Protection of AC and DC distribution systems. Embedding distributed energy resources: a comparative review and analysis

Monadi, Mehdi,Zamani, M. Amin,Candela García, José Ignacio,Luna Alloza, Álvaro,Rodríguez Cortés, Pedro

Abstract

The integration of distributed generation (DG) units into distribution networks has challenged the operating principles of traditional AC distribution systems, and also motivated the development of emerging DC systems. Of particular concern are the challenges associated with the Operation of conventional protection schemes and/or devices. This paper first analyses the fault current characteristics in AC and DC distribution systems; it then presents a comprehensive review of the latest protection methods proposed for distribution systems embedding DGs. In addition, the advantages and disadvantages of each method are outlined and compared. The differences between the protection algorithms employed in/proposed for AC and DC systems are also discussed. Finally, this study identifies the future trends and provides recommendation for researches in the field of protections of DC distribution networks. (C) 2015 Elsevier Ltd. All rights reserved.

Full text

1 Protection of AC and DC distribution systems Embedding distributed energy resources: A comparative review and analysis. Mehdi Monadi1,2,*, M. Amin Zamani3, Jose Ignacio Candela1, Alvaro Luna1, Pedro Rodriguez1,4 1 Technical University of Catalonia, Barcelona, Spain 2 Shahid Chamran University of Ahvaz, Ahvaz, Iran 3 Kinectrics Inc., Toronto, Canada 4 Abengoa Research, Seville, Spain Abstract- The integration of Distributed Generation (DG) units into distribution networks has challenged the operating principles of traditional AC distribution systems, and also motivated the development of emerging DC systems. Of particular concern is the challenges associated with the operation of conventional protection schemes and/or devices. This paper first analyses the fault current characteristics in AC and DC distribution systems; it then presents a comprehensive review of the latest protection methods proposed for distribution systems embedding DGs. In addition, the advantages and disadvantages of each method are outlined and compared. The differences between the protection algorithms employed in / proposed for AC and DC systems are also discussed. Finally, this study identifies the future trends and provides recommendation for researches in the field of protections of DC distribution networks. Keywords- AC distribution systems; DC distribution systems; distributed generation; power system protection; renewable energy resources. 1. INTRODUCTION The employment of Renewable Energy Systems (RESs) such as wind energy systems, Photovoltaic (PV) systems, biomass power plants, and small hydro turbines is increasing in electric networks. These resources, which constitutes one of the most relevant technologies among DGs, are typically smaller than conventional power plants and more distributed from a geographic point of view [1, 2]. Although the main part of electrical power is still generated by conventional power plants, RESs are the world’s fastest growing energy market [3]. Moreover, deregulation of electric utilities based on the liberalism of power markets, increases the opportunity for further deployment of RESs and other types of DGs [4]. One of the main reasons for this worldwide attention is the environmental concerns about the effects of using conventional power plant. While conventional power plants with fossil-based fuel has a significant impact on the greenhouse emission and global warming, RESs stand out as clean resources of energy [4, 5]. On the other hand, the limitation of fossil fuels and their increasing costs, along with the limited investment on constructing new large power plants and transmission lines, are the other reasons that have contributed to the deployment of small power plants. These power plants can be connected to strategic points of distribution systems or close to load centers [2]. Despite the aforementioned incentives, the integration of renewable-energy-based DGs into power systems has dramatic effects on the energy supply and the service continuation of distribution network; it also causes fundamental changes in the topology and operation of these networks [6]. Traditionally, distribution systems are passive grids [7] which deliver the electrical power from upper voltage levels down to the loads connected to medium-/low-voltage networks without generation *Corresponding author. Tel. : +34661153290; Fax: +34 93739 8225 Email: [email protected] Address: Research Center on Renewable Electrical Energy Systems (SEER Center), GAIA building, 22, Rambla Sant Nebridi, 08222, Campus Terrassa, Barcelona, Spain 2 facilities. The topology of these systems is selected based on the required consumer reliability and economic considerations. Although loop topology has been used in distribution systems, most distribution feeders have a radial structure [8, 9].The integration of RESs into distribution networks changes the operational philosophy of conventional power systems, especially those with the radial and passive nature [10, 11]. In other words, RESs converts the distribution system to an active network [7]. In addition, the intermittent nature of most RESs can adversely impact the operational aspects of power systems. Protection coordination, voltage control, system stability, and power quality are the major issues associated with DGs [12-14]. Particularly, protection of active distribution networks may not be adequately achieved by conventional methods, and new techniques are required [9, 15, 16]. Most RESs are interfaced with the grid through power-electronic converters [2, 17]. Therefore, using DC distribution systems can contribute to the loss/cost reduction, as some power conversion stages are eliminated [18, 19]. Moreover, compared to AC systems, DC networks can transmit higher power over longer distances. Enhancement in system safety, reduction of electromagnetic fields, and power quality improvement are other advantages of DC networks [19]. In addition to the abovementioned points, the simple integration of most modern electronic loads that are supplied by DC power has caused the concept of DC distribution systems to attract a considerable attention. It is worth mentioning that almost all voltage and current levels can be currently obtained by series or parallel combination of new power electronic devices [20, 21]. The employment of medium-voltage DC (MVDC) distribution systems has so far remained as a research topic, although they had limited application such as electrical ships [22]. However, due to their advantages, they are introduced as an alternative for AC systems in future commercial and industrial grids [23-29]. Creation of multi-microgrids [30], providing collection grids for off-shore wind farms and wide-area solar power plants [20, 31, 32], increasing the power transmission capacity of the existing AC lines [26, 33], and simple integration of industrial DC loads, [24] are some of the applications of MVDC systems. Fig. 1 shows a typical multi-terminal DC distribution system. Although MVDC systems can be considered as a future alternative for AC distribution networks, there are serious concerns about their application. Protection is one of the main key issues associated with the application of DC grids [3, 20, 34, 35]. The differences between the characteristics of AC and DC fault currents, inadequacy of conventional protection methods for fault detection, fault location, and fault interruption devices/methods are some of the protection challenges in these grids. Aside from the type of the distribution system, it must be effectively protected against different types of faults. An effective protection scheme shall provide adequate sensitivity, redundancy, selectivity, and security [36]. Therefore, it must be designed based on the characteristics of the system as well as applicable standards/regulations. This means that the following main protection issues should be addressed in emerging AC and DC distribution systems: 1) The impacts of DGs on the protection schemes of existing AC distribution systems, and proposing new effective protection methods. 2) Identification of the protection requirements for emerging DC distribution networks. The main objective of this paper is to provide a comprehensive and up-to-date review of the latest protection methods employed in /proposed for AC and DC distribution systems embedding DGs. The study also identifies the differences between the protection schemes in AC and DC systems. The review could be of great value for protective relay manufacturers, utility engineers as well as academicians and researchers.The rest of the paper is organized as follows: Section 2 discusses and compares the characteristics of fault currents in AC and DC systems. The protection challenges in both AC and DC systems are studied in Section 3. The proposed methods for AC and DC distribution systems are explained in Sections 4 and 5, respectively. Section 6 provides a brief comparison between the AC and DC protection schemes. Finally, the conclusions and future trends are provided in Section 7. 3 Fig 1. The structure of a prototype DC distribution system. 2. FAULT CHARACTERISTICS IN AC AND DC DISTRIBUTION SYSTEMS The design of a proper fault detection method requires some knowledge of the fault current characteristics. In addition, to coordinate protective devices and to determine the type and rating of fault interrupting and/or measuring devices, the features of the fault current should be known. In this section, the main characteristics of short-circuit currents in AC and DC systems are briefly discussed while the DG impacts are ignored; the effects of DGs will be discussed in Section 3. 2.1. Fault Characteristics in AC Systems Fault types vary from network to network. However, their classifications are universally accepted. They can generally be categorized to symmetrical faults, that is, three-phase faults (LLL, LLLG), and asymmetrical faults, that is, single-phase-to- ground faults (LG), phase-to–phase faults (LL), and double-phase-to-ground faults (LLG). The magnitude of the fault current depends on the type, location, and impedance of the fault. Typically, three-phase faults create maximum fault currents; Fig. 2 shows a simplified equivalent circuit of a power system when a three-phase fault impacts the network. Fig 2. Equivalent circuit for LLLG fault in AC systems. AC power systems are typically energized by three-phase synchronous generators, which can be modeled by a voltage source in series with impedance. Considering the equivalent circuit of Fig. 2, the three-phase fault current can be obtained as [36]:   (  ) =     (  +  −  ) + 󰇣     (  −  ) +   ( 0  ) 󰇤     (1) where denotes the nominal source voltage; =||∡ is the equivalent impedance, which consists of the generator impedance and the impedance from the generators terminal to the fault point, (=+);  signifies the network nominal 4 frequency (in rad/s);  is the phase angle (point of wave) at which the fault is initiated; (0) is the pre-fault current, and =/ denotes the circuit time constant. As Equation (1) shows, the fault current in AC networks has two components: i) decaying DC component and ii) steady-state AC component [37, 38]. Although the term steady-state is commonly used, it should be noted that the magnitude of this component is not constant during the first few cycles following the fault. Therefore, subsequent to a fault, the AC component will have different magnitudes during the three following periods [39] : 1) Sub-transient period, during which the magnitude of the AC component is calculated using the generator sub-transient reactance ( 󰆒󰆒); this period typically lasts for less than 50ms. 2) Transient period, during which the generator transient reactance ( 󰆒> 󰆒󰆒 ) is used to obtain the fault current level; based on the transient reactance value, fault currents during the transient period (50ms-1s) are smaller than those experienced during the sub-transient period. 3) Steady-state period, during which the fault current settles at its steady-state value; the fault current at this period is calculated using the generator synchronous reactance (> 󰆒) and is smaller than the sub-transient and transient fault currents. 2.2. Fault Characteristics in DC Systems In bipolar DC systems, short circuit faults are divided into two main categories, namely, pole to pole faults and pole to ground faults. In pole to pole faults, the positive pole is directly connected to the negative pole (PP) or simultaneously connects to the negative pole and ground/neutral point (PPG). These faults are often of low-impedance type and, thus, endanger the system very seriously. Pole to ground (PG) faults, on the other hand, occur when either the positive or negative pole is connected to the ground or the neutral point. This type of faults, which usually occur due to the insulation degradation, are the most common types of short circuits in DC grids; however, they are not as critical as pole to pole faults [40-42]. Different types of Voltage Source Converters (VSCs) are widely employed to connect DGs to DC grids and to construct DC switchgears. For instance, a multi-level VSC is used to interface an MVDC grid with an existing AC system [43]. Connection of PV systems and/or wind farms to DC networks also requires an energy conversion mechanism, including a medium-frequency interconnection transformer [44]. The transformer is particularly necessary for the connection of low-voltage DGs. It is important to note that, in addition to the network impedance, the operational characteristics of VSCs affect the behavior of DC faults and must be considered in the design of a proper protection system. This paper mainly focuses on VSC-based DC distribution systems. The fault characteristics of PP faults are discussed in the following paragraphs. Fig. 3 shows a simplified schematic diagram of a typical PP fault assuming that a two-level VSC is used as an interface. In this figure, R and L represent the resistance and inductance of the DC line between the main DC bus (location of DC-link capacitor) and the fault location. The analysis of the equivalent circuit of Fig. 3 indicates that the fault current is supplied by three sources, that is, i) DC-link capacitor, ii) cable inductance (discharged through freewheeling diodes), and iii) utility grid [45, 46]. Therefore, DC fault currents are constituted of three different components with different behavior, as follows: 5 Fig 3. A simplified schematic diagram for a PP fault in a VSC-based DC grid. 2.2.1-DC-Link Capacitor Discharge Component Following the occurrence of the fault in DC grids, the DC-link capacitor is discharged, mainly due to the voltage drop of the main DC bus. Using the equivalent circuit of Fig. 3 (see also Table 1), the DC-link capacitor component, , can be obtained by solving the following second-order differential equation:       +       + 1    = 0 (2) where R and L denote the DC line resistance and inductance, respectively; and C represents the capacitance of the DC-link capacitor. Depending on the damping factor (i.e., ) of the RLC circuit (see Table I), three different responses can be considered for the DC-link capacitor current, namely, i) under-damped response (<1), ii) critically damped response (= 1), and iii) Over-damped response (>1). The damping factor, in turn, is given by:  =  2    (3) As Equation (3) shows, the waveform of the DC-link capacitor current depends on the system impedance (R and L) as well as the DC-link capacitor (C). For example, in a short distribution feeder, if a solid fault impacts the DC line, the fault current will most likely have an under-damped form which is obtained as [45]:   (  ) = −            sin (    ) +         [ cos (    ) +  2   sin (    ) ] (4) where = , and  and  are the initial values of the capacitor voltage and cable current. The above discussion shows that the fault impedance can significantly affect the characteristics of the DC-link capacitor component of the fault current. In particular, the fault resistance changes both the magnitude and transient response of the fault current. It should also be pointed out that the DC-link capacitor current appears subsequent to a fault in all VSC-based DC grids, whereas the existence of the two other fault current components depends on other factors including the type and control of the VSC supplying the DC bus. 2.2.2-Cable-Discharge Component Fig. 3 shows a typical VSC whose DC side is struck by a fault. Subsequent to the fault, the control scheme of the converter turns off the VSC switches (e.g., IGBTs) to protect them against the overcurrent condition. Once the switches are blocked and the DC-link capacitor is discharged (V(t)=0), the energy stored in the cable inductance will be discharged through the antiparallel freewheeling diodes. Using the equivalent circuit of this phase (see Table 1), the cable-discharge component, i, can be obtained by solving a first-order differential equation as follows:  d i  dt + i  . R = 0 (5) Solving (5), the cable-discharge current is calculated as: i  ( t ) = I  e     (6) 2.2.3-Grid-Side Component Following the blocking of the main converter switches, the VSC operates as an uncontrolled full-bridge rectifier; thus, it continues to feed the fault from the AC grid through the freewheeling diode paths [47, 48]. In case of a three-phase AC-to-DC converter, this rectified current is obtained by [46]:   (  ) =   , ( > 0 ) +   , ( > 0 ) +   , ( > 0 ) (7) 6 where ,(>0) denotes the positive value of phase-x current () which contribute to the fault current through freewheeling diodes. For example, the phase-a part ,(>0) is calculated as [46] :  (  ) =    (    +  ) +         +             (    +  ) +             (    ) (8) where =[(1−)+()] ;=+; =−arctan󰇡 󰇢−arctan(. ); =−(+ ); =. −;  is the maximum grid current amplitude; and  and are the angular frequency and phase voltage angle of phase-a of the grid voltage. It is noted that, except the DC-link capacitor current, the other two fault current components flow through the freewheeling diodes; thus, these diodes may get damaged quickly if proper provisions are not put in place [47, 49]. 2.3. Comparison of AC and DC Fault Current Characteristics Based on the discussion of Sections 2.1 and 2.2, it is evident that AC and DC fault currents have different characteristics. In the view of the system protection, the main differences can be categorized as the following:  Since the AC fault current has a sinusoidal shape, it has two zero crossing points in each period. Hence, the fault interrupting devices can break the currents during a zero crossing of the current waveform. However, DC fault currents do not cross a zero point. Consequently, AC breakers are not suitable for breaking DC fault current.  In AC power systems, the fault impedance consists of reactance and resistance limits the fault current where the value of reactance is normally larger than its resistance. In DC networks, however, the value of reactance is quite negligible as compared to the network resistance. Consequently, not only the peak value of DC fault currents is higher than the peak value of fault currents in counterpart AC systems, but also the lower value of the fault impedance gives rise to a higher rate of change of the DC fault currents [50].  Since DC faults cause a high-raising-rate currents, faults in VSC-based DC systems develops faster than AC systems [34, 51]. On the other hand, the withstand rating of semiconductor devices employed in VSCs is fairly lower than that in AC power generators [41]. Consequently, the protection systems in DC networks must operate relatively faster in order to prevent any damage to the converter’s semiconductor (particularly, freewheeling diodes). The operating time of DC protection systems, which is in the range of several milliseconds, is typically less than the operating time of AC protection systems and is given by [46]:   = (  − arctan  ( (              cos  −   ) /  (9) where = √. It can be concluded from Equation (9) that many of conventional protection methods for AC systems are not suitable for application in DC systems as they are not fast enough. Thus, conventional protection schemes in AC grids should be modified to fulfill the fault detection/isolation requirements in DC systems. To provide a better understanding of issues, Table 1 has summarized the main differences between the characteristics of AC (LLLG) and DC (PP) fault currents. 7 Table 1. Comparison of AC and DC fault currents characteristics. AC Fault (LLLG) DC Fault (PP) Schematic of faulty feeder Equivalent circuit (EC) of faulty feeder Fault Current waveform First stage of fault current Sub-transient stage:   󰆒󰆒 =   (+ 󰆒󰆒) Capacitor discharge current (for under-damping condition):   (  ) =       sin (    ) +     [ cos (    ) −    sin (    ) ] Second stage of fault current Transient stage:   󰆒 =   (   +   󰆒 ) Cable discharge current:   (  ) =      Final stage of fault current Steady state current:   =   (   +   ) The rectified grid side current:   (  ) =   , ( >  ) +   , ( >  ) +   , ( >  ) Zero crossing time Based on the rated frequency. No zero crossing point (direct current). Maximum value of fault current Is related to voltage and equivalent fault impedance. Is according to the size of DC-link capacitor, DC voltage and equivalent fault impedance. Effect of fault impedance Change the amplitude of fault current. Change in the fault current characteristics. (Under/over/critical damping). Ideal fault clearing time The first possible zero crossing point. Before finishing the capacitor discharge stage. 0 0 8 3. PROTECTION CHALLENGES IN AC AND DC SYSTEMS Conventional distribution systems are passive networks and are mostly arranged in radial topology [8]. These networks are normally protected by current-based devices such as O/C relays, fuses, reclosers, and sectionalizers. The O/C protective relays monitor the current flowing through a protected circuit/element and trip the CB if the current exceeds a threshold for a specific period of times. The operating time of the relay is determined by the current magnitude measured by the relay, the relay settings, and the employed time-current characteristic (definite-time or inverse-time). O/C relays provide a non-unit protection in which the physical borders of the protected zone are not specified. The main feature of the non-unit protection is that the upstream relays can provide remote backup for downstream ones. However, the coordination between the main and backup relays should be performed very accurately so that adequate selectivity and sensitivity are achieved. Conventional protection systems are designed based on the assumption of unidirectional flows of power within the network, which may be affected in the presence of DGs. With the increasing penetration of DGs, the fundamentals of distribution system protection have been challenged. In the following paragraphs, the main issues associated with the protection of AC distribution system embedding DGs as well as protection challenges of DC grids are discussed. 3.1. Protection Challenges in AC Systems As discussed in previous section, the introduction of DGs has affected several operational aspects of AC power systems including their protection philosophy [8, 52]. Although impacts of DGs on the distribution network depend on such factors as size, type, location, and interconnection interface of DGs [52-55], they can potentially change the following: i) fault current level of the feeder and ii) power flow direction on the feeder. These changes, in turn, can impact the performance of currentbased protection schemes as described below. 3.1.1. Change in the fault current level DGs can change the fault current seen by a protective device depending on their size, type, location, and interconnection medium [56]. The increment in current can cause nuisance tripping if the measured current by the relay exceeds its pick-up setting. On the other hand, O/C protective devices of a distribution feeder are coordinated for a range between the minimum and maximum fault currents of that feeder. Therefore, any change in the fault current may lead to the protection miscoordination amongst relays, fuses, and reclosers [16, 57]. Moreover, in the presence of DGs, both DG and the main grid will contribute to the fault and hence, the fault current will be shared between them. This can reduce the fault contribution of the main grid and cause a delayed operation (or non-operation) of the corresponding relays, which is known as “blinding of protection"[39]. The severity of protection blinding depends on the local short-circuit level, grid impedance, and DG capacity and location [16]. 3.1.2. Change in the power flow direction Connection of a DG to a distribution feeder can also change the power flow and fault current direction in the corresponding feeder [55]. Therefore, the coordination amongst current based devices can be disrupted as most of them are non-directional units. On the other hand, when a DG is installed on a feeder, it can contribute to faults located on adjacent radial feeders. In this case, due to the change of the fault current direction (i.e., from feeder to main bus), the non-directional relays may incorrectly operate for a fault in the neighboring feeder. This issue, which is referred to as the “false tripping” in the technical literate [39], can decreases the system reliability. It should be pointed out that, with the addition of DGs to distribution networks, the demands will play a more active role in power systems. Thus, the system operational condition may regularly change. This requires the protection system adapting itself to the new operational situation in order to ensure system reliability. 3.2. Protection Challenges in DC Systems In addition to the aforementioned issues which may happen in both AC and DC systems with DGs, there are specific challenges which are related to the use of conventional protection devices in DC systems. These issues, which can exist with or without the presence of DGs, are described in the following subsections. 3.2.1. Difficulties in the coordination of O/C relays The key point in the coordination of time-inverse O/C protective devices is the discrepancy between the fault currents measured by them. Due to low value of the line reactance and the high rising rate of DC fault currents, coordination of O/C relays in DC systems is a challenging task [58, 59]. As mentioned before, the raising rate of DC fault currents is relatively higher than AC fault currents. Therefore, subsequent to the fault, all in-series O/C relays simultaneously measure a high 9 I I ⁄ ratio. This may lead them to operate on instantaneous mode. Moreover, O/C relays must be able to effectively detect both PP and PG faults, whereas there is a significant difference between the current magnitudes of these two types of fault. If the relay settings are selected based on the PP fault currents, it may result in the delayed operation of the protection scheme for PG faults. On the other hand, selection of a low pick-up for the relay can cause protection mis-coordination for PP faults. Reference [18] has analyzed various fault scenarios for a typical DC feeder. The results of the study show that O/C relays cannot protect DC systems in a coordinated manner, leading to a decreased selectivity. Although definite-time O/C relays can be used as an option to achieve selectivity in DC systems, coordination of definite-time relays may result in a long fault clearance in large DC systems with several radial lines [60]. 3.2.2. Inadequacy of AC circuit breakers (ACCBs) ACCBs are conventional fault current interrupters in distribution systems; they typically have a mechanical operating mechanism which is capable of clearing the fault in several tens of milliseconds [61]. ACCBs interrupt the fault current during a zero crossing of the current waveform. DC fault currents, however, do not cross zero point. Moreover, DC systems require a relatively faster protection system capable of operating in several milliseconds to prevent any damage to the freewheeling diodes of VSCs [18, 49, 62]. Therefore, conventional ACCBs are not suitable for fault current interruption in DC systems. Different types of solid-state and hybrid DC breakers have been proposed/implemented by researchers/engineers [63, 64]. However, due to the economic and technical issues associated with these CBs, fault interrupting devices are still one of the main challenges in the development of DC systems. Table 2 provides a summary of the main protection issues in AC distribution systems embedding DGs as well as MVDC grids. Table 2. Main issues associated with the use of conventional protection schemes in AC and DC distribution systems. Method AC distribution systems DC distribution systems O/C based fault detection Without DG:  Coordination of protection devices.  Detection of High-Impedance Faults (HIF) With DG:  Change in the current of the feeder which can cause nuisance tripping [54, 56].  Mis-coordination between current based devices due to the change in the minimum and maximum level of fault and also current direction [8, 54].  False tripping [39].  Blinding of protection [16].  Requirement to relays with flexible setting. Without DG:  Difficult relay coordination due to the high raising rate of DC fault currents [58, 59].  Fault resistance changes not only the peak value of the fault current, but also changes its specifications [45]. With DG:  Similar issues as AC systems.  Requirement for a fast action protection limits obtaining of the useful information for fault location [49]. AC circuit breakers  ACCBs interrupt the fault current at zero-crossing points which do not exist in DC fault currents.  ACCBs are not fast enough to prevent damages on the freewheeling diodes of the VSC.  Major economic and technological challenges around production of solid-state or hybrid DCCBs. 16 Table 4. Compare the performance of fault interruption schemes for a typical VSC-based MVDC Systems, shown in Fig. 1. Fault interruption method Protection system description parts which loss the supply after fault at F1 (see Fig. 1) Remarks Converter blocking  Blocking the converter  No switch in points A and B Entire DC system.  No selective protection and reduce the reliability.  Incapability in breaking capacitor discharge current.  No backup protection.  Incapability in breaking fault current feeding from AC-side (for typical VSCs). Converter blocking with AC-side CB  Blocking the converters  AC-side CB  No switch in points A and B Entire DC system.  No selective protection.  No fast enough method to prevent damage on freewheeling diodes.  Incapability in breaking capacitor discharge current.  Negative impact on AC side network. Converter blocking with DC switches and AC-side CB  Blocking the converter  AC-side CB  Fast isolating DC switches in points A and B Temporary overall blackout during ‘cut and try’ process and then Line23.  Provide selectivity after a ‘cut and try’ process.  No fast enough method to prevent damage on freewheeling diodes.  Incapability in breaking capacitor discharge current.  Impacts on the operation of sensitive loads.  Negative impact on AC side network. Employment of DCCB [51, 62]  DC CB for main capacitor Based on the existence of switches in points B.  No backup protection.  Destructive impacts on DC-bus voltage and power quality. Employment of DCCB [105, 106]  DC CBs in point A  Fast isolating DC switches in point B Temporary overall blackout during ‘cut and try’ process and then Line23.  Provide selectivity after an overall blackout.  Can impact on the operation of sensitive loads. Employment of DCCB [46, 107]  DC CBs in both A and B Points Only the faulty line (Line23).  Costly.  Selective protection.  Requirement to effective fault detection and location methods. 5.2. Fault Detection Methods Although different types of fault detection techniques have been proposed for AC systems, protective methods in DC systems are still in the early stage of development [58]. Moreover, the characteristics of DC systems limit the variety of the methods that can be employed to detect faults in these systems. For instance, a number of fault location methods are designed for AC systems, which work based on the phasor and harmonic analysis. However, due to the lack of frequency and phasor information, these methods are unlikely to be applied to DC systems [49]. Moreover, the lack of information in time domain limits the use of digital-signal-processing-based methods, such as DFT-based methods [58]. On the other hand, the need for a fast protection in DC networks prevents the application of those methods that extract fault data from the voltage and current waveforms [18, 49]. In the following section, the most important proposed methods for protection of active MVDC system are discussed. 5.2.1. Current-Based Protection Due to the simplicity of O/C protection, they are always the first choice for the protection of AC distribution systems. However, as explained in Section 3.2., this type of protection does not provide adequate selectivity for multi-terminal DC systems. Nonetheless, these relays can be used along with other types of protective functions to protect small DC grids. For instance, Reference [25] has proposed to analyze the magnitude of DC-link voltage along with the fault current in order to locate the fault in low-voltage DC microgrids. In Reference [62], a hybrid relay has been devised which is based on overcurrent and under-voltage elements; once both the overcurrent and under-voltage element pick up, the relay confirms the occurrence of the fault. The methodology proposed in [108] and the O/C-based relay suggested in [109] have been designed 17 based on the slope of the current in DC networks. However, as discussed in Section 3.1., the O/C-based methods can potentially fail when DGs are integrated into the network. Establishing communications between O/C relays has been proposed to improve the protection selectivity. For instance, References [110] suggests using the current magnitude, current direction, and voltage of the DC bus to provide a fast and reliable protection for low-voltage DC networks. In this method, faults are detected by monitoring the DC current of the individual feeders and the voltage of the DC bus. Then, the faulty feeder is determined based on the direction of the DC fault currents. It is noted that the feeder relays exchange the information of fault current directions via a suitable communication link. If a relay detects the fault with a forward current direction, its corresponding feeder is recognized as the faulty feeder and is disconnected from the DC bus. 5.2.2. Distance Protection In [46], a distance protection scheme has been proposed for MVDC networks. The salient difference between the proposed method and the conventional distance protection in AC system is on the calculation of the fault location. As compared to AC systems, the method of Reference [46] employs a simpler formulation to achieve a fast fault detection. According to the proposed methodology, the fault distance is estimated using two DC measuring elements installed on the protected line, and is given by:  =  (  )  (  ) −  (  )  (10) where () and () are the measured voltages by the two DC measuring elements, and  denotes the distance between these two measuring devices. This method has a favorable fast detecting time and also is applicable in DC systems with DGs. Active impedance estimation (AIE) has also been suggested in [111], where a current with a wide-range frequency is injected to the DC feeder while the resultant voltage is recorded. Then, using the measured voltage and current, the equivalent system impedance is estimated. The main challenge associated with the distance protection is that it is vulnerable to the fault impedance. Also, the choice of a proper frequency range for injected current is an important shortcoming of the AIE method. 5.2.3. Differential Protection As discussed in Section 4.1.3, differential protection has an accurately defined protection zone. The fault current level, the rate-of-change-of the current, existence of DGs, and fault resistance have relatively low impact on the performance of differential protection, making differential protection one of the best options for the protection of DC systems [18]. Reference [40] has proposed a protection methods for DC systems in which each section of the system is protected by a master controller; the controller, in turn, operates based on the difference between the measured currents at two ends of the protected section. If the current difference is more than a threshold, it is interpreted as a fault and trip commands are sent to the solid-state switches located at both ends of the faulty section. References [112, 113] suggested that a telecommunication link should be used between the protective devices in the both sides of each DC feeder. Then, each differential relay, which is installed on one side of the line, will only send the trip command to its corresponding CB. It is remembered that the protection system must be very fast for DC systems and, thus, differential protection is a proper choice. The results of Reference [114] show that differentialbased protection methods can detect DC faults in less than 40µs while the operating time of differential protection in AC networks is more than 20ms; these times are without considering the communication delay. It is worth noting that most of differential relays in Ac systems have to compare both the magnitude and the phase-angle of 3phase currents, whereas only the current magnitude are compared in DC systems; therefore, it can operate faster. It should be pointed out that communication delay and/or failure must also be taken into consideration when differential protection systems are designed, especially in case of MVDC feeders. For example, Reference [107] has employed O/C relays to provide backup protection if the communication network fails. Nonetheless, providing remote backup for adjacent protections, dependency on the communication network, and potential need for synchronized measurements in large systems are some of the challenges associated with differential protection in DC systems. 5.2.4. Signal-Processing Based Methods To overcome the challenges about the fault location in DC grids and provide a selective protection for these systems, wavelettransform-based methods have been suggested in [34, 115, 116]. In these methods, the criteria of fault location are defined based on the analysis of DC voltage and currents through wavelet transform (WT). For instance, a fault detection/location technique has been proposed in [34], which is based on the wavelet-transform coefficients of voltage and current as well as magnitude and derivative of the voltage. On the other hand, References [116] has used complex-wavelet coefficients of transient currents to detect DC faults. The use of a feature vector containing the energy of wavelet coefficients has been suggested in [115]; the proposed vector is generated based on the multi-resolution analysis (MRA) and compared with a 18 predefined threshold to detect the fault. The method proposed in [115] has also shown satisfactory results for the DC systems in the presence of DGs. However, since the fault location criteria and settings vary from network to network, the application of feature network may not provide a generic method for DC systems. Artificial Neural Networks (ANNs) have widely been used in AC power system. In most cases, the input data to ANN is obtained from the analysis of post-fault waveforms. For instance, Fourier transform has been used in [117] to extract the harmonic contents of voltages/currents in order to feed an ANN. However, as mentioned before, FFT cannot be easily used in DC systems due to the lack of time-domain information as well as required time for the process. Therefore, it has been suggested in [118] that the sampled value of DC current and voltage be fed to ANN directly. The main concerns about the direct use of voltage and current samples include noise and incorrect sampling [34]. Therefore, the use of wavelet transform and multi-resolution analysis (MRA) has respectively been suggested in [58, 119]in order to extract the feature vector of faults and feed them to an ANN. It is worth mentioning that the ANN-based protection schemes have the capability of both detection and classification of DC faults. The travelling-waves-based protection methods are also proposed for DC systems [120-122]. Following the fault occurrence in a line, the travelling waves are propagated from the fault point to the both sides of the line. By using the synchronized measurements, the accurate difference in arrival times of the travelling waves to each end of the line is determined. This means if the velocity of travelling waves is known, the fault location can be calculated. Reference [120] has used a travelling-wave- based method to protect multi-terminal DC systems with DGs. However, due to the small length of distribution feeders, it is very difficult to obtain the exact time difference and locate the faulty feeder. Moreover, since the travelling waves propagate along the lines of a multi-terminal system, most of the measurement devices installed within the DC network may receive these waves. As such, the travelling wave boundary method of Reference [122] may not find the exact location of the fault [116]. The abovementioned issues should be added to the concerns associated with the use of some sort of synchronizing mechanism for travelling waves in long lines 6. COMPARISSION OF PROTECTION METHODS IN AC AND DC NETWORKS Different protection methods for AC and DC distribution networks were explained in Section 4 and 5, respectively. The main features of these methods are summarized and compared in Table 5. 19 Table 5. A summary of protection methods in AC and DC networks. 7. CONCLUSIONS AND FUTURE TRENDS This paper analyzed the fault current characteristics in AC and DC distribution systems. The issues associated with the protection of these systems in the presence of DGs were also explained in the paper. Moreover, the methods proposed for the protection of both AC and DC distribution systems embedding DGs have been compared. The analyses reviewed in this study show that the conventional protection schemes must be modified to provide adequate protection for distribution systems with DGs. In particular, the realization of future DC systems requires further investigation about protection issues/solution, especially in multi-terminal DC systems with DGs. The outcomes of this study are of great interest for protective relay manufacturers, utility engineers as well as academicians and researchers. The following are specific conclusions and/or recommendations of this study for future works: - Fault detection/location methods in AC systems heavily rely on the processing of local values (current, voltage, harmonic contents, etc.) that are not effective for DC systems. Moreover, conventional protection methods, such as directional O/C relays and distance protection, must be modified based on the characteristics of DC networks during Fault detection method AC distribution systems DC distribution systems Over current  Simple algorithm.  Inefficient in the presence of DGs.  Fast method.  Should be used with other methods or equipped with communication links to provide selectivity.  Applicable in fault interrupt methods based on blocking the converters when selectivity is not desired. Differential  Mostly, phase and Magnitude of three-phase currents are compared.  Detects faults in 20-50ms.  Only the magnitudes of DC currents are compared.  Faster than AC differential relays.  Insensitive to high raising rate of DC currents and fault resistance. Distance  The measured current and voltage are used for distance estimation.  Use of symmetrical components analysis to avoid the impact of fault resistance.  Simple algorithm (use simpler fault location estimator).  Faster than AC relays.  More sensitivity to fault resistance (as compared to AC systems). Fault current limiting  Typically consists of constant or variable inductors.  Can be done by external inductors, or the current limiting modes of especial converter.  Requires high-speed semiconductor switches.  Requires devices with higher withstand rating DC current with high raising rate. Intelligent methods such as ANN, Fuzzy  Fast methods for fault detection, classification, and location without requirement to complex mathematical equations.  Requirements for analysis of the post-fault waveforms to input proper data to the ANN.  Frequency based transformations are not applicable for obtaining the input data.  Direct use of sampled data to the ANN increases the complexity of its structure and its training time.  Direct use of measured data increases the impact of noises and reduces the accuracy. Wavelet transform  Effective for fault detection and location with or without other methods, e.g. wavelet-ANN, wavelet-Fuzzy, etc.  Applicable for the analysis post-fault waveforms.  Can be used with intelligent methods for the protection of DC systems with DGs. Communication Based  Is increasing in distribution systems and smart grids due to the providing a fast, accurate and selective protection.  Can be applicable for coordination of O/C relays instead of using time grading methods.  Delay on the communication link can be a major concern.  Lack of the standard protocols for DC systems. Directional O/C  Detects the fault current direction according to the relative phases of the voltage and current.  Requirement to accurate and fast methods for detecting the current direction. 20 faults and transient incidents. Therefore, worldwide application of DC distribution systems requires a fresh look into the traditional protection schemes. - The effect of fault resistance on AC and DC systems are not exactly the same. Therefore, the proposed methods for high-impedance fault detection in AC systems are not necessarily applicable to DC systems. However, to the best of authors’ knowledge, no independent study has been conducted on the detection and location of high-impedance faults in DC distribution systems. - Due to the characteristics of DC fault currents, ACCBs are not suitable for fault current interruption in DC systems. On the other hand, economical concerns and technical challenges preclude the widespread use of DCCBs. Therefore, further studies are required to address the issues associated with fault breaking devices in DC distribution systems; the problem particularly manifests itself in medium-voltage level and above. - The high rising rate of DC fault currents makes it difficult to coordinate current-based protective devices in these systems. Although the use of communication technologies may enhance the performance of DC protection systems and improve the selectivity, there are other issues such as communication delays and the speed of fault detection methodology which should be taken into consideration. - The grounding method has a significant impact on the fault behavior and, hence, protection performance in DC systems. However, this factor has not been fully investigated in the existing technical literature. It is an important subject that should be addressed in the future studies. Acknowledgements This work was supported in part by the Spanish Ministry of Economy and Competitiveness under Project ENE2013-48428-C2- 2-R. The work of M.Monadi was supported by the Ministry of Science, Research, and Technology, Iran. Any opinions, findings, and conclusions or recommendations expressed in this material are those of the authors and do not necessarily reflect those of the host institutions or founders. 8. REFERENCES [1] [1] Borges CLT. An overview of reliability models and methods for distribution systems with renewable energy distributed generation. Renewable and Sustainable Energy Reviews. 2012;16:4008-15. [2] Justo JJ, Mwasilu F, Lee J, Jung J-W. AC-microgrids versus DC-microgrids with distributed energy resources: A review. Renewable and Sustainable Energy Reviews. 2013;24:387-405. [3] Karabiber A, Keles C, Kaygusuz A, Alagoz BB. An approach for the integration of renewable distributed generation in hybrid DC/AC microgrids. Renewable Energy. 2013;52:251-9. [4] Tan W-S, Hassan MY, Majid MS, Abdul Rahman H. Optimal distributed renewable generation planning: A review of different approaches. Renewable and Sustainable Energy Reviews. 2013;18:626-45. [5] Joselin Herbert GM, Iniyan S, Amutha D. A review of technical issues on the development of wind farms. Renewable and Sustainable Energy Reviews. 2014;32:619-41. [6] Abdullah M, Agalgaonkar A, Muttaqi K. Assessment of energy supply and continuity of service in distribution network with renewable distributed generation. Applied Energy. 2014;113:1015-26. [7] Marvasti AK, Yong F, DorMohammadi S, Rais-Rohani M. Optimal Operation of Active Distribution Grids: A System of Systems Framework. Smart Grid, IEEE Transactions on. 2014;5:1228-37. [8] Conti S. Analysis of distribution network protection issues in presence of dispersed generation. Electric Power Systems Research. 2009;79:49-56. [9] El-Zonkoly AM. Fault diagnosis in distribution networks with distributed generation. Electric Power Systems Research. 2011;81:1482- 90. [10] Pandi VR, Zeineldin H, Xiao W. Determining optimal location and size of distributed generation resources considering harmonic and protection coordination limits. Power Systems, IEEE Transactions on. 2013;28:1245-54. [11] Ustun TS, Ozansoy C, Zayegh A. Modeling of a centralized microgrid protection system and distributed energy resources according to IEC 61850-7-420. Power Systems, IEEE Transactions on. 2012;27:1560-7. [12] Coster EJ, Myrzik JM, Kruimer B, Kling WL. Integration issues of distributed generation in distribution grids. Proceedings of the IEEE. 2011;99:28-39. [13] Basak P, Chowdhury S, Halder nee Dey S, Chowdhury S. A literature review on integration of distributed energy resources in the perspective of control, protection and stability of microgrid. Renewable and Sustainable Energy Reviews. 2012;16:5545-56. [14] Ruiz-Romero S, Colmenar-Santos A, Mur-Pérez F, López-Rey Á. Integration of distributed generation in the power distribution network: The need for smart grid control systems, communication and equipment for a smart city — Use cases. Renewable and Sustainable Energy Reviews. 2014;38:223-34. 21 [15] Zamani MA, Sidhu TS, Yazdani A. A Protection Strategy and Microprocessor-Based Relay for Low-Voltage Microgrids. Power Delivery, IEEE Transactions on. 2011;26:1873-83. [16] Firouz Y, Lobry J, Vallée F, Durieux O. Numerical Comparison of the Effects of Different Types of Distributed Generation Units on Overcurrent Protection Systems in MV Distribution Grids. Renewable Energy: An International Journal. 2014. [17] Noroozian R, Abedi M, Gharehpetian G, Hosseini S. Distributed resources and DC distribution system combination for high power quality. International Journal of Electrical Power & Energy Systems. 2010;32:769-81. [18] Fletcher SDA, Norman PJ, Galloway SJ, Crolla P, Burt GM. Optimizing the Roles of Unit and Non-unit Protection Methods Within DC Microgrids. Ieee T Smart Grid. 2012;3:2079-87. [19] Elsayed AT, Mohamed AA, Mohammed OA. DC microgrids and distribution systems: An overview. Electric Power Systems Research. 2015;119:407-17. [20] Yang J, Fletcher JE, O'Reilly J. Multiterminal DC wind farm collection grid internal fault analysis and protection design. Power Delivery, IEEE Transactions on. 2010;25:2308-18. [21] Dastgeer F. Direct current distribution systems for residential areas powered by distributed generation: Victoria University; 2011. [22] Arcidiacono V, Monti A, Sulligoi G. Generation control system for improving design and stability of medium-voltage DC power systems on ships. IET Electrical Systems in Transportation. 2012;2:158. [23] Nilsson D, Sannino A. Efficiency analysis of low-and medium-voltage dc distribution systems. Power Engineering Society General Meeting, 2004 IEEE: IEEE; 2004. p. 2315-21. [24] Baran ME, Mahajan NR. DC distribution for industrial systems: opportunities and challenges. Industry Applications, IEEE Transactions on. 2003;39:1596-601. [25] Salomonsson D, Soder L, Sannino A. Protection of low-voltage DC microgrids. Power Delivery, IEEE Transactions on. 2009;24:1045- 53. [26] Larruskain DM, Zamora I, Abarrategui O, Iturregi A. VSC-HVDC configurations for converting AC distribution lines into DC lines. International Journal of Electrical Power & Energy Systems. 2014;54:589-97. [27] De Doncker RW, Meyer C, Lenke RU, Mura F. Power electronics for future utility applications. Power Electronics and Drive Systems, 7th International Conference on: IEEE; 2007. p. K-1-K-8. [28] Mura F, De Doncker RW. Design aspects of a medium-voltage direct current (MVDC) grid for a university campus. Power Electronics and ECCE Asia (ICPE & ECCE), 2011 IEEE 8th International Conference on: IEEE; 2011. p. 2359-66. [29] Planas E, Andreu J, Gárate JI, de Alegría IM, Ibarra E. AC and DC technology in microgrids: A review. Renewable and Sustainable Energy Reviews. 2015;43:726-49. [30] Majumder R. Aggregation of microgrids with DC system. Electric Power Systems Research. 2014;108:134-43. [31] Rufer A, Kenzelmann S. Modular DC/DC Converter for DC Distribution and Collection Networks [PhD]: ÉCOLE POLYTECHNIQUE FÉDÉRALE DE LAUSANNE; 2012. [32] Chen W, Huang AQ, Li C, Wang G, Gu W. Analysis and comparison of medium voltage high power DC/DC converters for offshore wind energy systems. Power Electronics, IEEE Transactions on. 2013;28:2014-23. [33] Larruskain DM, Zamora I, Abarrategui O, Aginako Z. Conversion of AC distribution lines into DC lines to upgrade transmission capacity. Electric Power Systems Research. 2011;81:1341-8. [34] De Kerf K, Srivastava K, Reza M, Bekaert D, Cole S, Van Hertem D, et al. Wavelet-based protection strategy for DC faults in multiterminal VSC HVDC systems. Generation, Transmission & Distribution, IET. 2011;5:496-503. [35] Li H, Li W, Luo M, Monti A, Ponci F. Design of smart MVDC power grid protection. Instrumentation and Measurement, IEEE Transactions on. 2011;60:3035-46. [36] Anderson PM. Power system protection: McGraw-Hill New York; 1999. [37] Grainger JJ, Stevenson WD. Power system analysis: McGraw-Hill New York; 1994. [38] Kundur P, Balu NJ, Lauby MG. Power system stability and control: McGraw-hill New York; 1994. [39] Darwish A, Abdel-Khalik A, Elserougi A, Ahmed S, Massoud A. Fault current contribution scenarios for grid-connected voltage source inverter-based distributed generation with an LCL filter. Electric Power Systems Research. 2013;104:93-103. [40] Park J-D, Candelaria J. Fault Detection and Isolation in Low-Voltage DC-Bus Microgrid System. IEEE Transactions on Power Delivery. 2013;28:779-87. [41] Li X, Song Q, Liu W, Rao H, Xu S, Li L. Protection of nonpermanent faults on DC overhead lines in MMC-based HVDC systems. Power Delivery, IEEE Transactions on. 2013;28:483-90. [42] Jimmy Ehnberg TN. Protection system design for MVDC collection grids for off-shore wind farms. Elforsk rapport 12:02. elforsk.se/Rapporter/?download=report&rid=12_02_2011. [43] Falcones S, Mao X, Ayyanar R. Topology comparison for solid state transformer implementation. Power and Energy Society General Meeting, 2010 IEEE: IEEE; 2010. p. 1-8. [44] Deng F, Chen Z. Design of protective inductors for HVDC transmission line within DC grid offshore wind farms. Power Delivery, IEEE Transactions on. 2013;28:75-83. [45] Fletcher S, Norman P, Galloway S, Burt G. Determination of protection system requirements for DC unmanned aerial vehicle electrical power networks for enhanced capability and survivability. IET Electrical Systems in Transportation. 2011;1:137-47. [46] Yang J, Fletcher JE, O'Reilly J. Short-circuit and ground fault analyses and location in VSC-based DC network cables. Industrial Electronics, IEEE Transactions on. 2012;59:3827-37. [47] Candelaria J, Park J-D. VSC-HVDC system protection: A review of current methods. Power Systems Conference and Exposition (PSCE), 2011 IEEE/PES: IEEE; 2011. p. 1-7. [48] Tang L, Ooi B-T. Protection of VSC-multi-terminal HVDC against DC faults. Power Electronics Specialists Conference, 2002 pesc 02 2002 IEEE 33rd Annual: IEEE; 2002. p. 719-24. 22 [49] Park JD, Candelaria J, Ma LY, Dunn K. DC Ring-Bus Microgrid Fault Protection and Identification of Fault Location. IEEE Transactions on Power Delivery. 2013;28:2574-84. [50] Jin C, Dougal RA, Liu S. Solid-state Over-current Protection for Industrial DC Distribution Systems. 4th International Energy Conversion Engineering Conference and Exhibit (IECEC). 2006:26-9. [51] Peng C, Huang AQ. A protection scheme against DC faults VSC based DC systems with bus capacitors. Applied Power Electronics Conference and Exposition (APEC), 2014 Twenty-Ninth Annual IEEE: IEEE; 2014. p. 3423-8. [52] Ai Q, Wang X, He X. The impact of large-scale distributed generation on power grid and microgrids. Renewable Energy. 2014;62:417- 23. [53] Kamel RM. Effect of wind generation system types on Micro-Grid (MG) fault performance during both standalone and grid connected modes. Energy Conversion and Management. 2014;79:232-45. [54] Javadian SAM, Haghifam MR, Fotuhi Firoozabad M, Bathaee SMT. Analysis of protection system’s risk in distribution networks with DG. International Journal of Electrical Power & Energy Systems. 2013;44:688-95. [55] Girgis A, Brahma S. Effect of distributed generation on protective device coordination in distribution system. Power Engineering, 2001 LESCOPE'01 2001 Large Engineering Systems Conference on: IEEE; 2001. p. 115-9. [56] Geidl M. Protection of power systems with distributed generation: state of the art: ETH, Eidgenössische Technische Hochschule Zürich, EEH Power Systems Laboratory; 2005. [57] El-Khattam W, Sidhu TS. Restoration of directional overcurrent relay coordination in distributed generation systems utilizing fault current limiter. Power Delivery, IEEE Transactions on. 2008;23:576-85. [58] Li WL, Monti A, Ponci F. Fault Detection and Classification in Medium Voltage DC Shipboard Power Systems With Wavelets and Artificial Neural Networks. Instrumentation and Measurement, IEEE Transactions on 2014;63:2651-65. [59] Cuzner R, MacFarlin D, Clinger D, Rumney M, Castles G. Circuit breaker protection considerations in power converter-fed DC Systems. Electric Ship Technologies Symposium, 2009 ESTS 2009 IEEE2009. p. 360-7. [60] Gopalan SA, Sreeram V, Iu HH. A review of coordination strategies and protection schemes for microgrids. Renewable and Sustainable Energy Reviews. 2014;32:222-8. [61] Gas insulated MV circuit-breakers. In: ABB, editor. Medium voltage products: www.abb.com; 2013. [62] Baran ME, Mahajan NR. Overcurrent protection on voltage-source-converter-based multiterminal DC distribution systems. Power Delivery, IEEE Transactions on. 2007;22:406-12. [63] M. Callavik AB, J. Häfner, B. Jacobson. The Hybrid HVDC Breaker: An innovation breakthrough enabling reliable HVDC grids. 2012 ed. www.abb.com ABB Grid Systems, 2012; 2012. [64] Flourentzou N, Agelidis VG, Demetriades GD. VSC-Based HVDC Power Transmission Systems: An Overview. Power Electronics, IEEE Transactions on. 2009;24:592-602. [65] Yazdanpanahi H, Li YW, Xu W. A new control strategy to mitigate the impact of inverter-based DGs on protection system. Smart Grid, IEEE Transactions on. 2012;3:1427-36. [66] Ma J, Li J, Wang Z. An adaptive distance protection scheme for distribution system with distributed generation. Critical Infrastructure (CRIS), 2010 5th International Conference on: IEEE; 2010. p. 1-4. [67] Sortomme E, Venkata S, Mitra J. Microgrid protection using communication-assisted digital relays. Power Delivery, IEEE Transactions on. 2010;25:2789-96. [68] Tang J, McLaren P. A wide area differential backup protection scheme for shipboard application. Power Delivery, IEEE Transactions on. 2006;21:1183-90. [69] Dambhare S, Soman S, Chandorkar M. Adaptive current differential protection schemes for transmission-line protection. Power Delivery, IEEE Transactions on. 2009;24:1832-41. [70] Zamani A, Sidhu T, Yazdani A. A strategy for protection coordination in radial distribution networks with distributed generators. Power and Energy Society General Meeting, 2010 IEEE: IEEE; 2010. p. 1-8. [71] Jones D, Kumm J. Future distribution feeder protection using directional overcurrent elements. Rural Electric Power Conference (REPC), 2013 IEEE: IEEE; 2013. p. B4-1-B4-7. [72] Jiadong H, Zeyun Z, Xiaobo D. The Influence of the Distributed Generation to the Distribution Network Line Protection and Countermeasures. Physics Procedia. 2012;24:205-10. [73] Zhang Y, Dougal RA. Novel dual-FCL connection for adding distributed generation to a power distribution utility. Applied Superconductivity, IEEE Transactions on. 2011;21:2179-83. [74] Hussain B, Sharkh S, Hussain S, Abusara M. An Adaptive Relaying Scheme for Fuse Saving in Distribution Networks With Distributed Generation. 2013. [75] Ghanbari T, Farjah E. Development of an Efficient Solid-State Fault Current Limiter for Microgrid. Power Delivery, IEEE Transactions on. 2012;27:1829-34. [76] Nimpitiwan N, Heydt GT, Ayyanar R, Suryanarayanan S. Fault current contribution from synchronous machine and inverter based distributed generators. Power Delivery, IEEE Transactions on. 2007;22:634-41. [77] Basso TS, DeBlasio R. IEEE 1547 series of standards: interconnection issues. Power Electronics, IEEE Transactions on. 2004;19:1159- 62. [78] Brahma SM, Girgis AA. Development of adaptive protection scheme for distribution systems with high penetration of distributed generation. Power Delivery, IEEE Transactions on. 2004;19:56-63. [79] Javadian S, Haghifam M-R, Rezaei N. A fault location and protection scheme for distribution systems in presence of dg using MLP neural networks. Power & Energy Society General Meeting, 2009 PES'09 IEEE: IEEE; 2009. p. 1-8. [80] Dewadasa M, Ghosh A, Ledwich G, Wishart M. Fault isolation in distributed generation connected distribution networks. IET generation, transmission & distribution. 2011;5:1053-61. 23 [81] Conti S, Nicotra S. Procedures for fault location and isolation to solve protection selectivity problems in MV distribution networks with dispersed generation. Electric Power Systems Research. 2009;79:57-64. [82] Ma J, Wang X, Zhang Y, Yang Q, Phadke A. A novel adaptive current protection scheme for distribution systems with distributed generation. International Journal of Electrical Power & Energy Systems. 2012;43:1460-6. [83] Amraee T. Coordination of directional overcurrent relays using seeker algorithm. Power Delivery, IEEE Transactions on. 2012;27:1415-22. [84] Najy WK, Zeineldin HH, Woon WL. Optimal protection coordination for microgrids with grid-connected and islanded capability. Industrial Electronics, IEEE Transactions on. 2013;60:1668-77. [85] Zayandehroodi H, Mohamed A, Shareef H, Farhoodnea M. A novel neural network and backtracking based protection coordination scheme for distribution system with distributed generation. International Journal of Electrical Power & Energy Systems. 2012;43:868-79. [86] Rezaei N, Haghifam M-R. Protection scheme for a distribution system with distributed generation using neural networks. International Journal of Electrical Power & Energy Systems. 2008;30:235-41. [87] Javadian SAM, Haghifam MR, Bathaee SMT, Fotuhi Firoozabad M. Adaptive centralized protection scheme for distribution systems with DG using risk analysis for protective devices placement. International Journal of Electrical Power & Energy Systems. 2013;44:337-45. [88] Mirsaeidi S, Mat Said D, Wazir Mustafa M, Hafiz Habibuddin M, Ghaffari K. An analytical literature review of the available techniques for the protection of micro-grids. International Journal of Electrical Power & Energy Systems. 2014;58:300-6. [89] Wan H, Li K, Wong K. An adaptive multiagent approach to protection relay coordination with distributed generators in industrial power distribution system. Industry Applications, IEEE Transactions on. 2010;46:2118-24. [90] Zamani MA, Yazdani A, Sidhu TS. A communication-assisted protection strategy for inverter-based medium-voltage microgrids. Smart Grid, IEEE Transactions on. 2012;3:2088-99. [91] Perera N, Rajapakse A, Buchholzer T. Isolation of faults in distribution networks with distributed generators. Power Delivery, IEEE Transactions on. 2008;23:2347-55. [92] Laaksonen HJ. Protection principles for future microgrids. Power Electronics, IEEE Transactions on. 2010;25:2910-8. [93] Mackiewicz R. Overview of IEC 61850 and Benefits. Power Systems Conference and Exposition, 2006 PSCE'06 2006 IEEE PES: IEEE; 2006. p. 623-30. [94] CODE P. Communication networks and systems in substations–Part 5: Communication requirements for functions and device models. 2003. [95] Vanfretti L, Chenine M, Almas MS, Leelaruji R, Angquist L, Nordstrom L. SmarTS Lab—A laboratory for developing applications for WAMPAC Systems. Power and Energy Society General Meeting, 2012 IEEE: IEEE; 2012. p. 1-8. [96] Ishchenko D, Oudalov A, Stoupis J. Protection coordination in active distribution grids with IEC 61850. Transmission and Distribution Conference and Exposition (T&D), 2012 IEEE PES: IEEE; 2012. p. 1-6. [97] Zadeh HK, Manjrekar M. A novel IEC 61850-based distribution line/cable protection scheme design. Innovative Smart Grid Technologies (ISGT), 2012 IEEE PES: IEEE; 2012. p. 1-6. [98] Baran M, Mahajan NR. PEBB based DC system protection: opportunities and challenges. Transmission and Distribution Conference and Exhibition, 2005/2006 IEEE PES: IEEE; 2006. p. 705-7. [99] Peralta J, Saad H, Dennetiere S, Mahseredjian J, Nguefeu S. Detailed and averaged models for a 401-level MMC–HVDC system. Power Delivery, IEEE Transactions on. 2012;27:1501-8. [100] Friedrich K. Modern HVDC PLUS application of VSC in Modular Multilevel Converter topology. Industrial Electronics (ISIE), 2010 IEEE International Symposium on: IEEE; 2010. p. 3807-10. [101] Cairoli P, Kondratiev I, Dougal RA. Coordinated control of the bus tie switches and power supply converters for fault protection in dc microgrids. Power Electronics, IEEE Transactions on. 2013;28:2037-47. [102] Tang L, Ooi B-T. Locating and isolating DC faults in multi-terminal DC systems. Power Delivery, IEEE Transactions on. 2007;22:1877-84. [103] Shi J, Tang Y, Wang C, Zhou Y, Li J, Ren L, et al. Active superconducting DC fault current limiter based on flux compensation. Physica C: Superconductivity. 2006;442:108-12. [104] Ghisla U, Kondratiev I, Dougal R. Protection of medium voltage DC power systems against ground faults and negative incremental impedances. IEEE SoutheastCon 2010 (SoutheastCon), Proceedings of the: IEEE; 2010. p. 259-63. [105] Mehdi Monadi CK-C, Alvaro Luna, Jose Ignacio Candela, Pedro Rodriguez. A Protection Strategy for Fault Detection and Location for Multi-Terminal MVDC Distribution Systems with Renewable Energy Systems. ICRERA2014. Milwakee, USA: IEEE; 2014. [106] Farhadi M, Mohammed O. Event-Based Protection Scheme for a Multiterminal Hybrid DC Power System. [107] Yuan C, Haj-ahmed M, Illindala M. Protection Strategies for Medium Voltage Direct Current Microgrid at a Remote Area Mine Site. [108] Fletcher S, Norman P, Galloway S, Burt G. Fault detection and location in DC systems from initial di/dt measurement. Euro Tech Con Conference. 2012. [109] Cinieri E, Fumi A, Salvatori V, Spalvieri C. A New High-Speed Digital Relay Protection of the 3-kVdc Electric Railway Lines. Power Delivery, IEEE Transactions on. 2007;22:2262-70. [110] Emhemed AA, Burt GM. An Advanced Protection Scheme for Enabling an LVDC Last Mile Distribution Network. 2014. [111] Christopher E, Sumner M, Thomas DWP, Xiaohui W, de Wildt F. Fault Location in a Zonal DC Marine Power System Using Active Impedance Estimation. Industry Applications, IEEE Transactions on. 2013;49:860-5. [112] Descloux J, Raison B, Curis J-B. Protection strategy for undersea mtdc grids. PowerTech (POWERTECH), 2013 IEEE Grenoble: IEEE; 2013. p. 1-6. [113] Hajian M, Zhang L, Jovcic D. DC Transmission Grid with Low Speed Protection using Mechanical DC Circuit Breakers. Power Delivery, IEEE Transactions on. 2014;PP:1-. [114] Fletcher SDA, Norman PJ, Fong K, Galloway SJ, Burt GM. High-Speed Differential Protection for Smart DC Distribution Systems. Smart Grid, IEEE Transactions on. 2014;5:2610-7. 24 [115] Li W, Luo M, Monti A, Ponci F. Wavelet based method for fault detection in medium voltage DC shipboard power systems. Instrumentation and Measurement Technology Conference (I2MTC), 2012 IEEE International: IEEE; 2012. p. 2155-60. [116] Cheng J, Guan M, Tang L, Huang H. A fault location criterion for MTDC transmission lines using transient current characteristics. International Journal of Electrical Power & Energy Systems. 2014;61:647-55. [117] Joorabian M, Taleghani Asl SMA, Aggarwal RK. Accurate fault locator for EHV transmission lines based on radial basis function neural networks. Electric Power Systems Research. 2004;71:195-202. [118] Chanda NK, Fu Y. ANN-based fault classification and location in MVDC shipboard power systems. North American Power Symposium (NAPS), 2011: IEEE; 2011. p. 1-7. [119] Chang C, Kumar S, Liu B, Khambadkone A. Real-time detection using wavelet transform and neural network of short-circuit faults within a train in DC transit systems. Electric Power Applications, IEE Proceedings-. 2001;148:251-6. [120] Azizi S, Afsharnia S, Sanaye-Pasand M. Fault location on multi-terminal DC systems using synchronized current measurements. International Journal of Electrical Power & Energy Systems. 2014;63:779-86. [121] Xiaqing L, Shuyou G, Yiming Z, Yunhua L, Shengtao F. Research on Fault Diagnosis and Protect Model for DC Traction Power Supply System Based on Traveling Wave Theory. Robotics, Automation and Mechatronics, 2006 IEEE Conference on2006. p. 1-5. [122] Xiaolei L, Osman AH, Malik OP. Hybrid Traveling Wave/Boundary Protection for Monopolar HVDC Line. Power Delivery, IEEE Transactions on. 2009;24:569-78.