Model of aeronautical ground lighting system transformers
Abstract
Airport ground lighting (AGL) systems provide visual reference to aircrafts during airport operations. In AGL systems, constant current regulators feed a beacon circuit supplied through isolation transformers. Component modeling is necessary to simulate AGL systems, and thus characterize and predict their behavior. This paper presents an isolation transformer model including transformer core saturation. Moreover, a procedure to estimate transformer model parameters is proposed. Both the model and the estimation method are validated with extensive measurements on more than 20 isolation transformers of different power ratings and trade names.
Full text
UPCommons Portal del coneixement obert de la UPC http://upcommons.upc.edu/e-prints Aquesta és una còpia de la versió author’s final draft d'un article publicat a la revista [ IET Electric Power Applications ]. URL d'aquest document a UPCommons E-prints: http://hdl.handle.net/2117/79229 Paper publicar1 / Published paper : Vidal, D., Monjo, Ll., Sainz, L. and Pedra, J. (2015) Model of aeronautical ground lighting system transformers. IET Electric Power Applications, 9. 5. 239-247. Doi: 10.1049/iet-epa.2014.0282 1 Substituir per la citació bibliogràfica corresponent
Model of Airport Ground Lighting System Transformers D. Vidal1, Ll. Monjo2, L. Sainz2 and J. Pedra2 1 A.A.S.A. Airport of Reus, Reus, 43206, Spain. 2 Department of Electrical Engineering, ETSEIB-UPC, Av. Diagonal 647, Barcelona 08028, Spain. E-mails: [email protected], lluis.mon[email protected], s[email protected]c.edu, [email protected] Abstract: Airport ground lighting (AGL) systems provide visual reference to aircrafts during airport operations. In AGL systems, constant current regulators feed a beacon circuit supplied through isolation transformers. Component modeling is necessary to simulate AGL systems, and thus characterize and predict their behavior. This paper presents an isolation transformer model including transformer core saturation. Moreover, a procedure to estimate transformer model parameters is proposed. Both the model and the estimation method are validated with extensive measurements on more than 20 isolation transformers of different power ratings and trade names. Nomenclature f Frequency of the supply voltage T Period of the supply voltage Angular pulsation of the supply voltage R Winding resistance of the transformer R p , R s Primary and secondary winding resistances X Leakage reactance of the transformer L d Leakage inductance of the transformer L dp , L ds Primary and secondary leakage inductances R Fe Core loss resistance M Core non - linear magnetizing inductance u p , u s Primary and secondary transformer voltages i p , i s Primary and secondary transformer currents
i m Magnetizing current i Fe Core loss resistance current Core magnetic flux p Core magnetic flux across the primary winding f tc Magnetic potential in the transformer core (ftc) Non - linear reluctance N p , N s Primary and secondary winding turns r t Winding turn ratio u p, sc Primary voltage measurements of the short-circuit test i p, sc Primary current measurements of the short-circuit test u p, 0, i p, 0 P rimary voltage and current measurements of the open-circuit test u s, 0 Secondary voltage measurements of the open-circuit test p Fe Transformer active power consumption P N Rated power of the isolation transformer D Length of the underground cables P B A ctive power of beacons R B Resistance of beacons y Vector of the magnetizing inductance function parameters r(y) Residual vector y lb , y ub Lower and upper bound vectors of the magnetizing inductance function parameters M 1 , M 2 , p and i0 Parameters of the magnetizing inductance function 1 Introduction Airport ground lighting (AGL) systems provide visual information by means of beacons to aircrafts in the stages of approaching, landing and taxing operations [1]. These systems are 5 kV series circuits of 2x6 mm2 XLPE insulated copper underground cables where constant current regulators (CCRs) supply beacons through isolation transformers (Fig. 1) [1][5]. Constant current regulators are 5 kV variable voltage sources close to the airport power supply which provide a tunable rms current according to brightness requirements. These regulators modify the supply voltage to maintain the rms current required and ensure circuit continuity, even in case of Underground cable CCR I RL X L YC /2 YC /2 D Beacon Isolation transformer B1 TR1 B2 TR2 Bn TRn BN b TRN b Fig. 1 Airport ground lighting system.
beacon failure. Their standard power ratings are 4, 7.5, 10, 15, 20, 25, 30, 50 and 70 kVA with a usual current rating of 6.6 A (a current rating of 20 A is also common for AGL systems with power ratings above 30 kW). These current ratings have five discrete brightness steps (6.6, 5.2, 4.1, 3.4 and 2.8 A or 20.0, 15.8, 12.4, 10.3 and 8.5 A) [1], [2], [4]. Beacons are visual aids for pilots. Their pattern, intensity, color and direction of light emission are modified according to their function (approach lighting system (ALS), precision approach path indicator (PAPI), runway lighting system (RLS) and taxiway lights and guidance signs). They are generally classified into high and low intensity beacons, with power ratings above and below 150 W, respectively. The former are used for ALS, PAPI and RLS and the latter for taxiway lights and guidance signs [1], [2], [6]. The number of beacons ranges from 10 up to 300 in small and large airport AGL systems, respectively (Nb = 10 to 300 in Fig. 1). Isolation transformers separate CCRs and beacons into primary and secondary circuits. They ensure continuity of the series circuit even in case of beacon failure (allowing functioning beacons to remain lit) and isolate beacons from the high operating voltage of the primary circuit (generally insulated to 5 kV). In the event of beacon failure, the transformers maintain circuit continuity but work in saturation because they operate in open circuit at series circuit rated current. This must be considered in AGL system studies (i.e., in isolation transformer modeling) because it modifies the CCR operating conditions and could reduce AGL system power quality [7]. AGL systems require frequent expensive maintenance and conservation work mainly consisting in the detection and location of failed beacons [5]. AGL simulation tools and component models are necessary to study the behavior of these systems and thus predict their response to electrical events or further technological changes in the system components [4], [5], [8], [9]. Procedures for AGL component parameter estimation are also required. However, there is still a lack of adequate AGL system component models for performing accurate simulations of AGL system electrical response. This paper provides results of measurements on more than 20 actual isolation transformers delivered by the Airport of Reus (Spain) to the power quality laboratory of the Department of Electrical Engineering of the Universitat Politècnica de Catalunya (UPC). A model considering the transformer saturation characteristics is presented from the traditional transformer equivalent circuit. The paper also proposes a method for model parameter estimation. Both are validated with extensive measurements. a b Fig. 2 Experimental tests: a Isolation transformers b Setup of circuit measurements
2 Isolation transformer model Isolation transformers are single-phase transformers made as fully encapsulated units with their own primary and secondary cables (Fig. 2a). In general, they consist of a rectangular magnetic core made of low-loss grain oriented laminations and with separated primary and secondary windings made of enameled copper wire (Fig. 3a). Their power ratings range from 30 to 500 W and their current ratio is generally 6.6/6.6 A (i.e., the winding turn ratio rt is equal to 1). Other turn ratios (e.g., 20/6.6 A) are common in AGL systems with power ratings above 30 kW because the CCR current is greater than 6.6 A to maintain the primary circuit voltage below 5 kV. The transformers used in this paper are ICAO and FAA compliant [2][10]. 2.1 Electric circuit modeling Fig. 3b shows the electric equivalent circuit of isolation transformers, where R = Rp + rt2·Rs and Ld = Ldp + rt2·Lds are the primary/secondary winding resistance and constant leakage inductance, RFe is the core loss resistance and M(im) is the core non-linear magnetizing inductance, which depends on the magnetizing current im. According to Fig. 3b the electric relations of isolation transformers are ( ( ) ) 1 1 ( ( ) ) 0 , p m m p d p t s s t t m m Fe Fe m p s t Fe d d M i i d u R L i r u u dt r dt r dt d M i i R i dt i i i r i (1) where rt = Np/Ns is the winding turn ratio, Np and Ns are the primary and secondary winding turns and p = M(im)·im is the core magnetic flux across the primary winding. 2.2 Magnetic Circuit Modeling Fig. 3c shows the magnetic circuit of isolation transformers, which provides the magnetic flux and current relations: ( ) , p p s s tc tc tc N i N i f f f (2) ip _ + up Np _ + us is Ns b c + + Np·ip Ns·is (ftc) + ftc R Ld ip _ + up RFe _ + urs = rt·us iFe im M(im) irs = is/rt a Fig. 3 Equivalent circuits of isolation transformers: a Isolation transformer b Electric equivalent circuit c Magnetic equivalent circuit.
where Np·ip, Ns·is are the primary/secondary magnetomotive forces, ftc is the magnetic potential in the transformer core, is the core magnetic flux and (ftc) is the non-linear reluctance, which depends on the magnetic potential in the core. By neglecting the current in the core loss resistance with respect to the primary and secondary currents (i.e., im ip + is/rt), (2) can be arranged as follows to obtain the (p im) core saturation curve: 2 1 ( ) ( ) ( ) . p s tc p p p tc m m m t p p i f i N f i M i i r N N (3) The following functional relationship is used to characterize the (p im) core saturation curve M(im) by means of an anhysteretic magnetization curve: 1 2 1 0 , 1 ( ) mp p m M M i M i i (4) where M1, M2, p and i0 are experimental parameters allowing the fitting of the above reluctance function to the (p im) core saturation curve (see Fig. 4): M1 and M2 define the slope of the linear and non-linear segments of the core saturation curve. p defines the shape of the curve. i0 defines the core saturation knee point. 3 Isolation transformer parameter estimation Studies on AGL systems with the isolation transformer model in the previous Section involve the estimation of the transformer equivalent circuit parameters R, Ld, RFe and the core magnetizing inductance M(im) (4) from voltage and current measurements. 3.1 Transformer Winding Parameters The voltage and current measurements of the short-circuit test (i.e., up, sc and ip, sc) provide a fairly accurate i 0 p (Wb) 1.2 0 i m (A) 2 3 4 1 0 M2 M1 + M2 i 0 = 1 A M 1 = 1.05 Wb/A M2 = 0.05 Wb/A p 2 5 20 Fig. 4 ( p im) characteristic of the proposed core saturation curve.
estimation of the transformer winding resistance and leakage inductance. In this test, the secondary voltage is null (i.e., us, sc = 0) and (1) results in , , ,, ( ) , p sc d p sc d p sc p sc d u R L i U R jL I dt (5) where = 2·f and f is the frequency of the sinusoidal supply voltage of the short-circuit test, up, sc. 3.2 Transformer Core Parameters The voltage and current measurements of the open-circuit test (i.e., up, 0, us, 0 and ip, 0) provide an estimation of the transformer core resistance and anhysteretic magnetization curve (4). The core resistance is estimated from the transformer active power balance in the open-circuit test 2 2 ,0 ,0 2 ,0 ,0 ,0 2 ,0 ,0 ,0 ( ) ( ) , t s t s Fe p p p p Fe Fe p p p p mean r u r U p u i R i R Ru i R I (6) where Ip, 0 and Us, 0 are the rms values of the primary current and the secondary voltage of the open-circuit test, respectively. In the previous expression, the primary winding resistance Rp is approximated to half the shortcircuit resistance value (i.e, Rp R/2). Parameters M1, M2, p and i0 of the single-valued function M(im) in (4) are estimated by close fitting of the open-circuit measurements of the (p im) core saturation curve. Considering that the secondary current is null, the measured magnetizing current and flux are evaluated as follows ,0 ,0 ,0 ,0 ,0 ,0 ,0 0 1 ( ) ( ) , t s m p Fe t p s p t s pr t r u i i R d u t r u t d r dt (7) where pr is the residual flux, which is calculated imposing that ,0 0 ( ) 0 ( 1 ), T p t d T f (8) with f being the frequency of the sinusoidal supply voltage open-circuit test, up, 0. Subsequently, the singlevalued (p im) function (4) is determined from the measured (p im) curve as ,0 meas ,0 ,0 ( ) , p mm M i i (9) and parameters M1, M2, p and i0 in (4) are estimated by solving a non-linear least-square algorithm formulated as follows:
min ( ) min ( ) ( ) subject to , T S r r y y lb ub y y y y y y (10) where y = (M1, M2, p and i0), ylb and yub are vectors representing lower and upper bounds of the parameters and r(y) is the residual vector corresponding to differences between samples of the measured and simulated transformer magnetization curves (i.e., the measured and simulated functions Mmeas(im) and M(im) in (9) and (4), respectively) at each measured current value im, 0, meas ,0 ,0 ( ) ( ) ( ) . m m r M i M i y (11) The above non-linear least-square problem is solved by the MATLAB function lsqnonlin (·) [11] considering the following parameter bounds: M1 = (0, M1, ub), where the upper limit value M1, ub is set to 1 H according to the experimental test results. M2 = (0, M2, ub), where the upper limit value M2, ub is set to 3 mH according to the experimental test results. p = (0, 50), where upper limit values above 20 do not affect the solution of the least-square problem. i0 = (0, i0, ub), where the upper limit value i0, ub is chosen by simple inspection of the (p im) core saturation curve. The initial values of the non-linear least-square problem are set as the upper limit values of the parameters divided by 2. 4 Experimental Validation of the Model To validate experimentally the proposed isolation transformer model, several laboratory tests were conducted on four 6.6/6.6 A 50 Hz isolation transformers of different power ratings and trade names (Fig. 2a and Table 1). There are also other isolation transformers of 300 and 400 W power ratings in AGL systems, however, the Table 1 6.6/6.6 A 50 Hz Isolation Transformers Experimentally Tested Technical data Estimated parameters Winding parameters Core parameters Manufacturer PN (W) Supplied load R () Ld (mH) M1 (mH) M2 (mH) p (pu) i0 (A) TR45W # 1 45 45 W low intensity beacons for taxiway lights and guidance signals 0.187 0.370 176.5 1.10 1.11 0.347 TR 60W # 2 60 Signal area and sign panels and 45 W low intensity beacons far from series transformers 0.281 0.849 327.6 1.40 1.20 0.321 TR 150W # 1 150 150 W high intensity beacons for ALS, PAPI and RLS 0.281 1.19 693.8 1.80 0.906 0.286 TR 200W # 3 200 200 W high intensity beacons for ALS, PAPI and RLS 0.301 1.71 650.0 1.80 1.15 0.338
experimental tests reveal that their behavior cannot be accurately described by the proposed model. Further studies out of the paper scope are being performed to understand their behavior and propose and appropriate model for this type of transformers. First, the short- and open-circuit tests were made to estimate the transformer parameters. Subsequently, two tests were conducted to determine the accuracy of the model. The test circuits were fed with the power sources 15 kVA AC Spitzerberger Three-phase Switching Amplifier or 4.5 kVA AC ELGAR Smartwave Switching Amplifier, which can generate tunable voltage waveforms. Recordings were made with a YOKOGAWA DL 708E digital scope. The test set-up consisted of the power supply feeding the test circuits and the oscilloscope suitably connected for measurements (Fig. 2b). Simulations to validate the model were performed with Matlab/Simulink software [11]. 4.1 Estimation of the Isolation Transformer Parameters Five units of the four isolation transformers in Table I were tested to obtain their parameters. The mean of the estimations was adopted as the final parameter value of each transformer type. These mean values are shown in Table I. The winding resistance and leakage inductance were estimated by the short-circuit test at transformer rated Ld (mH) 1.8 0.2 0.6 1.0 1.4 3 Transformer Unit 4 5 2 1 0.32 0.16 0.24 TR 60W TR 45W TR 150W TR 200W R ( ) Fig. 6 Transformer winding parameter estimation. v p ip TR 60W Measured waveforms Simulated waveforms 10 t (ms) 20 0 vp (V), ip (A) 10 10 0 Fig. 5 Measured and simulated voltage and current waveforms in the short-circuit test.
6 Acknowledgements This research was carried out with the support of the A.A.A.S.A Airport of Reus (Spain), which the authors gratefully acknowledge. 7 References 1 Aerodrome design manual, Part 4: Visual aids, 4th Edition International Civil Aviation Organization, 2004. 2 Aerodromes, Volume I: Aerodrome design and operations, Annex 14 to the convention on International Civili Aviation, 4th Edition International Civil Aviation Organization, 2004. 3 Saraf, N., Salvi, R., Salunkhe, N., and Sahasrabuddh, R.: ‘Airfield lamp monitoring & control systems,’ Int. Conf. on Information, Communication and Embedded Systems (ICICES 2013), February. 2013, pp. 1141-1143. 4 Kevin, P.E.: ‘Integration of aviation lighting system and computer controlled monitoring system,’ IEEE Int. Conf. on Systems, Man and Cybernetics, October 1996, pp. 1132-1137. 5 Granado, J., Chavez, J., Torralba A. and Oria, A. C.: ‘Modeling airfield lighting systems for narrowband power-line communications,’ IEEE Trans. on Power Delivery, 2010, 25, (4), pp. 2399-2405. 6 Smith, C. C.:’Some aspects of airport lighting,’ Electronics and Power, 1970, 16, (3), pp. 85-89. 7 Zhongming, Y., Lo, E., Pong, M.H., Tang Ping, ‘Power quality investigation of cluster of phase controlled rectifiers of airport grounding lighting system,’ The 25th Annual Conference of the IEEE (IECON '99), December 1999, pp. 247-252 8 Bejleri, M., Rakov, V. A., Uman, M. A., Rambo, K. J., Mata C. T., and Fernandez, M. I.: ‘Triggered lighting testing of an airport runway lighting system,’ IEEE Trans. on Electromagnetic Compatibility, 2004, 46, (1), pp. 96-101. 9 Theethayi, N., Rakov, V. A., and Thottappillil, R.: ‘Responses of airport runway lighting system to direct lighting strikes: Comparisons of TLM predictions with experimental data,’ IEEE Trans. on Electromagnetic Compatibility, 2008, 50, (3), pp. 660-668. 10 Fed. Aviat. Admin: Specification for Series to Series Isolation Transformers for Airport Lighting System (150/5345- 47B), Airport Safety and Standards, 2005. 11 Matlab 7.9 (R2009b) and Simulink, The MathWorks, Natick, MA: 2009