºC. In addition, the cooling demand was set to 0 kW given that there is no cooling demand, and the air exchange rate of the ventilation system will be deducted from the energy balance. The calculations of the dwelling’s envelope U- values are provided in Appendix B. Other manual calculations of the villa’s energy 1 Rotronic information: https://www.rotronic.com/en-cn/cl11 24 use are provided in Appendix C. Nevertheless, in Table 1 the most crucial input values for the software are presented: TABLE 1: DATA INPUT FOR IDA ICE SOFTWARE TO CREATE THE MODEL. Aspect Data Thermal bridges Internal: 1 value to the left of typical Infiltration General values Extra energy and losses None Ground properties General values Airflow 0.35 L/s·m2 Set temperatures 20-25 ºC (except garret: -20 to 40ºC) Occupation Kitchen and dining room: 3h/day; Bedroom 3: 9h/day; Living room: 12h/day Equipment Laundry room: 75 W, 5h/week (Saturday); Boiler room: 75 W, always on; Kitchen and dining room: 100 W, 3h/day; Living room: 100 W, 12h/day Lighting Kitchen and dining room: 75 W, 3h/day; Bedroom 3: 75 W, always on; Living room: 75 W, 12h/day; Entrance and hall: 75 W, always on Building defaults Same U-values for the dwelling part as the ones calculated by hand, adapting the thickness of the parts Heating systems Heating: default carrier electricity: COP 1 Domestic hot water: default carrier electricity: COP 1 A full-year simulation of the building's energy use was compared to the same year’s energy bill and the calculations in the appendixes to ensure accurate modeling of the household’s energy use. A difference of less than 10 % between the bills and the simulation model should be obtained to consider the model reliable for analyzing the differences in energy use before and after the implementation of the measures. Additionally, manual calculations will also be conducted to verify the numbers and identify any discrepancies between the model and the calculations. This will also help to understand where the greatest losses occur. The dwelling is expected to have an energy use in the vicinity of 25 MWh/year. 31 An analysis on some parts of the building revealed a tendency to elevated heat loss in certain locations. When implementing measures such as increasing the U-value of the walls, it is important to consider the location of these thermal bridges to achieve a more significant impact: - Junctions between walls and roof (Figure 7). - Junctions between walls and floor in the basement (Figure 8). FIGURE 7: NORMAL AND THERMAL PICTURE OF THE SOUTHERN LIVING ROOM IN THE MAIN FLOOR . FIGURE 8: NORMAL AND THERMAL PICTURE OF THE BASEMENT LIVING ROOM . 4.2 Energy gains Electricity and firewood bills show that the house heating demand was 25.61 MWh in 2023. While some of the demand was met with electricity, the majority was derived from the household’s use of firewood. The annual consumption of wood was 10 m3, which accounted for a total of 19.8 MWh. This is a high value in comparison to more efficient options. Figure 9 illustrates the share of energy supplied to the dwelling for its various energy carriers. Firewood represents the largest share of energy use, followed by electricity and solar radiation. 32 FIGURE 9: HEAT ENERGY INPUT OF THE DWELLING BROKEN DOWN BY SOURCE. Most of the electricity is used for heating purposes (59 %), with a significant proportion also employed for both electric appliances and lighting operation (41 %). Electricity and firewood serve as reliable sources of heat, with low prices in the Swedish energy market. The amount of energy obtained from solar energy is also noteworthy. It accounts for 5.73 MWh annually, considering only the period comprised between mid- September and mid-May. Only two-glazed windows contributed to heating the dwelling, and the contribution is illustrated in Figure 10: FIGURE 10: SOLAR RADIATION HEAT COMING THROUGH THE TWO-GLAZE WINDOWS SURROUNDING THE DWELLING IN WH. The solar gains vary depending on the direction of the sun. West does not have any windows; not contributing to heating the dwelling. The southern windows are, by far, the largest contributors to heating the house between mid-September and mid- May. The contribution of each month can be obtained in Figure 11: 19.80 5.81 1.86 5.73 Firewood Electricity Internal generation Solar radiation 0.53 0.60 4.61 0 - 1.00 2.00 3.00 4.00 5.00 North (-180˚) East (-90˚) South (0˚) West (90˚) MWh 33 FIGURE 11: MONTHLY SOLAR ENERGY PROVIDED TO THE DWELLING, EXCLUDING SUMMER MONTHS (MID-MAY TO MID-SEPTEMBER). From Figure 11, some conclusions can be drawn. Solar radiation is directly correlated with the number of hours of sunlight. May is expected to be the month with the highest solar radiation levels but given that only 15 days are used for the calculations, the total value is less than that of other months such as April. The winter months of December and January contribute with the least amount of heat to the dwelling. In addition to solar radiation, there are other sources of heat. Internal gains account for 1.86 MWh, with 0.43 MWh derived from the occupants and 1.43 MWh resulting from the energy loss of electric appliances. Solar radiation is the largest contributor to heat generation, with no additional cost, accounting for approximately three times that of the other internal gains combined. 4.3 Energy losses Energy transmission through the envelope, ventilation, and the use of hot water can contribute to the cooling of the house. These losses result in greater energy being used by the owner of the dwelling, which in turn contributes to higher energy bills and greater CO2 emissions. Calculations were key to understand how these losses are spread. The first step was to determine the total heat transmission power, which was found to be 11 kW. Of this total, 9.51 kW (86 %) were lost in the main building, while losses through the wall separating the dwelling and the garage, and the garage itself, accounted for 0.13 kW and 1.36 kW, respectively. Energy that travels through the wall between the dwelling and the garage contributes to heating the garage space, requiring less energy use in the end. Figure 12 represents the share of power needs due to energy losses through the building’s envelope. 0 200000 400000 600000 800000 1000000 1200000 1400000 Energy heat [MWh] Months 34 FIGURE 12: LOSSES CONTRIBUTION TO POWER NEEDS OF THE DWELLING, IN KW. When the annual energy loss was calculated, a value of 33.2 MWh was obtained for the total losses on transmission through the envelopes. Most of the energy loss is through the dwelling’s envelope, which accounts for 25.52 MWh (86 %). Figure 13 shows that the major contributor to energy loss was the envelope, followed by natural ventilation & other losses. FIGURE 13: HEAT POWER LOSSES [MWH] OF THE DWELLING FOR ITS VARIOUS SOURCES AND THEIR CONTRIBUTION IN PERCENTAGE FOR THE YEAR 2023. Figure 14 shows the contribution of each surface of the envelope to the heat power losses, with a comparison between their contribution, in W/K, and their surface area [m2]. This information is relevant to assess the energy measures, tackling first those areas with the greatest contribution. 9.51 0.13 1.36 Dwelling [kW] Dwelling-garage [kW] Garage [kW] 28.52; 86% 0.22; 0% 0.91; 3% 3.55; 11% Envelope [MWh] Mechanical ventilation [MWh] Hot tap water [MWh] Natural ventilation & other losses [MWh] 35 FIGURE 14: AREA AND U-VALUE TIMES AREA FOR EACH SURFACE OF THE ENVELOPE OF THE DWELLING . The greatest transmission losses through the envelope were given through the basement floor and walls, as well as the two-glaze windows. This is related to the fact that they have the highest U-values, a big area or a combination of both. Tackling these parts first, could help reduce the overall energy losses faster. The ventilation system was divided into three categories: natural ventilation, kitchen mechanical ventilation and bathroom mechanical ventilation. A flowmeter was used to quantify the ventilation flow rate of the mechanical system and results were presented previously in Table 5. The values were reasonable, and their contribution to the overall losses through ventilation were negligible. The mechanical exhaust of the kitchen was set to second speed (45 L/s), as explained in Appendix C. Setting the operating hours of the fans to one hour per day and 20 minutes per day for both the kitchen and the bathroom, respectively, the total energy lost due to mechanical ventilation accounts for 0.22 MWh annually. Figure 15 presents the contribution of the different ventilation systems. To calculate the energy losses due to natural ventilation, it was calculated considering the difference between energy used to heat the house and the known losses (energy balance). Some of these losses considered into natural ventilation are due to infiltration through the envelope of the house in the parts detected with the IR-camera. This is an approximation and may differ from the real value, but it gives a great understanding on how energy losses are distributed. 020 40 60 80 100 120 140 Ceiling External walls Basement walls ground Basement walls on the surface Basement floor Entrance door Living room door Windows (2 glaze) Windows (glass block) U·A [W/K] A [m2] 36 FIGURE 15: HEAT LOSS CONTRIBUTION [MWH] FOR THE VARIOUS VENTILATION CATEGORIES . Total ventilation accounts for 3.77 MWh, which represents an 11 % of the total energy losses. This value is reasonable considering that the dwelling has a natural ventilation system. Energy used for other purposes such as heating tap water is also considered as energy losses. Almost a third of the total water consumption (15.67 m3 of the total 47 m3) was heated, with a demand of 0.91 MWh throughout a year. 4.4 IDA ICE simulation Performing the simulation with the IDA ICE software, a total of 25.1 MWh of bought energy were required to heat the dwelling (Figure 16). This energy has a difference of under 1 % in comparison to the energy obtained by the bills and manual calculations (25.6 MWh of electricity and firewood). Since this difference is lower than 10 %, the model can be used to assess the performance with the proposed measures. Nevertheless, since there are two types of energy source (electricity and firewood) IDA ICE simulation is carried out considering that all energy is provided by electricity. With the energy bills, the amount of used electricity is known, and the rest should be provided by firewood. To estimate this value, the difference between the total energy and electricity (25.1 MWh and 5.8 MWh) is divided by the efficiency of the firewood heater. The total energy use is 27.24 MWh, which is still a difference of 6.4 % (under 10 %). FIGURE 16: BOUGHT ENERGY TO HEAT THE DWELLING THROUGHOUT A YEAR (IDA ICE MODEL). 3.55 0.22 Natural [MWh] Kitchen & bathroom [MWh] 37 Figure 17, Figure 18 and Figure 19 represent the evolution of temperatures in different rooms throughout the year. It is worth mentioning, that temperature does not go below 20 ºC at any given moment, and high temperatures during the summer period can be decreased by ventilating with the windows open. It is worth mentioning that the bedroom has the least variation of temperatures within a day, while it increments in the kitchen and the living room. This could be due to the internal heat generation of the rooms, since the occupants stay in the room during the day (like solar radiation), while internal heat generation in the bedroom is higher at night (outdoor temperatures are lower). FIGURE 17: REPRESENTATION OF THE TEMPERATURES IN THE MAIN BEDROOM THROU GHOUT THE YEAR. FIGURE 18: REPRESENTATION OF THE TEMPERATURES IN THE LIVING ROOM THROUGHOUT THE YEAR. FIGURE 19: REPRESENTATION OF THE TEMPERATURES IN THE KITCHEN AND DINING ROOM THROUGHOUT THE YEAR. In Figure 20 the total heating demand of the dwelling, with its variations through the weather is presented. It is relevant to note, that overall maximum power is achieved in December, and it has a peak of 12 kW. The second highest peak is under 10 kW. This may be due to an extremely cold day in the year. 38 FIGURE 20: TOTAL HEATING DEMAND OF THE DWELLING THROUGHOUT THE YEAR. Figure 21 represents the energy losses of the dwelling. As it is shown, transmission losses contribute to the most amount of energy losses, but the value is rather different compared to the manual calculations. This difference may be given by the fact that in manual calculations thermal different mechanical ventilation for certain hours was given, while in the model it was not possible. Also infiltrations and openings take up a big amount of the model calculations, while in manual calculations they have a different result. The overall result though accounts for the same energy losses from the building. Window and solar are also calculated in a different way as in the manual results. In this case, both gains and energy losses are considered in the same calculation, while in the manual calculations energy losses are considered part of the envelope, and energy gains are part of the solar radiation gains. FIGURE 21: ENERGY LOSSES THROUGH THE DIFFERENT PARTS OF THE DWELLING . Although there are many differences in the calculation procedure, there is a clear tendency of more heat use during winter months that decreases in summer months (Figure 22). 39 FIGURE 22: REPRESENTATION OF ENERGY GAINS AND LOSSES THROUGHOUT THE YEAR,WITH THE SAME LEGEND AS IN FIGURE 21. Energy losses through the envelope are shown in Figure 23, where the same thoughts as with the manual calculations can be concluded: • Walls: most energy escapes through transmission from the walls, mainly due to the high area they encompass, and also because of the high U-value on the basement walls. • Windows: Windows have a high U-value and lots of energy escapes from this part of the house. New windows provide more insulation and could prevent more heat from escaping. • Thermal bridges: they take part in the energy losses, it would be interesting to cover them when applying extra insulation in some areas of the dwelling. FIGURE 23: ENERGY LOSSES THROUGH THE ENVELOPE BY SURFACE AREA . Although IDA ICE can represent the energy losses of a building given its characteristics, its calculation methods may vary from the manual calculations provided in this paper and may be difficult to make direct extrapolations of values. 40 4.5 Energy measures 4.5.1 Ground Source Heat Pump (GSHP) Both the IDA ICE and manual calculation methods indicate a reduction of a third in energy use for heating purposes. The first evaluates the upgrade with a total electricity consumption of 8.37 MWh/year, while the latter shows an energy use of 8.54 MWh/year. This difference less than 2 %, which makes IDA ICE calculations acceptable for the results. According to the calculations, the energy use of the building would be reduced by 66 %. The annual energy bill though would be reduced by 33 %. For an economical perspective, the heat pump is evaluated over a 15-year period. Consequently, the payback period should be less than 15 years to be advisable. Given that current interest rate is 4 % 10 , the annuity factor is 0.08994 (to add on top of the investment cost). Electricity prices in Sweden 11 during at the end of 2023 and the beginning of 2024 ranged from 520 SEK/MWh to 800 SEK/MWh. A mean value of 660 SEK/MWh is assumed to calculate energy savings (constant throughout the years). On the other hand, firewood prices 12 are approximately 1 330 SEK/m3. The savings are achieved by reducing the number of resources to heat the house. Heat pumps provide 3 kWh of heat for every kWh of used electricity. In other words, there will no longer be a need for firewood purchases, but the demand of electricity will be higher, enough to cover a third of the previous heat: 𝐸𝑒𝑙𝑒𝑐 =25.6 𝑀𝑊ℎ 3=8.53 𝑀𝑊ℎ Given that no firewood will be purchased, the resulting savings would be as follows: 𝑺𝒂𝒗𝒊𝒏𝒈𝒔𝑮𝑺𝑯𝑷 =(1 330𝑆𝐸𝐾 𝑚3·10 𝑚3+5.8 𝑀𝑊ℎ·660 𝑆𝐸𝐾 𝑀𝑊ℎ) −8.53 𝑀𝑊ℎ·660 𝑆𝐸𝐾 𝑀𝑊ℎ=𝟏𝟏 𝟒𝟗𝟖.𝟐 𝑺𝑬𝑲 𝒚𝒆𝒂𝒓 10 Interest rates Sweden 2024: https://tradingeconomics.com/sweden/interest-rate 11 Electricity prices: https://www.statista.com/statistics/1271491/sweden-monthly-wholesale-electricity-price/ 12 Firewood prices: https://www.trygghandel.se/sv/artiklar/ved-15-m3-torr- ved.html?gad_source=1&gclid=CjwKCAjw3NyxBhBmEiwAyofDYQ0mdZFRsujRBZJPL9zEEtIH0FUQoiDKxtwEg1D2 qAYLn7jpwasVMxoCmOMQAvD_BwE 47 5 Conclusions 5.1 Study results The objective of this project was to analyze the energy use of an existing villa in Älvkarleby and reduce it by 25 %, thus contributing to an increase in the dwelling’s energy efficiency. This was achieved by investing in efficiency measures that resulted in savings in energy use, both from an energetical and economical perspective. The energy survey indicated that the majority of the energy losses occurred through the envelope of the dwelling, being the basement walls and the windows the primary contributors. The dwelling’s energy efficiency could be achieved by a variety of strategies. However, not all of them resulted in economic profitability over time. The installation of a GSHP resulted in a reduction of the building’s energy use by a third, from 25.1 MWh/year to 8.37 MWh/year. The addition of PV panels could help reduce this energy use by 2.17 MWh, lowering the energy use to 6.21 MWh, resulting in an overall increase of only 0.4 MWh of electricity use when compared to the previous electricity bill (electricity for heating purposes). Furthermore, the use of firewood was significantly reduced from 10 m3 to 0 m3. These modifications would contribute to reducing the yearly energy bill by 12 930.4 SEK. On the other hand, both the replacement of windows with newer models with greater insulation characteristics and the addition of external insulation to the building’s basement do increase energy efficiency. However, they are not economically viable. The first option would be a viable option for a 15-year period if either windows needed replacement due to other issues or if the cost could be lowered to under 35 710.50 SEK, or 85 710.50 SEK including subsidies. The second option would be viable if the investment cost could decrease to 65 835 SEK, or 115 835 SEK including subsidies. Although total CO2 emissions increased due to an increase in electricity use of 0.4 MWh, local emissions resulting from firewood combustion were eliminated. However, depending on the typology of the forest, some emissions could be linked to the combustion of firewood. The implementation of efficiency measures would result in a reduction in the overall CO2 emissions. 5.2 Outlook Future prospects for the work may include an in-depth analysis of the contributions of combustion of firewood to CO2 emissions and an energy survey of the dwelling’s energy use when the proposed measures are applied. Moreover, the market costs of 48 the alternatives may vary over time, with the need of a potential revision of the measures could be revised in case they become profitable. Furthermore, minor changes such as the replacement of electric appliances with more efficient models could be studied to reduce the electricity bill. In addition, it would be interesting to use more sensors to monitor the energy use of the firewood and electric boilers. This would provide a clear understanding of their performance and if there are any energy surpluses when both work at the same time. Another key aspect is the monitoring of the owner’s behavior to identify potential changes in activities that could help reduce energy losses without any additional costs. 5.3 Perspectives This project brings light into the energy surveys of old houses in Sweden and the economic viability of efficiency measures to reduce energy use. The findings of this study may be useful for dwellings in other cold climate locations, and for a variety of other buildings. Moreover, this project may contribute to share knowledge regarding energy efficiency methodologies, thus encouraging homeowners to implement some of the measures and contributing to a reduction in CO2 emissions. 49 References Alev, Ü. et al. (2014) ‘Renovation alternatives to improve energy performance of historic rural houses in the Baltic Sea region’, Energy and Buildings, 77, pp. 58–66. doi: https://doi.org/10.1016/j.enbuild.2014.03.049. ASHRAE (2017a) 2017 ASHRAE Handbook-Fundamentals (SI) (b). ASHRAE. ASHRAE (2017b) 2017 ASHRAE Handbook Fundamentals (SI) (a). ASHRAE. Borveket (2019) Boverket´s building regulations – mandatory provisions and general recommendations, BBR. Sweden. Available at: https://www.boverket.se/en/start/publications/publications/2019/boverketsbuilding-regulations--mandatory-provisions-and-general-recommendations-bbr/ Hämtad 2024-04-09. Boussaa, Y. et al. (2021) ‘Energy efficient measures for thermal envelope of a multiapartment building in Sweden: analysis of cost effectiveness with respect to carbon abatement costs implementation’, in. Boussaa, Y. et al. (2023) ‘Integrating Passive Energy Efficient Measures to the Building Envelope of a Multi-Apartment Building in Sweden: Analysis of Final Energy Savings and Cost Effectiveness’, Buildings, 13(10). doi: 10.3390/buildings13102654. FAO (2017) Wood energy. Available at: https://www.fao.org/sustainable-forest- management/toolbox/modules/wood-energy/basic-knowledge/en/?type=111. FLIR (no date) FLIR Exx-Series. Available at: https://nexxis.com.au/wpcontent/uploads/2019/05/FLIR-Exx-E75-Exx95-Spec-Sheet.pdf. Jalilzadehazhari, E., Pardalis, G. and Vadiee, A. (2020) ‘Profitability of Various Energy Supply Systems in Light of Their Different Energy Prices and Climate Conditions’, Buildings, 10(6). doi: 10.3390/buildings10060100. Jiang, W. et al. (2021) ‘Energy performance of window with PCM frame’, Sustainable Energy Technologies and Assessments, 45, p. 101109. doi: https://doi.org/10.1016/j.seta.2021.101109. Jiang, W. et al. (2023) ‘Net-zero energy optimization of solar greenhouses in severe cold climate using passive insulation and photovoltaic’, Journal of Cleaner Production, 402, p. 136770. doi: 10.1016/J.JCLEPRO.2023.136770. Kim, S.-I. et al. (2023) ‘Simulation-based comparative analysis of U-value of field measurement methods’, Case Studies in Thermal Engineering, 50, p. 103433. doi: https://doi.org/10.1016/j.csite.2023.103433. Li, Q. et al. (2022) ‘Evaluation of energy-saving retrofits for sunspace of rural residential buildings based on orthogonal experiment and entropy weight method’, Energy for Sustainable Development, 70, pp. 569–580. doi: https://doi.org/10.1016/j.esd.2022.09.007. 50 Mata, É., Kalagasidis, A. S. and Johnsson, F. (2013) ‘A modelling strategy for energy, carbon, and cost assessments of building stocks’, Energy and Buildings, 56, pp. 100–108. doi: https://doi.org/10.1016/j.enbuild.2012.09.037. Mata, É., Sasic Kalagasidis, A. and Johnsson, F. (2013) ‘Energy usage and technical potential for energy saving measures in the Swedish residential building stock’, Energy Policy, 55, pp. 404–414. doi: https://doi.org/10.1016/j.enpol.2012.12.023. Moshfegh, B. (1992) Thermal analysis of passive systems with multilayer insulation at room temperature. Sweden: Linkoeping (SE); Linkoeping Univ. Available at: https://doi.org/10.1016/j.cryogenics.2014.04.008. Nilsson, P.-E. and Commtech Group (2003) Achieving the desired indoor climate : energy efficiency aspects of system design, TA - TT -. Lund SE - [16], xiv, 668, [78] s. : illustrations ; 25 cm: Studentlitteratur : Commtech Group. doi: LK - https://worldcat.org/title/185984426. Nordström, G., Lidelöw, S. and Johnsson, H. (2012) ‘Comparing energy signature analysis to calculated U-values in wooden houses in a cold climate’, WIT Transactions on Ecology and the Environment, 165, pp. 411 – 419. doi: 10.2495/ARC120361. Olsson, D., Filipsson, P. and Trüschel, A. (2023) ‘Feedback Control in Swedish Multi-Family Buildings for Lower Energy Demand and Assured Indoor Temperature—Measurements and Interviews’, Energies, 16(18). doi: 10.3390/en16186747. Paul, K. I. et al. (2006) ‘Net carbon dioxide emissions from alternative firewoodproduction systems in Australia’, Biomass and Bioenergy, 30(7), pp. 638–647. doi: https://doi.org/10.1016/j.biombioe.2006.01.004. Peñaloza, D. et al. (2022) ‘Social and market acceptance of photovoltaic panels and heat pumps in Europe: A literature review and survey’, Renewable and Sustainable Energy Reviews, 155, p. 111867. doi: https://doi.org/10.1016/j.rser.2021.111867. Risholt, B. and Berker, T. (2013) ‘Success for energy efficient renovation of dwellings—Learning from private homeowners’, Energy Policy, 61, pp. 1022–1030. doi: https://doi.org/10.1016/j.enpol.2013.06.011. Rotronic (no date) CL11 - Inexpensive multiple parameter meter. Available at: https://www.rotronic.com/en-cn/cl11. SMHI (2023) Ladda ner meteorologiska observationer, SMHI. Available at: https://www.smhi.se/data/meteorologi/ladda-ner-meteorologiska- observationer/#param=airtemperatureInstant,stations=core,stationid=107420. Steen Englund, J. et al. (2020) ‘Measured and Simulated Energy Use in a Secondary School Building in Sweden—A Case Study of Validation, Airing, and Occupancy Behaviour’, Energies, 13(9). doi: 10.3390/en13092325. Suhonen, J. et al. (2020) ‘Demand Response Control of Space Heating in Three Different Building Types in Finland and Germany’, Energies, 13(23). doi: 51 10.3390/en13236296. SVEBY (2024) Beräkning | SVEBY. Available at: https://www.sveby.org/huranvander-jag-sveby/berakning/ (Accessed: 14 April 2024). Svensk byggnorm (1975) Svensk byggnorm: SBN 75. Utgåva 3. Available at: https://www.boverket.se/contentassets/c4c3f9ae57294ae889bfaf710b08b125/sb n-1975-utg-3.pdf. Swedish Energy Agency (2023) Energy consumption. Available at: https://www.energimyndigheten.se/en/energysystem/energy-consumption/. Tsoumis, G. T. (2023) Properties of wood, Encyclopedia Britannica. Available at: https://www.britannica.com/science/wood-plant-tissue/Bark-and-bark-products. United Nations (2002) Report of the World Summit on Sustainable Development. New York. Available at: https://digitallibrary.un.org/record/478154?v=pdf. United Nations (2015) ‘Paris Agreement’, in Framework Convention on Climate Change. Paris: United Nations, p. 60. Available at: https://wedocs.unep.org/20.500.11822/20830. Wahlström, M. H. and Hårsman, B. (2015) ‘Residential energy consumption and conservation’, Energy and Buildings, 102, pp. 58–66. doi: https://doi.org/10.1016/j.enbuild.2015.05.008. Xue, T. et al. (2022) ‘Experimental evaluation of IDA ICE and COMSOL models for an asymmetric borehole thermal energy storage field in Nordic climate’, Applied Thermal Engineering, 217, p. 119261. doi: https://doi.org/10.1016/j.applthermaleng.2022.119261. A1 Appendix A: Floor plans of the dwelling AN_FIGURE 1: MAIN FLOOR PLAN. A2 AN_FIGURE 2: BASEMENT PLAN. A3 AN_FIGURE 3: SOUTHERN FAÇADE AND LATERAL PLAN. A4 AN_FIGURE 4: HOUSE ORIENTATION AND PROFILE. B1 Appendix B: U-value calculations U-value can be calculated as the inverse of the sum of thermal resistances. The thermal resistance can be calculated as the ratio between thickness (d) and the thermal conductivity of the material (λ): 𝑈= 1 ∑𝑅𝑖 𝑛 𝑖=0 An_eq. 1 𝑅𝑖=𝑑𝑖 λi An_eq. 2 External walls AN_TABLE 1: MATERIAL PROPERTIES OF THE EXTERNAL WALL STRUCTURE: THICKNESS (D), THERMAL CONDUCTIVITY (Λ), AND TOTAL RESISTANCE VALUE (R). Material d [m] λ [W/(m·K)] R [m2·K/W] Rse - - 0.04 Brick 0.12 0.6 0.2 Air gap 0.02 0.1 0.2 Plastic board - - - Mineral wool + wood 0.95 0.0475 2.0 Wood 0.019 0.14 0.14 Rsi - - 0.13 An_Table 1 presents the material properties and thickness required to calculate the U-value of the external wall. The plastic board serves to prevent moisture from entering the building. Rse and Rsi represent the convection resistance on the external and internal parts of the wall, respectively. The total R-value (as the sum of the individual R-values) is R = 2.71 m2·K/W. Therefore, the U-value of the external walls can be solved by An_eq. 1, with a result of U = 0.37 W/m2·K. The mineral wool and wooden beams have a mixed U-value, which has been calculated with the λ-method stated in Eq. 4, with an alfa value of α= 50 𝑚𝑚 600 𝑚𝑚 = 0.083 for wood, and β=600−50 𝑚𝑚 600 𝑚𝑚 =0.917 for mineral wool insulation. Also, the used λ-value for the wood and mineral wool were 0.14 W/m·K and 0.04 W/m·K, respectively. C5 The value 𝑞 represents the air flow in [m3/s] and its value varies depending on the status of the fans. Natural ventilation cannot directly be calculated. Therefore, it will be the result of the difference in energy input and output. Here are listed the different mechanical air flows: • 𝑞𝑘𝑖𝑡𝑐ℎ𝑒𝑛 =45𝐿 𝑠=0.045𝑚3 𝑠 : it is supposed that the fan is used at its second speed all the time. • 𝑞𝑏𝑎𝑡ℎ𝑟𝑜𝑜𝑚 =7𝐿 𝑠=0.007𝑚3 𝑠 These different air flows result in different power requirements for heating the outdoor air (using Eq. 5 with the specified values): 𝑃𝑣𝑒𝑛𝑡_𝑘𝑖𝑡𝑐ℎ𝑒𝑛 =2.06 𝑘𝑊 𝑃𝑣𝑒𝑛𝑡_𝑏𝑎𝑡ℎ𝑟𝑜𝑜𝑚 =0.32 𝑘𝑊 Energy As with the procedure for calculating energy lost in the envelope, degree hours are required to determine the energy lost in ventilation. Given that the outside temperature fluctuates throughout the year, the degree hours are identical to those obtained in the energy section of this appendix for calculating the energy transmitted through the envelope (92 296 ºh). Using Eq. 6, energy can be calculated: 𝐸𝑣𝑒𝑛𝑡_𝑘𝑖𝑡𝑐ℎ𝑒𝑛 =0.045·1.2·1.005·92 296=5 009 𝑘𝑊ℎ 𝑦𝑒𝑎𝑟 𝐸𝑣𝑒𝑛𝑡_𝑏𝑎𝑡ℎ𝑟𝑜𝑜𝑚 =0.007·1.2·1.005·92 296=780 𝑘𝑊ℎ 𝑦𝑒𝑎𝑟 These values are calculated without consideration of the proportion of time each ventilation system is active. For the sake of simplicity, the kitchen mechanical exhaust system is assumed to be active for half an hour during lunch and dinner (equivalent to 1 hour per day, resulting in 365 hours per year), while the bathroom ventilation system is switched on for 20 minutes per day (121.7 hours per year). 𝐸𝑣𝑒𝑛𝑡_𝑘𝑖𝑡𝑐ℎ𝑒𝑛 =5 009 𝑘𝑊ℎ 𝑦𝑒𝑎𝑟·365 8 760=208.7𝑘𝑊ℎ 𝑦𝑒𝑎𝑟 𝐸𝑣𝑒𝑛𝑡_𝑏𝑎𝑡ℎ𝑟𝑜𝑜𝑚 =780 𝑘𝑊ℎ 𝑦𝑒𝑎𝑟·121.7 8 760=10.8𝑘𝑊ℎ 𝑦𝑒𝑎𝑟 The overall energy loss due to ventilation is the addition of the previous losses: C6 𝑬𝒗𝒆𝒏𝒕 =𝐸𝑣𝑒𝑛𝑡_𝑘𝑖𝑡𝑐ℎ𝑒𝑛 +𝐸𝑣𝑒𝑛𝑡_𝑏𝑎𝑡ℎ𝑟𝑜𝑜𝑚 =(208.7+10.8)𝑘𝑊ℎ 𝑦𝑒𝑎𝑟 =219.5𝑘𝑊ℎ 𝑦𝑒𝑎𝑟 =𝟎.𝟐𝟐𝑴𝑾𝒉 𝒚𝒆𝒂𝒓 Hot tap water The bill accounts for an annual consumption of water of 47 m3. Using Eq. 7, the estimated hot water consumption can be calculated as follows: 𝑞ℎ𝑜𝑡_𝑤𝑎𝑡𝑒𝑟 ≈𝑞𝑐𝑜𝑙𝑑𝑤𝑎𝑡𝑒𝑟 3=47 3=15.67 𝑚3 This value can now be used in Eq. 8 to obtain the energy used to heat up water throughout the course of a year: 𝐸ℎ𝑜𝑡_𝑤𝑎𝑡𝑒𝑟 =15.67 𝑚3 ·1 000𝑘𝑔 𝑚3·4.18 𝑘𝐽 𝑘𝑔·°𝐶·(55−5)°𝐶 3 600 𝑠 1ℎ ≈0.91𝑀𝑊ℎ 𝑦𝑒𝑎𝑟 Heat pump dimentioning Daily consumption of hot tap water: 15.67 𝑚3 365 𝑑𝑎𝑦𝑠=0.043 𝑚3 𝑑𝑎𝑦 Power required for daily consumption of hot tap water, considering that there is only one occupant, hence a day’s water consumption can be heated overnight in 5 hours or more: 𝑃𝑑𝑎𝑖𝑙𝑦_ℎ𝑜𝑡_𝑤𝑎𝑡𝑒𝑟 =0.043 𝑚3·1 000𝑘𝑔 𝑚3·4.18 𝑘𝐽 𝑘𝑔·°𝐶·(55−5) °𝐶 5·3 600 𝑠 =0.5 𝑘𝑊 C7 Solar radiation To calculate the solar radiation energy that the household is going to receive throughout the year, Eq. 9 is used. Some considerations are taken into account: solar radiation is calculated from mid-September to mid-May, since during summer, it generates an excess of heat; there are different cloud factors depending on the month, and different radiation rates depending on the orientation of the windows and the month. Also, the energy trespassing the windows is different depending on the windows type. In this project, the radiation factor of two-glazed windows was assessed at 0.8, while the radiation factor of glass-block windows in the basement was found to be insignificant and therefore ruled out. Calculation for two-glazed windows is provided in An_Table 6. AN_TABLE 6: SOLAR RADIATION CALCULATION FOR TWO-GLAZE WINDOWS FOR ALL THE ORIENTATIONS. The total heat contribution of the sun is about 5.73 MWh annually. However, this value may vary slightly depending on the cloud factor of each year. Internal heat generation People As previously mentioned, humans generate heat, with an estimated production of 80 W per person. In the case of the studied household, there is one occupant who is presumed to be present for the majority of the year. It is assumed that the owner will not be inside the building for two hours a day, for activities such as gardening, grocery shopping, and other. The internal heat generation of people can be calculated by multiplying the heat power by the time: 𝐸𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑡 =80 𝑊·22ℎ 𝑑𝑎𝑦·242.5𝑑𝑎𝑦𝑠 𝑦𝑒𝑎𝑟 =426.8𝑘𝑊ℎ 𝑦𝑒𝑎𝑟 =0.43𝑀𝑊ℎ 𝑦𝑒𝑎𝑟 Appliances and lighting In the Internal generation of heat theory, information regarding electricity use of appliances and lighting in Sweden is shared. It is estimated that approximately 70 % of the electricity used by electric appliances is converted to heat due to losses. Month Windows' radiation factor (r) Cloud factor (c) Days (d) I A E I A E I A E I A E January 0.8 0.45 31 130 7.73 11214.684 550 2.5 15345 2710 9.65 291850.74 550 0 0 February 0.8 0.49 28 370 7.73 31392.4576 1550 2.5 42532 4880 9.65 516881.792 1550 0 0 March 0.8 0.58 31 730 7.73 81167.4736 3050 2.5 109678 6320 9.65 877251.392 3050 0 0 April 0.8 0.58 30 1350 7.73 145262.16 4750 2.5 165300 6410 9.65 861042.48 4760 0 0 May 0.8 0.63 15 2350 7.73 137331.18 5630 2.5 106407 5730 9.65 418026.42 5630 0 0 September 0.8 0.58 15 900 7.73 48420.72 3520 2.5 61248 6130 9.65 411715.32 3520 0 0 October 0.8 0.51 31 510 7.73 49862.2104 2110 2.5 66718.2 5620 9.65 685938.984 2110 0 0 November 0.8 0.42 30 200 7.73 15583.68 840 2.5 21168 3480 9.65 338506.56 840 0 0 December 0.8 0.43 31 80 7.73 6594.6176 350 2.5 9331 2030 9.65 208902.428 350 0 0 526 829.18 597 727.20 4 610 116.12 0 2-glaze windows 5.73 TOTAL [MWh] North (-180˚) South (0˚) East (-90˚) West (90˚) [ ℎ 𝑚2· 𝑑𝑎𝑦] [ ℎ 𝑚2· 𝑑𝑎𝑦] [ ℎ 𝑚2· 𝑑𝑎𝑦] [ ℎ 𝑚2· 𝑑𝑎𝑦] 𝑚2𝑚2𝑚2𝑚2 [𝑊ℎ] [𝑊ℎ] [𝑊ℎ] [𝑊ℎ] C8 Moreover, a single-family dwelling is estimated to use approximately 30 kWh/m2·year of energy (Mata, Kalagasidis and Johnsson, 2013). As the basement is rarely used, the surface area of the main floor is used to calculate the internal heat energy due to appliances and lighting: 𝐸𝑎𝑝𝑝𝑙𝑖𝑎𝑛𝑐𝑒𝑠 =30 𝑘𝑊ℎ 𝑚2·𝑦𝑒𝑎𝑟·0.7·102.75 𝑚2·242.5 365 =1.43 𝑀𝑊ℎ Therefore, the total internal energy generation is: 𝑬𝒊𝒏𝒕𝒆𝒓𝒏𝒂𝒍 =𝐸𝑝𝑒𝑜𝑝𝑙𝑒 +𝐸𝑎𝑝𝑝𝑙𝑖𝑎𝑛𝑐𝑒𝑠 =0.43+1.43=𝟏.𝟖𝟔 𝑴𝑾𝒉 Normal year correction Degree days for a certain year can be calculated from the 2023 climate data document by subtracting the average temperature of each day below 17 ºC from this value. To illustrate, if the mean temperature for a given day is 10 ºC, the difference between 17 ºC and 10 ºC (7 ºC) would be the degree days for that day. The total degree days of the year are obtained by adding all the degrees calculated for each day. For the actual year, the total is: Sactual_year = 3 993 degree days. For a normal year in Gävle, the total is Snormal_year = 3 959 degree days. The energy index is calculated with Eq. 16 and the degree days of both years previously stated: 𝐸𝑛𝑒𝑟𝑔𝑦 𝑖𝑛𝑑𝑒𝑥 =𝑆𝑛𝑜𝑟𝑚𝑎𝑙 𝑆𝑎𝑐𝑡𝑢𝑎𝑙 =3 959 3 993=0.99 The corrected energy losses resulting from the transmission through the envelope and ventilation can now be calculated: 𝐸𝑡𝑟𝑎𝑛𝑠 =28.81 𝑀𝑊ℎ·0.99=28.52 𝑀𝑊ℎ 𝐸𝑣𝑒𝑛𝑡 =0.22 𝑀𝑊ℎ·0.99=0.22 𝑀𝑊ℎ The values considered for the heat balance are not dependent on a particular year; rather, they represent the average of the previous years. Heat balance The overall heat balance is the sum of the previously calculated values. Internal heat generation, solar radiation, and hot tap water all contribute to the heating of the house through their energy losses. Moreover, the house is heated with both electricity and wood. C9 The energy content of firewood can be calculated using its heat energy (4.4 kWh/kg) (FAO, 2017), and the average density for firewood, which is approximately 500 kg/m3 (Tsoumis, 2023). Moreover, a 90 % efficiency is considered based on the heater’s model 14 . These values provide an approximation of the heating provided by firewood and are useful for understanding the energy content of firewood: 𝐸𝑤𝑜𝑜𝑑 =0.9·(4.4𝑘𝑊ℎ 𝑘𝑔 )·500 𝑘𝑔 𝑚3·10𝑚3=19.8 𝑀𝑊ℎ Electricity used in other areas than strictly heating, are discounted from the overall electricity bill, to assess what part is for heating purposes. In this case, the electric appliances are calculated for the whole year, as they use electricity all year long, even if this results in the generation of unwanted heat during the summer months: 𝐸𝑒𝑙𝑒𝑐_𝑎𝑝𝑝𝑙 =30 𝑘𝑊ℎ 𝑚2·𝑦𝑒𝑎𝑟·102.75 𝑚2=3 082𝑘𝑊ℎ 𝑦𝑒𝑎𝑟 𝑬𝒆𝒍𝒆𝒄 =(9 800−3 082−910) 𝑘𝑊ℎ=𝟓 𝟖𝟎𝟖 𝒌𝑾𝒉 The overall supplied heat can now be calculated using Eq. 11: 𝐸𝑡𝑜𝑡𝑎𝑙 =𝐸𝑤𝑜𝑜𝑑 +𝐸𝑒𝑙𝑒𝑐 +𝐸𝑖𝑛𝑡 +𝐸𝑠𝑜𝑙𝑎𝑟 =(19.8+5.81+1.86+5.73) 𝑀𝑊ℎ =33.2 𝑀𝑊ℎ The energy supplied to the house is compensated for by the energy losses incurred by the house. With Eq. 10, it is known that the total energy loss accounts for 43.88 MWh, which can be presented with Eq. 12: 𝐸𝑜𝑢𝑡 =𝐸𝑡𝑟𝑎𝑛𝑠 +𝐸𝑚𝑒𝑐ℎ_𝑣𝑒𝑛𝑡 +𝐸ℎ𝑜𝑡_𝑤𝑎𝑡𝑒𝑟 +𝐸𝑢𝑛𝑤𝑎𝑛𝑡𝑒𝑑_𝑣𝑒𝑛𝑡 =28.52+0.22+0.91+𝐸𝑣𝑒𝑛𝑡 Energy lost in natural ventilation and other infiltration losses result in 𝐸𝑣𝑒𝑛𝑡=3.55 MWh (11 %). 14 Boiler Värmebaronen combimax 30 ub model efficiency: https://issuu.com/villaliv_net/docs/villaliv_nr6_2012/22 D1 Appendix D: Meters information AN_FIGURE 6: FLIR E75 ADVANCED TEHRMAL IMAGING IR-CAMERA SPECIFICATION SHEET (FLIR, no date) (1/2). D2 AN_FIGURE 7: FLIR E75 ADVANCED TEHRMAL IMAGING IR-CAMERA SPECIFICATION SHEET (FLIR, no date) (2/2). D3 AN_FIGURE 8:CALIBRATION CERTIFICATE SWEMAFLOW 233 FOR AIRFLOW MEASUREMENTS.