Assessment of the fibre orientation factor in SFRC slabs

Blanco Álvarez, Ana,Pujadas Álvarez, Pablo,Fuente Antequera, Albert de la,Pialarissi Cavalaro, Sergio Henrique,Aguado de Cea, Antonio

Abstract

The design of steel fibre reinforced concrete (SFRC) structures is evolving towards a new approach that uses correction factors to consider differences between the small-scale characterization specimens and the real-scale elements. Recently, the Model Code 2010 proposed an orientation factor (K) that accounts for the effects of the orientation in the structural response of elements. The present study focuses on the identification of this factor in SFRC slabs with different dimensions. For that, flexural tests on real-scale slabs were conducted and the fibre orientation was assessed with an inductive method. A finite element analysis showed the differences between the experimental curves and the prediction of the Model Code without considering K. Based on the results obtained, a range of values is proposed for K and validated. This study sheds light on possible modifications that this philosophy of design might require to better reproduce the behaviour of slabs.

Full text

Assessment of the fibre orientation factor in SFRC slabs A. Blanco ⇑ , P. Pujadas, A. de la Fuente, S.H.P. Cavalaro, A. Aguado Department of Construction Engineering, Universitat Politècnica de Catalunya, UPC, Jordi Girona 1-3, 08034 Barcelona, Spain article info Article history: Received 17 April 2014 Received in revised form 2 August 2014 Accepted 1 September 2014 Available online 21 September 2014 Keywords: A. Fibres B. Mechanical properties C. Finite element analysis (FEA) D. Mechanical testing abstract The design of steel fibre reinforced concrete (SFRC) structures is evolving towards a new approach that uses correction factors to consider differences between the small-scale characterisation specimens and the real-scale elements. Recently, the Model Code 2010 proposed an orientation factor (K) that accounts for the effects of the orientation in the structural response of elements. The present study focuses on the identification of this factor in SFRC slabs with different dimensions. For that, flexural tests on real-scale slabs were conducted and the fibre orientation was assessed with an inductive method. A finite element analysis showed the differences between the experimental curves and the prediction of the Model Code without considering K. Based on the results obtained, a range of values is proposed for Kand validated. This study sheds light on possible modifications that this philosophy of design might require to better reproduce the behaviour of slabs. Ó2014 Elsevier Ltd. All rights reserved. 1. Introduction Steel fibre reinforced concrete (SFRC) has arisen as an alternative to traditional reinforced concrete (RC) in structural applications that demand materials with tensile stress bearing capacity and ductility. Nevertheless, the fact that fibres are distributed in the mass leads to a behaviour different from that of RC. While in the latter steel rebars tend to be efficiently placed in the section with regard to the cracking plane, in SFRC the orientation of the fibres may not be as efficient. This has a direct effect on the postcracking tensile response, either enhancing or penalising it [1]. Originally, the research conducted by the scientific community focused on the development of constitutive models for the design as well as on the implementation of characterisation tests for the assessment of the performance of the material. Back then, the first codes and guidelines did not incorporate the fibre orientation explicitly in the design. However, more recently numerous studies in the literature reported the big influence of this parameter on the structural response of FRC [2–5], suggesting the need to use correction factors to account for the differences between the small-scale characterisation specimen and the real-scale element. In this regard, the Model Code 2010 [6] proposed an orientation factor that affects the design serviceability and ultimate residual strengths when favourable or unfavourable fibre orientations are experimentally verified. Examples of advantageous preferential orientations caused by the geometry are slabs and plates. The casting direction of these elements is usually perpendicular to their largest surface. Moreover, due to their low height to width ratio, the concrete poured presents mainly a horizontal movement on the formwork. Since the fibres tend to align perpendicularly to the cast direction and in the same plane of the concrete flow, the number of fibres crossing the failure plane increases. In line with that, a recent study by Blanco et al. [7] revealed an enhanced sectional response in this type of element as the width increases. The orientation factor may vary for the same type of element depending on the several aspects that modify the fibre orientation (the fresh-state properties of the concrete after mixing, the production process, the type of fibre and the geometry of the formwork) [8–10,2]. Although this new philosophy represents a paramount step forward in the integration of fibre orientation in the design, no specific guidelines on the quantification of such orientation factor is proposed. This fact reveals the need for further studies about the orientation in different typologies of structures and about the structural response obtained [11]. Furthermore, several questions yet must be answered. For instance, how the orientation factor should be calculated? Should the dimensions of the structure be considered when determining the effect of a favourable fibre orientation? How does the fibre orientation in the slabs and the orientation factor change with the dimensions of the element? Is the use of the same orientation factor for all strain levels enough to reproduce the behaviour of real-scale elements or different orientation factors are required depending on the strain reached? Considering the above, this paper focuses in the assessment of the orientation factor for SFRC slabs with different dimensions, http://dx.doi.org/10.1016/j.compositesb.2014.09.001 1359-8368/Ó2014 Elsevier Ltd. All rights reserved. ⇑ Corresponding author. Tel.: +34 93 401 7347; fax: +34 93 401 1036. E-mail address: [email protected] (A. Blanco). Composites: Part B 68 (2015) 343–354 Contents lists available at ScienceDirect Composites: Part B journal homepage: www.elsevier.com/locate/compositesb maintaining constant other parameters such as casting procedure and type of SFRC. For that, flexural tests on real-scale slabs were performed and the fibre orientation was assessed. Furthermore, orientation factors are proposed for the design of the slabs tested and then validated with a finite element analysis (FEA). This study represents a contribution towards a more robust design of SFRC elements. It provides an example of deduction of orientation factors and sheds light on additional modifications that this philosophy of design requires to better reproduce the behaviour of slabs. 2. Experimental program Few examples of tests on real-scale SFRC slabs with different width and subjected to condition similar to the found in practice may be found in the literature. Therefore, an experimental program was conducted with the aim of assessing the mechanical response observed and to estimate the fibre distribution in this type of elements. The following sections present a description of the experimental program. 2.1. Specimens Slabs with 3.0 m of length, 0.2 m of thickness and widths of 1.5 m, 2.0 m or 3.0 m were tested. These sizes were selected to reproduce possible dimensions of SFRC suspended slabs that may be used in buildings. According to the notation adopted, the slabs were either small (S), medium (M) or large (L) depending on their width (1.5 m, 2.0 m or 3.0 m, respectively). Two slabs were cast and characterised for each size, making a total of six slabs. The letter A or B was appended to the notation in order to identify the elements of each pair (e.g. S_A or L_B) (see Table 1). 2.2. Materials and concrete mix The concrete mix used to cast the slabs contained 40 kg/m 3 of hooked-end steel fibres Dramix Ò RC80/50BN and was designed to obtain a high fluidity, in order to minimise the vibration required. Three batches with the same mix proportion were produced to cast all slabs in three different days due to limitation in the mould available. Table 2 summarises the details of the concrete mix used. The slabs L_A and M_A were cast with the first batch, the slabs L_B and M_B were produced with the second batch and, the slabs S_A and S_B were cast with the third batch. The mix was poured from the centre of the formwork (see Fig. 1) in all cases to avoid introducing additional variables to the study. Once the pouring of the material was finished, the walls of the formwork were vibrated externally during approximately 20 s to ensure a uniform distribution of the concrete in the mould. The average results at 28 days for the modulus of elasticity (E cm ), compressive strength (f cm ) and residual flexural strengths (f Ri ) are presented in Table 4. These properties were obtained according with the standards UNE 83507:2004 [12], UNE 83316:1996 [13] and EN 14651:2005 [14], respectively. The results of E cm and f cm correspond to the average of three specimens; whereas the values of f Ri were obtained with the average of six beams. Notice that for the third batch only three beams were tested and one of them failed due to malfunctioning of the crack mouth opening displacement (CMOD) control device. The scatter observed in the results is high but smaller than the 20% reported in the literature [15,16]. The comparison of the residual flexural tensile strengths show that the first and the second batches present almost identical average values, whereas the third batch exhibits lower values. Given that the concrete mix used is the same and the other tests (compressive strength and modulus of elasticity) provide similar results for all batches, the difference in the post-cracking performance of the third batch is attributed to the reduced number of specimens tested. Therefore, hereinafter it will be assumed that the performance of the third batch is equivalent to the others. 2.3. Mechanical test setup and procedure The slabs were placed over steel trestles located at the borders, extending over the central half of the sides (see Fig. 2). This setup was chosen to obtain a hyperstatic support condition that allows an internal redistribution of forces and the contribution of fibres in more than one direction, like in suspended slabs. The load was applied at the center of the element by means of a piston connected with a servo-hydraulic jack. Neoprene sheets (200 200 20 mm) were placed between the piston and the top of the slab to ensure full contact with the loading surface. To limit the contact area and to guarantee a more uniform load transmission to the supports, neoprene sheets were also placed between the slab and the steel trestles. In this case, the layer of neoprene was 2 cm thick, 20 cm wide and 1.5, 1 or 0.75 m long depending on the length of the supported side. The load applied (P), the displacement of the piston and the deflection (d) at different locations of the slab were measured throughout the test. The assessment of the deflections was performed with 14 magnetostrictive displacement transducers located at the axes of the element, at the supports and in two diagonally opposed corners to evaluate the expected raising of these points. Fig. 3 indicates the exact position of the displacement transducers on the top surface of the slabs. In the shortest direction the distance abetween the transducers was variable depending on the width of the slab, being 20 cm for slabs S, 32 cm for slabs M and 53 cm for slabs L. The displacement transducers placed in the longest direction were separated 53 cm apart. Notice that no transducer was placed at the centre of the slab since this position is occupied by the piston of the jack. Therefore, in order to assess the deflection at the centre, the measurements from the other transducers were used. The analysis of the data obtained during the test indicated that a linear relation (R 2 = 0.999 in all cases) exists between the displacement and the position of the transducer regarding the symmetry axes. Considering that, an extrapolation of a linear regression was used to estimate the expected movement at the centre of the slab. To derive the deflection, this movement should be corrected by subtracting the displacement from the neoprene layers at the Table 1 Dimensions of the slabs. Notation Dimensions [m] S_A and S_B 1.5 3.0 0.2 M_A and M_B 2.0 x 3.0 0.2 L_A and L_B 3.0 3.0 0.2 Table 2 Concrete mix. Materials Characteristics Quantities [kg/m 3 ] Gravel (6/15 mm) Granite 520 Gravel (2.5/6 mm) Granite 400 Sand (0/3 mm) Granite 510 Cement CEM I 52,5 R 350 Filler Marble dust 300 Water – 178 Superplasticizer Adva Ò Flow 400 12 Fibres Steel fibres 40 344 A. Blanco et al. / Composites: Part B 68 (2015) 343–354 supports (calculated as the average of the readings of transducers T1, T6, T12 and T7 shown in Fig. 3). The tests were performed with displacement control of the jack, following a load procedure divided in two sequential stages. At the first stage, a smaller displacement rate was used to allow a clear appreciation of the arising and the propagation of cracks. Considering that the flexibility of the elements tested increases with the width, displacement rates of 0.15 mm/min, 0.20 mm/min and 0.25 mm/min were adopted for slabs S, M and L, respectively. Once the extent of the major cracks had stabilized, the rate was increased to assess the behaviour of the slabs for high displacement values. Values of 0.20 mm/min, 0.30 mm/min and 0.40 mm/ min were used in the second stage for slabs S, M and L, respectively. The slabs were loaded until the stabilization of the softening stage was observed and the rate of softening was approximately constant. As a general criterion, the tests were stopped once the post-peak load reached between 65% and 70% of the maximum load. This approach intended to provide the characterisation of the behaviour of the slabs for large deflection without approaching the collapse, which could compromise the posterior assessment of the crack pattern. 2.4. Fibre distribution assessment The assessment of the fibre distribution in the slabs was conducted after the mechanical tests by means of a non-destructive magnetic method [17–19] applied on cubic specimens extracted from the elements. This method is based on the measurement of the alterations produced in a magnetic field when the SFRC specimen is placed within a coil. Such alterations are evaluated in the three main axes of the specimen. The summed measurements is related with the fibre content, whereas the differences among measurements indicate the alignment of the fibres in each direction. This method was already applied to real-scale structures to assess fibre content and fibre orientation [20–22]. To obtain specimens suitable for the test, cylindrical cores with 200 mm of height and 225 mm of diameter were drilled from the slabs (see Fig. 4a). Their location and orientation with regards to the sides of the slabs were properly marked before the extraction. The cylindrical cores were then cut into 150 mm cubic samples (see Fig. 4b and c), keeping the resultant sides parallel to the sides of the slabs. First, the lateral edges of the cylinders were eliminated to obtain 150 150 200 mm prisms. Afterwards, the 25 mm thick slices at the top and bottom of the prism were cut. The number of cores drilled ranged from 12 to 18 per slab, depending on the size of the element. The position of extraction was defined under the criterion of obtaining at least two samples close to each other, maximizing the area covered. Since the casting date for slabs S_A and S_B is the same and the load–deflection curves are very similar, only the former was characterised. In order to assess the differences in terms of fibre distribution in the real-scale and small-scale elements, the beams used in the Fig. 1. (a) Concrete pouring in the centre of the slab and (b) flow of concrete to the edges. Fig. 2. Setup for slab (a) S, (b) M and (c) L. 10 cm Displacement transducer Symmetry axis 10 cm 10 cm 10 cm a a 53 cm 53 cm 10 cm T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 Axis 1 Axis 2 y x Fig. 3. Location of the displacement transducers on the top surface of the slab. A. Blanco et al. / Composites: Part B 68 (2015) 343–354 345 bending tests were also characterised. The inductive method was applied in cubic specimens extracted as indicated in Fig. 5. Notice that the cut was performed at a distance of 75 mm from the edges to avoid the zone cracked during the bending test and to reduce the influence of the wall-effect close to the extremities of the mould. The average fibre orientation in a certain direction (i)is evaluated through the orientation number ( g i ). This parameter corresponds to the average projected length of all fibres along direction i, divided by the total fibre length. As a result, the values of g i may range from 0 (when fibres are parallel to the direction i) to 1 (when fibres are perpendicular to the direction i). This parameter is also related with the mechanical performance at a sectional level in case a crack appears perpendicularly to i.Itis expected that the efficiency of the fibres and the post-cracking response would reduce as g i approaches 0. On the contrary, the efficiency and the response would increase as g i approaches 1. For the cubic specimens tested with the magnetic method, the orientation number in the three main axes (X,Yand Z) may be obtained through Eq. (1) proposed by Cavalaro et al. [19]. This equation considers the inductance measurements taken in the corresponding axis ( D L i ), the sum of the measurements in the three axes ( D L) and a coefficient ( c ) that accounts for the aspect ratio of the fibre. According with the formulation proposed by the same authors, the contribution of the fibres (C i ) was calculated with Eq. (2) as the proportion of the summed orientation numbers observed in each axis. It is important to remark that the coordinated system adopted in the slabs has Xand Yaxes within the plane of the element, whereas in the beams Xis parallel to the length. In all of them, the Zaxis coincides with the casting direction. g i ¼1:03 ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi D L i ð1þ2 c Þ D L c D Lð1 c Þ s0:1 for i¼X;Y;Zð1Þ C i ¼ g i g X þ g Y þ g Z for i¼X;Y;Zð2Þ In a perfectly isotropic SFRC, the g i measured with the inductive method in the three main axes tend to 0.5. On the other hand, studies performed by Torrents et al. [18] and Galeote [23] in cores extracted from the central part of beams used in the flexural tests suggest an anisotropic fibre distribution with an orientation number close to 0.6 in the direction parallel to the axis of the beam and values between 0.3 and 0.4 in the other orthogonal directions. It is important to remark that, when the experimental program was performed, the inductive method proposed by Torrents et al. [18] was capable of assessing the fibre orientation only in the three axes parallel to the sides of the cubic cores. Therefore, a general criterion was established for the extraction of the cores from the slabs and the small-scale beams. Since the formwork plays an important role in the fibre distribution, it was decided that in all cases the cubic cores would have the sides parallel to the formwork. This would provide a clearer picture of the influence of the formwork and simplify the definition of a fibre distribution pattern. Despite the advantages of this criterion, it also has drawbacks. In case the cracks in the slabs are not parallel to the sides of the formwork, the orientation measured would not necessarily correspond to that found perpendicular to the cracks. Consequently, any intent to justify the differences in terms of the structural response based on the orientation number would require a conversion of the orientation measured parallel to the formwork to that expected perpendicularly to the cracks. For that, a simplified approach was proposed and applied, as described in Section 5. Fig. 4. (a) Detail of the core drilling, (b) cylindrical cores extracted, (c) cubic specimens and (d) cutting procedure. Fig. 5. Cutting procedure to obtain cubic specimens from the beams. 346 A. Blanco et al. / Composites: Part B 68 (2015) 343–354 3. Results and discussion 3.1. Crack patterns Fig. 6 shows the crack pattern observed after testing the slabs. In general, main cracks (thicker black lines) and secondary cracks (thinner grey lines) are observed. The former are the first to be observed during the test, marking a change in the stiffness of the element. They usually extended from the point of load application to the end of the supports, presenting openings several times bigger than those of the secondary cracks. This is consistent with the yield line theory and the experimental results from the literature [24]. The secondary cracks became visible as a result of an internal redistribution of stresses once bigger displacements were applied. An increase in the number of secondary cracks is observed as the width increases. In other words, the redistribution capacity increased with the width. It is also important to remark that the bigger number of main cracks observed in the slabs M_B and L_B suggest that they are more like to exhibit a post-cracking behaviour different from their corresponding pairs (M_A and L_A). 3.2. Load–deflection (P–d) curves Fig. 7 shows the experimental results in terms of the vertical load versus the deflection estimated at the centre of the slabs. A considerable difference in the structural response of slabs S, M and L was expected due to variation in the size of the elements. However, the average maximum loads for slabs S, M and L are 335.5 kN 313.5 kN and 288.6 kN, respectively. The maximum load exhibited by the slabs S is 16.3% higher than the average of slabs L, even though the width of slabs L is 100% bigger than that of slabs S. These results suggest that the fibre reinforcement allowed the larger slabs (M and L) to reach load levels close to those of the slabs S, despite the increase in the width. It is evident that the bearing capacity of the steel fibres as the only reinforcement compensates for the influence of the geometry, providing a ductile behaviour and reducing the differences regarding the maximum load reached during the test. Another parameter that indicates the structural contribution of the fibres and the ductile behaviour of SFRC is the high residual load in comparison with the maximum load reached during the test. In the case of the slab L_A the residual load is 217.7 kN for the maximum deflection reached (68.2 mm) whereas the slab L_B presents a residual load equal to 184.5 kN for the maximum deflection reached (47.8 mm). These values correspond to 73% and 66% of the highest load measured for each of them. The curves also reveal that the pairs of slabs present a similar behaviour for small deflections. However, the differences grow with the deflection and the level of damage produced. For example, the values measured in the slabs L for 1 mm only differ by 0.7%; Fig. 6. Detailed crack patterns of slabs (a) S_A; (b) S_B; (c) M_A; (d) M_B; (e) L_A and (f) L_B. A. Blanco et al. / Composites: Part B 68 (2015) 343–354 347 whereas for 20 mm and 40 mm the difference increases up to 6.5% and 25.7%, respectively. The reason for the increasing difference in load values with large deflections may be the fibre reinforcement itself. Before cracking occurs, the response of the slabs of each pair is almost identical since their performance and the first cracking appearance depend on the concrete matrix properties. Nevertheless, after the first crack appears, the development of new cracks depends on the distribution and orientation of the fibres in the concrete matrix. This means that dispersions will lead to the development of different crack patterns, ultimately producing a variation of the structural response. As mentioned in Section 3.1, this is more evident for the pair of slabs M and L that present either 4 or 5 main cracks. On the contrary, the pair of slabs S has similar behaviour justified by almost the same crack pattern. 3.3. Fibre distribution The results of the inductive method for the fibre distribution are presented in Fig. 10 in a map with the location of each specimen in the slab. The circumscribed number shows the reference used to identify the cores. The fibre distribution is represented through the orientation number in parenthesis and the contribution of the fibres in percentage (blue values were obtained along Xaxis and red along Yaxis). Notice that the remaining percentage to complete 100% equals the proportion of fibres placed along the Z axis. The results suggest a preferential orientation perpendicular to the casting direction (Zaxis), as expected due to the geometry of the element and the casting procedure. Furthermore, other preferential orientations are detected near the walls of the slab where the fibres are aligned parallel to the boundaries (see specimens located near the edges in all of the slabs of Fig. 8). Such outcome is the result of the wall-effect of the formwork [25–27]. As a general trend, specimens located near the centre of the slab present similar orientations in both axes. The fibre orientation changes at increasing distance from the casting point (see specimens 6, 5, 4 and 2 of slab S_B in Fig. 8a). The cause of this result is related with the extensional or radial flow of concrete, illustrated in Fig. 9. According to the latter, the velocity profile exerted by the movement of concrete generates forces that cause the fibres to drift, rotate and align perpendicular to the direction of the flow. Consequently, they tend to change their orientation while moving from the pouring point (at the centre of the slab) towards the edges of the slab, as shown in Fig. 9. This becomes more evident as the flow distance covered by the SFRC increases. Such observation is consistent with the experimental results obtained here and with other from the literature in which the flow is governed by extensional stresses [8,28,4]. Due to the combination of the wall-effect and the extensional flow, three main zones of orientation may be defined in each slab according to Fig. 10. In the central zone, a similar alignment of fibres may be assumed in both axes, whereas a tendency of preferential orientation parallel to the edges is observed in the most external zone. The intermediate zone marks a change between both conditions. In the random slab of Fig. 10, a characteristic orientation is indicated by a range of values corresponding to the fibre alignment measured in the experimental program. The range is defined by the second quartile (the lowest value) and the 95th percentile (the highest value) of the results of the specimens from all slabs located in the same zone. Notice that the length of the external zone is the average of the distances containing the cores from the edge (usually between 32 and 36 cm). In the central zone a double condition depending on the length L 1 (where L 1 6L 2 ) of the slab is considered. This double condition takes into account that in a narrow slab the distance covered by the concrete flow is shorter in one direction. In such case, the concrete flow would reach the edges in one direction much earlier than in the other direction, raising the level of the concrete and affecting the upcoming concrete flow. This creates a new border acting as a wall that would change the orientation of the fibres, thus reducing the extent of the central zone. Therefore, the length of the central zone is the minimum value between 0.3L 1 and 60 cm. On the right side of Fig. 10, an illustrative representation of the alignment along the Xaxis in a cross section is depicted. This evolution corresponds to the tendency of the fibres to orientate perpendicular to the flow of concrete as they advance from the centre to the edges. Notice that the proposed division of the slabs in zones responds to the analysis of the results obtained for a certain casting procedure and a limited number of geometries studied. The annotation of the zones proposed could be improved by further research on different geometries. Moreover, the pattern described may change if other casing procedures were performed. The average orientation numbers ( g i ) in the three directions X,Y and Zare presented in Table 4 for the slabs and the beams used in the bending test. For the slabs, the average of the results in each zone indicated in Fig. 10 was performed. This procedure intends to avoid that a zone in which more cores were extracted would affect the average more than zones with a smaller number of extracted cores. In the case of the beams, the average of 12 cubic specimens cut from 6 beams was considered. As observed in previous works from the literature, the smallest orientation number are obtained along the casting direction (Z axis). This may be attributed to the flow of concrete during the filling of the moulds and the effect of vibration applied that tend to align the fibres in the horizontal plane. For the beams, the highest orientation number is obtained along the length (Xaxis) probably because of the clear flow restrictions and the marked influence of the wall-effect in this case. Smaller values are obtained in all slabs since an extensional flow is evident and the wall-effect from the Fig. 7. P–dcurves for slabs: (a) S, (b) M and (c) L. 348 A. Blanco et al. / Composites: Part B 68 (2015) 343–354 lateral of the moulds influences a more reduced proportion of the element. Although Table 4 provides a general view of the fibre distribution, the expected repercussion in the structural response is not so clear in the case of the slabs. In fact, none of the axes used for the assessment of the orientation number coincide with the cracking plane observed experimentally. This only occurs for the beams whose measurements in the Xaxis are approximately perpendicular to the cracks observed during the bending test. Therefore, to obtain a clearer view of the influence of the fibre distribution in (a) (b) (c) (d) (e) S_B M_A M_B L_A L_B Fig. 8. Fibre orientation in specimens of slabs: (a) S_B, (b) M_A, (c) M_B, (d) L_A and (e) L_B. Edge of the slab Direction of the low Flow velocities Rotation of the ibre Fibre Formwork Radial low Fig. 9. Rotation of fibres while moving from the centre of the slabs to the edges. A. Blanco et al. / Composites: Part B 68 (2015) 343–354 349 the structural response, it would be interesting to estimate the orientation number in the axis perpendicular to the cracks of the slabs. Given that such estimation is not mathematically feasible with the results of only three orthogonal axes; a simplified approach was used to derive a fair comparison between the fibre distribution in the beams and in the slabs regarding the cracked plane. The maximum angle (h) formed between the resulting vector of the orientation number and the direction perpendicular to the crack is estimated. Table 4 shows the results obtained considering that the average angle of the cracks with the Xaxis is 60°,57°and 55°for slabs S, L and M, respectively. Notice that the angle formed is twice as big in the slabs in comparison with the beam. This indicates that fibres would tend to be more efficiently aligned in the latter than in the former. Consequently, an overestimation of the experimental mechanical response of the slabs would be expected if the constitutive equations obtained from the bending test were used in numerical models. 4. Numerical simulation 4.1. Description of the FEM model A numerical simulation of the structural behaviour was performed and compared with the experimental results in order to evaluate the possible overestimation indicated in the previous section. The numerical simulation was conducted in the finite element software ATENA 4.3.1g [29], which includes specific material models for concrete and elements for a 3D analysis. This was essential in the present study since redistribution of moments and the contribution of fibres in more than one direction occur during the test. The tensile behaviour of concrete was simulated with non-lin- ear fracture model combined with the crack band method and the smeared crack approach. In tension, the constitutive model included in the Model Code 2010 [6] was selected. Notice that in this case the orientation factor Kwas considered 1.0 so that no effect of differential orientation was taken into account. In other words, it is assumed that the sectional responses of the slabs and of the specimen characterised in the bending test are equivalent. The maximum crack opening is related with the ultimate strain ( e u ) considered in the constitutive model. The limitation of the contribution of the fibres was implemented in accordance with the recommendations from the Model Code 2010. Consequently, a stress of 0 is resisted once the strain surpasses e u .Notice that a maximum e u of 20‰is also established for elements subjected to bending. Therefore, in case the formulation from the Model Code 2010 provided a value for e u bigger than this limit, the constitutive curve was considered only up to a strain of 20‰. Hence, the part of the curve that corresponds to higher strain levels was neglected and a remaining residual strength of 0 was assumed. The crack band size was automatically calculated by ATENA and the characteristic size used to estimate the strain was defined according with other works from the literature. According to de Montaignac et al. [30] the recommended values of the characteristic length (l c ) to simulate the structural performance of SFRC without traditional reinforcement vary from half the height (h/2) to twice the height (2h) of the element simulated. Considering this, the influence of l c on the results of the FEM was analysed prior to selecting one for subsequent analyses. Such values are 100 mm and 200 mm, which correspond respectively to half the full height (h/2) and the height (h) of the slabs tested. The P–d curves obtained with both characteristic sizes for the models of slabs S and L are shown in Fig. 11. The results reveal that the influence of the selected values of l c on the P–dcurves is almost negligible. Such outcome was previously reported by Kooiman [31] that observed a small sensitivity of the load-bearing capacity of SFRC to the values of l c , particularly for high deflections. Based on the results obtained and the findings of previous studies from the literature [31,32], the value of l c equal to h/2 (100 mm) was considered for the present study. The neoprene sheets placed at the loading point and at the support were simulated using the properties obtained experimentally in the tests of the EN 1337-3:2005 [33]. A linear elastic regime according with Hooke’s law was assumed due to the small values of compressions and strains reached at the supports during the simulations. In addition, the friction between the slab and the support and the mixed stress state produced as a result of it were also simulated. Simply supported conditions were imposed by restraining the vertical displacement of the bottom face of the neoprene located in the supports. The load case consisted of a vertical displacement acting simultaneously at all nodes on the top face of the neoprene in contact with the piston. Table 5 shows the material properties of the SFRC, the neoprene and the interface elements used. Notice that the modulus of elasticity and the compressive strength of the SFRC correspond to the results obtained in the experimental program shown in Table 3. The finite element mesh was composed by tetrahedral solid elements. The size of the mesh was defined with the aim of assuring the accurate reproduction of the localised cracking of SFRC without compromising the calculation time since several models would be processed to obtain the constitutive equation that best fits the experimental results. For that reason, the possibility of simulating a reduced model with only one quarter of the slabs was assessed. The preliminary analysis showed that the P–dcurves for the complete slab and for the quarter of the slab are practically identical. L1 42-47% 31-52% 42-55% 35-53% 65-77% 20-27% 65-77% Central zone External zone Intermediate zone 35 cm 35 cm l=min ( 0.3·L1; 60 cm ) l=min (0.3·L1; 60 cm) L2 20-27% 20-27% 65-77% 65-77% Evolution of ali g nment alon g horizontal axis 20-27% X Y Alignment of ibres [%] Fig. 10. Division of slabs in zones depending on fibre orientation. 350 A. Blanco et al. / Composites: Part B 68 (2015) 343–354 Based on such outcome [7], the reduced model was selected. Notice that the displacement perpendicular to the symmetry planes was also restrained. 4.2. Results Fig. 12 shows the P–dcurves estimated with the constitutive equation from the Model Code 2010 (for K= 1.0) and the experimental results. The general tendency observed is a significant overestimation of the experimental curves, which becomes more evident as the width of the element diminishes. For instance, the maximum load measured during the test of slabs L and S represent 53% and 46% of the estimated response, respectively. The results reveal that the direct application of the constitutive model obtained from the flexural tests of small beams to the design of SFRC slabs under the assumption that the fibre orientation is the same in both elements may lead to unsafe predictions of the structural response. This confirms the hypothesis presented in Section 3based on the results of the inductive method. Such outcome reinforces the need for correction factors that take into account differences between the small-scale specimen and the real-scale element. Therefore, according with the design philosophy proposed in the Model Code 2010, the orientation factor (K) is assessed for the case of the slabs tested. 5. Orientation factor for SFRC slabs Following the philosophy of the Model Code 2010 to account for the fibre orientation, the values of r 2 and r 3 from the bending test were divided by K. Therefore, the constitutive equation is obtained by applying this procedure to the values presented in Table 5. The modified constitutive equation was then used in the finite element simulations. Fig. 11. Influence of the lc on the P–dcurves provided by the model: (a) slab S and (b) slab L. Table 3 Modulus of elasticity, compressive strength and residual flexural strengths at 28 days. Property First batch Second batch Third batch Average [MPa] CV [%] Average [MPa] CV [%] Average [MPa] CV [%] Modulus of elasticity E cm 29,030 0.96 28,640 2.79 30,160 2.20 Compressive strength f cm 46.73 0.77 49.46 0.59 46.77 2.54 Residual flexural strengths f L 5.42 7.05 5.29 2.23 3.76 7.96 f R1 6.25 12.50 6.13 13.71 3.75 22.29 f R2 7.02 12.39 7.04 15.77 4.24 17.91 f R3 7.05 11.59 7.08 15.05 4.30 15.88 f R4 6.62 12.08 6.62 12.08 4.17 15.68 0 100 200 300 400 500 600 700 0 5 10 15 20 Load P[kN] Delection δ[mm] Experimental S_MC_K=1.00 S_MC_K=3.10 010203040 Delection δ[mm] Experimental M_MC_K=1.00 M_MC_K=2.50 0102030405060 Delection δ[mm] Experimental L_MC_K=1.00 L_MC_K=2.64 Fig. 12. P–dcurves from simulation with the MC 2010 with Kequal to 1.0, obtained in the numerical fit (grey area) and obtained from the inductive method for slabs (a) S, (b) M and (c) L. A. Blanco et al. / Composites: Part B 68 (2015) 343–354 351