Modelling and analysis of CIGRE HVDC offshore multi-terminal benchmark grid

Pegueroles, Jordi,Barnes, Mike,Gomis, Oriol,Beddard, Antony,Bianchi, Fernando Daniel

Abstract

HVDC power transmission systems are being commissioned in the North Sea to link inland power grids with large offshore wind power farms. The growing number of large wind farms is driving the need to design more reliable high power transportation systems, leading to the conception of multi-terminal HVDC grids. These future grids will be purely formed by power electronics converters, the control of which will have to be designed to ensure proper performance and robust operation. This paper presents the analysis of the benchmark system proposed by the CIGRE working group SC B4, focusing on the proper selection of the components models and parameters. The small signal model of the system is first formulated. Then the bandwidth of the different control loops is obtained and the fidelity of the HVDC line model is selected accordingly. Finally, the performance of the benchmark system is studied by means of small signal analysis and compared numerical time series simulation of the non-linear model. © 2015 The Authors. Published by Elsevier Ltd.

Full text

1876-6102 © 2015 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/). Peer-review under responsibility of SINTEF Energi AS doi: 10.1016/j.egypro.2015.11.409 Energy Procedia 80 ( 2015 ) 72 – 82 ScienceDirect 12th Deep Sea Offshore Wind R&D Conference, EERA DeepWind'2015 Modelling and analysis of CIGRE HVDC offshore multi-terminal benchmark grid Jordi Peguerolesa * , Mike Barnesb, Oriol Gomisa, Antony Beddardb and Fernando D. Bianchia aCatalonian Institue for Energy Research (IREC), 08930, Barcelona, Spain bSchool of Electrical & Electronic Enineering, University of Manchester, Manchester, United Kingdom Abstract HVDC power transmission systems are being commissioned in the North Sea to link inland power grids with large offshore wind power farms. The growing number of large wind farms is driving the need to design more reliable high power transportation systems, leading to the conception of multi-terminal HVDC grids. These future grids will be purely formed by power electronics converters, the control of which will have to be designed to ensure proper performance and robust operation. This paper presents the analysis of the benchmark system proposed by the CIGRE working group SC B4, focusing on the proper selection of the components models and parameters. The small signal model of the system is first formulated. Then the bandwidth of the different control loops is obtained and the fidelity of the HVDC line model is selected accordingly. Finally, the performance of the benchmark system is studied by means of small signal analysis and compared numerical time series simulation of the non-linear model. © 2015 The Authors. Published by Elsevier Ltd. Selection and peer-review under responsibility of SINTEF Energi AS. Keywords: offshore HVDC; Small Signal Analysis; Multi-Terminal; * Corresponding author. Tel.: +34 933 562 615; fax: + 34 933 563 802. E-mail address: [email protected] Available online at www.sciencedirect.com © 2015 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/). Peer-review under responsibility of SINTEF Energi AS Jordi Pegueroles et al. / Energy Procedia 80 ( 2015 ) 72 – 82 73 1. Introduction New power transmission systems will be required to connect multiple wind farms located far offshore with onshore connection points. High voltage direct current (HVDC) technology [1] is the main candidate for implementing these new power transmission systems, forming a multi-terminal HVDC (MT-HVDC) grid. Towards the implementation of such systems, the CIGRE SC B4 working group has proposed the use modular multi-level converters (MMC) with overhead lines and undersea DC cables [2]. In a MT-HVDC system [3], the operation of every converter may be reflected to each node of the system, leading to interactions among power converters, and interactions between converters and transmission lines [4]. The analysis of VSC-HVDC with different control parameters and structures has been performed in [5], using a small signal model of the converter. Also, the impact of current controlled DC choppers in MT-HVDC systems has been studied in [6], by using detailed numerical simulation. This paper analyses the stability margins of the control scheme proposed in [2], by means of small signal studies using accurately linearised models of the different elements in a multi-terminal HVDC system. The stability results are compared with a numerical simulation of the non-linear model of the system implemented in SIMULINK/SimPowerSystems. 2. Modelling The system under study is a four-terminal symmetric monopole (േʹͲͲkV) MT-HVDC system, as illustrated in Fig. 2. It connects the offshore wind power plant at F1 and an offshore oil platform at E1 to the onshore nodes B3 and B2, this last one located further inland (labelling of converters is derived from [2]). This benchmark system consists of long overhead lines and cables in series, and HVDC-MMC power converters, in order to study interactions among these elements. Fig. 1. Benchmark DC system proposed by CIGRE. The power converters forming the benchmark system have different control objectives. On the one hand, onshore converters, Cm-B2 and Cm-B3, are converters regulating AC power with droop control of the DC voltage. The droop control modifies the external power set-point of the converter in order to maintain the DC voltage within the operational range (ͳേͲǤͳͷpu). On the other hand, the offshore converters have different control objectives. Converter Cm-F1 accepts the power drawn from the wind farm, and implements a dead-band control of the DC voltage. This is to manage extreme cases; e.g. a fault on the AC side blocking the operation of the droop converters. Finally, the converter Cm-E1 supplies the power demand of the oil platform. This converter does not actively contribute to the DC voltage regulation. Different regulatory specifications for the power converters may exist depending on the country hosting the power stations. However, some minimum operational requirements are shared in those regulations. As a guideline, some typical requirements are defined in [7], requiring the power converter station operate under difference 74 Jordi Pegueroles et al. / Energy Procedia 80 ( 2015 ) 72 – 82 adverse grid conditions, such as variations of the grid frequency and voltage. Moreover, according to [7], the converter must remain stable and connected to the system without tripping for a close-up solid three-phase or any unbalanced short circuit fault for up to 140 ms; i.e. it must have fault ride-through capability. 2.1. Control of a HVDC converter To fulfill the aforementioned requirements and achieve the control objectives of each converter, the CIGRE SC B4 working group has proposed a benchmark control scheme for each case. 2.1.1. Power Control The typical control objective of MT-HVDC power converters is to track an AC power set-point, commonly given by the on-shore transmission system operator (TSO). To accomplish this end, the control scheme depicted in Fig. 2 is proposed by CIGRE. Fig. 2. Control scheme of a HVDC converter. The proposed control scheme relies on a cascaded structure, where the droop control modifies the power reference of the active power control, and the active and reactive power control outputs are the references to the low level current control, which generates the voltage reference for the MMC. In this scheme, the dead band control does not modify the power control reference (as the droop control would), but modifies the power control output. This scheme is valid for both droop and dead-band control, but both controls cannot be active simultaneously. The droop control can be expressed as ܲ෠௞כൌܲ௞ೝ೐೑൅ܭ௞೏ೝ൫ܸ஽஼ כെܸ௞ವ಴൯ሺͳሻ ܲ௞כൌ൫ܲ෠௞כǡܲ௞೘ೌೣǡܲ௞೘೔೙൯ǡ݇אՅǡሺܽǡܯܣܺǡܯܫܰሻൌቐܯܣܺ ܽ ܯܫܰ݂݅ ܽ൒ܯܣܺ ݂݅ ܯܣܺ൐ܽ൐ܯܫܰ ݂݅ ܯܫܰ൑ܽ ǡ and Յൌሼʹǡ͵ǡͳǡͳሽ, ܭ௞೏ೝis the droop gain, ܸ௞ವ಴ is the DC voltage of converter ݇ ǡ ܲ௞ೝ೐೑ is the power set-point of the converter, ܸ஽஼ כ is the nominal voltage of the HVDC grid, and ܲ௞כ is the reference of the power control. From herein and for the sake of clarity, it is assumed that, ݇א Յ unless otherwise stated. 2.1.2. AC voltage Control In addition to active and reactive power control as in Fig. 2, MMC-HVDC converters might provide AC voltage regulation when they are used to either supply isolated electrical systems or when connected to weak AC systems. For these situations, CIGRE proposes a voltage control scheme to regulate the electrical grid and provide the necessary power demand, shown in Fig. 3. It should be noted that this scheme does not provide any means to limit the current when the converter is overloaded neither does it provide any support, active or passive, to the DC grid. Fig.3. Control scheme of a HVDC converter in AC voltage control mode. KV V min V max Vd* - + Vd Oscillator ϴ PID Vabc* Jordi Pegueroles et al. / Energy Procedia 80 ( 2015 ) 72 – 82 75 Converter Cm-E1 uses this control scheme to supply the demand of the offshore oil platform. It is assumed that this can be approximated in the small signal analysis as a constant power control, neglecting the dynamics of the load, in order to simplify the analysis. 2.2. Component model In this paper, two different models are considered for the analysis of the CIGRE benchmark system. On the one hand, non-linear detailed models are used to implement a numerical simulation using SIMULINK Simpowersystems. On the other hand, linearised models of the electrical components such as the power transmission lines, the HVDC converters, the multi-terminal DC grid, and the AC side dynamics are used for the small signal analysis of the system. This subsection describes how to obtain the small signal models. It should be noted that all variables are expressed in the per unit (pu) system. 2.2.1. Modular Multi-level Converter model The power converter is modeled using an average-value model (AVM) based on switching functions, which approximates the system dynamics by neglecting switching details, i.e. insulated gate bipolar transistors (IGBT) are not explicitly represented. The AVM assumes that all internal variables of the MMC are perfectly controlled, all sub-modules capacitors balanced and harmonic currents circulating in each leg are suppressed. The modeling is based on guidelines of [8]; the following equations describe the MMC voltage for each phase ܸ௞௝ ௖ൌݏܽݐ൫ܸ௞௝ כǡܸ௞ವ಴Ȁʹǡെܸ௞ವ಴Ȁʹ൯ǡ ׊݆ൌܽǡܾǡܿ where ୩୨ ୡ is the j-phase voltage at the output of the converter k, ୩୨ כ is the voltage reference for the MMC. For the small signal analysis it is assumed that the MMC is working in the linear region. In the DQ reference frame, the small signal voltages can be expressed as ߂ܸ௞೏೜ ௖ൌ߂ܸ௞೏೜ כǤ ሺʹሻ The MMC controllers used in the detailed numerical simulation has been implemented in the discrete form, using a zero order sample and hold sampled at the switching frequency for the measurements of the continuous time signals. The AC voltage waveform is generated using a zero order sample and hold of the ܸ௞௝ ௖ signal, using a nearest level control (NLC) modulation in order to emulate switching of the sub-modules, i.e. the output AC voltage is a staircase waveform. The DC side of the model (see Fig. 4) is derived using the principle of power balance, where the power injected to the DC side is the power drawn from the AC side minus the power losses of the MMC. Current losses are calculated as ܫ௞೗೚ೞೞൌܴ௞೗೚ೞೞܫመ௞ವ಴ ଶȀܸ௞ವ಴ǡ  ሺ͵ሻ  with ܫመ௞ವ಴ given by ܫመ௞ವ಴ൌ௉ೖಲ಴ ௏ೖವ಴ǡ ሺͶሻ where ܲ௞ಲ಴ is the active power of the MMC ݇ and ܴ௞೗೚ೞೞ is the equivalent resistance of the MMC. Thus, the DC current injected to the equivalent capacitor ܥ௞೐ of the MMC is ܫ௞ವ಴ ௖ൌܫመ௞ವ಴Ȃܫመ௞೗೚ೞೞǤ  ሺͷሻ Fig. 4. DC side model of the MMC. 76 Jordi Pegueroles et al. / Energy Procedia 80 ( 2015 ) 72 – 82 In order to obtain the small signal model of (5), equations (3) and (4) are linearised, obtaining ߂ܫ௞ವ಴ ௖ൌ൬ଵ ௏ೖವ಴ ത ത ത ത ത ത ത ത ൅ʹܴ௞೗೚ೞೞܲ௞ಲ಴ ത ത ത ത ത ത ൰߂ܲ௞ಲ಴െቆ௉ೖಲ಴ ത ത ത ത ത ത ത ത ௏ೖವ಴ మ ത ത ത ത ത ത ത ൅͵ோೖ೗೚ೞೞ௉ೖಲ಴ ത ത ത ത ത ത ത ത ௏ೖವ಴ రቇ߂ܸ௞ವ಴ǡ ሺ͸ሻ where the over-line denotes the equilibrium values in steady state, and ȟ the small signal variables. 2.2.2. Line model When the frequency spectrum of the signals involved in the simulation is not too wide, the assumption of frequency-independent line parameters constitutes a reasonable simplification. In such cases, cascading T circuits is a simple alternative to obtain a state space description of the power transmission line [9]. Fig. 5 shows a power HVDC transmission line represented by connecting short nominal T sections in cascade. Fig. 5. Line model used for linearisation. The number of sections to be used depends on the frequency range of concern. In this study, the frequency range will be determined by the bandwidth of the droop control, which is the system interacting with the power HVDC line. A good approximation of the highest frequency range represented by the cascaded nominal circuits is given by the following equation ݂௠௔௫ൌ ܰ ߨ߁ξܮܥǡ where ܮ and ܥ are the inductance and capacitance per length unit respectively, ܰ is the number of sections and Ȟ is the line length. The resulting linear model of the line can be expressed in the state-space as ௗ ௗ௧ݔ௟௜௡௘ൌ߉௟௜௡௘ݔ௟௜௡௘൅ܤ௟௜௡௘߂ܸ௟௜௡௘ǡ߂ܫ௟௜௡௘ൌܥ௟௜௡௘ݔ௟௜௡௘ǡ ሺ͹ሻ With ݔ௟௜௡௘ൌሾ݅ௗ௖ ଵݒௗ௖ ଵ݅ௗ௖ ଶݒௗ௖ ଶǥ݅ௗ௖ ଶேାଵሿ்ǡ Ȧ defined in the appendix, and ݎൌ߁ ܴ ܰ൅ͳǡ݈ൌ߁ ܮ ܰ൅ͳǡܿൌ߁ ܥ ܰǡ݃ൌ߁ ܩ ܰǡ where ܴǡܮǡܥǡܩ are the resistance, inductance, capacitance and conductance per length unit respectively. Let ߂ܫ௞ൌܻ௞՜௝߂ܸ௞denote the transfer function from the voltage at node ݇ to the current drawn at node݇; i.e. ܤ௟௜௡௘ൌቂଵ௟ͲǥͲቃ் and ܥ௟௜௡௘ൌሾͳͲǥͲሿ. Likewise, let ߂ܫ௝ൌܻ௞՜௝߂ܸ௞denote the transfer function from the voltage at node ݇ to the current injected at node ݆; i.e.ܤ௟௜௡௘ൌቂଵ௟ͲǥͲቃ் and ܥ௟௜௡௘ൌሾͲͲǥͲͳሿ. 2.2.3. DC grid The former line models (7) are used to form a multiple input multiple output (MIMO) system for analysing the small signal multi-terminal system. To form the MIMO system, first it is required to write the nodal admittance matrix as (8), where ȟ୩ and ȟ୩ are the DC current injected in every node and the node voltage respectively; ୩՞୪ǡ്are the admittance line models as defined in (7). ۏ ێ ێ ێ ۍ ߂ܫ஻ଶವ಴ ߂ܫ஻ଷವ಴ ߂ܫிଵವ಴ ߂ܫாଵವ಴ ے ۑ ۑ ۑ ې ൌ൦ܻ஻ଶ՜஻ଷ െܻ஻ଷ՜஻ଶ ͲͲ െܻ஻ଶ՜஻ଷ ܻ஻ଷ՜஻ଶ൅ܻ஻ଷ՜ிଵ െܻிଵ՜஻ଷ Ͳ Ͳെܻ ஻ଷ՜ிଵ ܻிଵ՜ாଵ െܻாଵ՜ிଵ ͲͲെܻ ிଵ՜ாଵ ܻாଵ՜ிଵ൪ ۏ ێ ێ ێ ۍ ߂ܸ஻ଶವ಴ ߂ܸ஻ଷವ಴ ߂ܸிଵವ಴ ߂ܸாଵವ಴ ے ۑ ۑ ۑ ې    ሺͺሻ  Jordi Pegueroles et al. / Energy Procedia 80 ( 2015 ) 72 – 82 77 2.2.4. AC grid The AC grid model is composed by the output impedance of the converter's arms and the series impedance of the interfacing ȟY transformer. This modelling is possible since the measurements of the AC signals (voltage and current) are taken on the primary side of the transformer, connected to the AC grid. The output impedance of the converter and the transformer can be expressed in the DQ reference frame as ௗ ௗ௧ݔ௔௖ൌ߉௔௖ݔ௔௖൅൤ ଵ ௅೗೒ା௅೟ೝ൨்߂ܸ௞೏ ௖ǡ߉௔௖ൌ൦െோ೗೒ାோ೟ೝ ௅೗೒ା௅೟ೝ ߱ െ߱ െோ೗೒ାோ೟ೝ ௅೗೒ା௅೟ೝ൪ǡ ሺͻሻ  with ݔ௔௖ൌቂ߂ܫ௞೏ ௖߂ܫ௞೜ ௖ቃ்ǡ൤߂ܲ௞ಲ಴ ߂ܳ௞ಲ಴൨ൌ቎ଷ௏ೖ೏ ത ത ത ത ത ത ଶଷ௏ೖ೜ ത ത ത ത ത ത ଶ ଷ௏ೖ೜ ത ത ത ത ത ത ଶെଷ௏ೖ೏ ത ത ത ത ത ത ଶ቏ቈ߂ܫ௞೏ ௖ ߂ܫ௞೜ ௖቉൅቎ଷூೖ೏ ത ത ത ത ത ଶଷூೖ೜ ത ത ത ത ത ଶ ଷூೖ೜ ത ത ത ത ത ଶെଷூೖ೏ ത ത ത ത ത ଶ቏ቈ߂ܸ௞೏ ߂ܸ௞೜቉ǡ  where ȟ୩ౚ౧ is the AC grid voltage, ୪୥, ୲୰, ୪୥ǡ ୲୰ are the inductance and resistance of the MMC arm and transformer respectively, ɘ is the AC grid frequency and ȟ୩ౚ౧ ୡ are the converter output AC currents in the DQ reference frame. 3. Small signal multi-terminal system In order to form the complete small signal model, in this section the relations among the models of the components defined in the previous section will be formulated. 3.1. AC dynamics of converter݇ To obtain the transfer function from ȟܲ௞ಲ಴ כtoȟܲ௞ಲ಴, first the closed loop transfer function of the current control and the AC side dynamics can be obtained. The current control loop, as proposed in [2], is a PI control with a decoupling feed-forward term, which can be expressed as a state space system ௗ ௗ௧ݔ௞ು಺ ೎ൌ൤݇݅௖Ͳ Ͳ݇݅௖൨ቈ߂ܫ௞೏ כെ߂ܫ௞೏ ௖ ߂ܫ௞೜ כെ߂ܫ௞೜ ௖቉ǡ ቈ߂ܸ௞೏ כ ߂ܸ௞೜ כ቉ൌݔ௞ು಺ ೎൤݇݌௖Ͳ Ͳ݇݌ ௖൨ቈ߂ܫ௞೏ כ ߂ܫ௞೜ כ቉൅ቈ߂ܸ௞೏ ߂ܸ௞೜቉െቈ ݇݌௖൫ܮ௟௚൅݈௧௥൯߱ ൫ܮ௟௚൅݈௧௥൯߱ ݇݌௖቉ቈ߂ܫ௞೏ ௖ ߂ܫ௞೜ ௖቉ ሺͳͲሻ where ݇݌௖ and ݇݅௖ are the control parameters, and ݔ௞ು಺ ௖ are the integrator states. The small signal power control can be expressed as a state space system as well ௗ ௗ௧ݔ௞಺ುൌ൤݇݅௣Ͳ Ͳ݇݅௣൨ቈ߂ܲ௞ಲ಴ כെ߂ܲ௞ಲ಴ ߂ܳ௞ಲ಴ כെ߂ܳ௞ಲ಴቉ǡቈ߂ܫ௞೏ כ ߂ܫ௞೜ כ቉ൌଵ ௏ೖ೏ ത ത ത ത ത ത ݔ௞ು ೛൅௉ೖಲ಴ ത ത ത ത ത ത ത ത ௏ೖವ಴ మ ത ത ത ത ത ത ത ቈ߂ܸ௞೏ ߂ܸ௞೜቉ǡ ሺͳͳሻ where ݇݅௣ is the power control tuning parameter, and ୩ౡ౅ ౦is the integrator state. Using (2), (9), (10) and (11) it is straight forward to form the closed loop transfer function from ȟܲ௞ಲ಴ כ to ȟܲ௞ಲ಴, denoted as G-ACk, which can be expressed as ݔ௔௖ ௖௟ ൌ߉௔௖ ௖௟ݔ௔௖ ௖௟൅ൣͲǥͲ݇݅௣Ͳ൧்߂ܲ௞ಲ಴ כǡ߂ܲ௞ಲ಴ൌቂଷଶܸ௞೏ ത ത ത ത ଷଶܸ௞೜ ത ത ത ത ͲǥͲቃݔ௔௖ ௖௟ ሺͳʹሻ with Ȧ௔௖ ௖௟defined in the appendix. where ݔ௔௖ ௖௟ൌቂȟܫ௞೏ ௖ȟܫ௞೜ ௖ݔ௞ು಺ ೎ݔ௞಺೛ቃ் , and ୟୡ and ୟୡ are the sum of the converter arm and transformer resistance and inductance respectively. 78 Jordi Pegueroles et al. / Energy Procedia 80 ( 2015 ) 72 – 82 3.1.1. Dynamics with dead band control The dead band control constitutes a non-linear feedback of the DC voltage injected to the current reference. It can be expressed as ܫ௞೏್ൌቐെܭௗ௕൫ܸ஽஼െܸ஽஼೏್ ெ஺௑൯ െܭௗ௕൫ܸ஽஼െܸ஽஼೏್ ெூே൯ Ͳ݂݅ ܸ஽஼൐ܸ஽஼೏್ ெ஺௑ ݂݅ ܸ஽஼൏ܸ஽஼೏್ ெூே ݈݁ݏ݁ ǡ  where ܭௗ௕ is the dead band control gain, the input of the d-axis of the current control is ܫ௞೏್൅ܫ௞೏ כǡ and ܸ஽஼೏್ ெ஺௑ and ܸ஽஼೏್ ெூே are the limits of the dead band region. The linearised model with dead band control can be expressed as ݔ௔௖ ௖௟ ൌ߉௔௖ ௖௟ݔ௔௖ ௖௟൅ܤ௔௖ ௖௟ൣ߂ܲ௞ಲ಴ כ߂ܸ௞ವ಴൧்ǡ  ሺͳ͵ሻ ܤ௔௖ ௖௟ൌ൤ ͲͲͲͲ݇݅ ௣Ͳ െ݇݌௖ܭௗ௕ Ͳെ݇݅௖ܭௗ௕ ͲͲͲ ൨ǡ߂ܲ௞ಲ಴ൌቂଷଶܸ௞೏ ത ത ത ത ଷଶܸ௞೜ ത ത ത ത ͲǥͲቃݔ௔௖ ௖௟  in the appropriate region of operation of ܸ஽஼. 3.1.2. DC dynamics of converter ݇ DC dynamics are defined as the transfer function from ȟܲ௞ಲ಴ to ȟܸ௞ವ಴. To obtain this transfer function, the voltage can be expressed as a function of the current difference ߂ܸ௞ವ಴ൌଵ ௦஼ೖ೐൫߂ܫ௞ವ಴ ௖െ߂ܫ௞ವ಴൯Ǥ ሺͳͶሻ Replacing (6) in (14) and after some simple manipulations, it can be obtained ߂ܸ௞ವ಴ൌଵ ௦஼ೖ೐൫ߓ߂ܲ௞ಲ಴െ߂ܫ௞ವ಴൯ǡߓൌ భ ೇೖವ಴ ത ത ത ത ത ത ത ത ത ାଶோೖ೗೚ೞೞ௉ೖಲ಴ ത ത ത ത ത ത ത ത ଵା భ ೞ಴ೖ೐ቌುೖೌ೎ ത ത ത ത ത ത ത ത ೇೖವ಴ మ ത ത ത ത ത ത ത ത ത ାయೃೖ೗೚ೞೞುೖಲ಴ ത ത ത ത ത ത ത ത ത ೇೖವ಴ ర ത ത ത ത ത ത ത ത ത ቍሺͳͷሻ 3.2. Complete closed loop dynamics Using the previously defined models, the interconnected closed loop system can be build as shown in Fig. 6. The blocks VSC B2, B3, E1, F1 are formed by the transfer function defined in (15); blocks G-ACB2, B3, E1 ,F1 are either transfer functions (12) or (13); DC GRID block is defined in (8). Fig. 6. Small signal model of the multiterminal system. Jordi Pegueroles et al. / Energy Procedia 80 ( 2015 ) 72 – 82 79 4. Results In this section, the performance of the MT-HVDC benchmark system proposed in [2] will be analysed. The small signal analysis results will be compared with the results of a numerical simulation of the detailed system implemented in MATLAB/Simulink and Simpowersystems toolbox. Firstly, the frequency behaviour of the HVDC cable is presented in Fig. 7. The model is a state space representation with 11 states obtained by selecting ܰൌͷ in (7), with the parameters summarized in Table 1. The bode plot of the 200 km DC cable linking Cm-B2 and Cm-B3 is shown in Fig. 7. The model with CIGRE paramters is accurate up to 130~Hz approximately, enough for the frequency range of analysis of this paper. Fig. 7. Cable model comparison with CIGRE values (black) and proposed values (gray) Table 1. Cable parameters used in the model. CIGRE Used values Resistance 0.0110 0.0113 ȳȀ Inductance 2.6150 0.4660 Ȁ Capacitance 0.2185 0.2800 ɊȀ Conductance 0.0550 0.0550 Ȁ As it can be seen, the response of the DC cable presents a resonance at 94~Hz, with the parameters from [2]. However, studies in the line model parameters indicates that other, slightly modified, parameters might be more appropriate in this case. The key difference between the two sets of parameters is that inductance value employed for this work is smaller since it is based on a VSC-HVDC system with a metallic return. With the used values, the resonance is displaced at a frequency of 197.5~Hz, as observed in the light gray line in Fig. 7. Since the interaction among converters is given by the droop control, the dead band control and the DC cables, the bandwidth of these controls loops is obtained by analysing the sigma values of the multi-variable system. Fig. 8 shows the closed loop sigma values, which indicate the bandwidth is approximately 10~Hz. As the DC cable model is accurate up to 10 times this frequency, this model is valid for the analysis. Fig. 8. Maximum sigma values of the closed loop system during normal operation. Fig. 9 shows the closed loop sigma values when converter Cm-F1 is in the dead band control mode. The dead band control modifies the current reference of the AC current loop, achieving a wider control bandwidth than the droop control. As shown by the sigma values, this bandwidth is approximately 40 Hz, still under the frequency resolution of the cable model. 80 Jordi Pegueroles et al. / Energy Procedia 80 ( 2015 ) 72 – 82 Fig. 9. Maximum sigma values of the closed loop system with dead band control operation. To analyse the performance of the benchmark model, two different scenarios are studied: a) converter Cm-F1 AC side trips permanently due to a fault on the offshore AC grid; b) converter Cm-B3 AC side is disconnected as a result of a permanent fault in the AC onshore grid. In both scenarios the initials conditions are identical, ܲ஻ଶ஺஼ൌ ͶͲͲ, ܲ஻ଷಲ಴ൌെͺͲͲǡܲிଵಲ಴ൌͷͲͲǡܲ஻ଶಲ಴ൌെͳͲͲ (minus sign indicates the power is injected to the AC grid). The small signal analysis indicates that the system with two droop control converters presents a faster response than the system with only one droop converter. However, when two droop controls are working in parallel, the transient response of the system to some disturbances, such as the loss of a converter or an AC voltage sag, has a much higher overshoot. This behavior can be observed by the pole location shown at Fig. 10. Scenario a) and b) correspond to fig. 10a and fig. 10b respectively. Fig. 10. CIGRE four terminal benchmark system poles. Table 2. Modes from the CIGRE four terminal benchmark system; With AC side of Cm-F1 blocked Pole Damping Frequency (Hz) -2.39E+01 1.00E+00 3.80 -3.27E+01 1.00E+00 5.20 -3.28E+01 1.00E+00 5.23 -2.39E+01 1.00E+00 5.92 -1.31E+01 ± 3.48e+01i 3.51E-01 11.05 -8.18E+00 ± 6.89e+01i 1.18E-01 16.01 -5.55E+00 ± 1.00e+02i 5.52E-02 20.86 -2.59E+00 ± 1.31e+02i 1.98E-02 49.53 Table 3. Modes from the CIGRE four terminal benchmark system; With AC side of Cm-B3 blocked Pole Damping Frequency (Hz) -2.39E+01 1.00E+00 4.18 -3.27E+01 1.00E+00 5.21 -1.80E+01 ± 5.67E+01i 3.02E-01 9.46 -6.54E+00 ± 9.18E+01i 7.11E-02 14.64 -9.29E+01 1.00E+00 14.79 -1.30E+01 ± 1.11E+02i 1.17E-01 17.72 -2.02E+02 ± 2.37E+02i 6.49E-01 49.53 -1.98E+02 ± 2.88E+02i 5.67E-01 55.57